Bedienungsanleitung APC ACRP101

50 Seiten 0.99 mb
Download

Zur Seite of 50

Summary
  • APC ACRP101 - page 1

    InRow ® RP Chilled W ater/Direct Exp ansion — 50/60 Hz T echnical Dat a AIR-COOLED ACRP100 ACRP101 ACRP102 CHILLED W A TER ACRP500 ACRP501 ACRP502 ...

  • APC ACRP101 - page 2

    American Power Conversion Legal Discla imer The information presented in th is manual is not wa rranted by the American Power Conversion Corporation to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development pla n. Therefore, American Power Conversion Corpo ...

  • APC ACRP101 - page 3

    Content s InRow RP Technical Data Manual i Overview ....................................... ................................... 1 Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Room Air Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Configuration . . . . . . . . . . ...

  • APC ACRP101 - page 4

    InRow RP Technical Data Manual ii InRow RP Models ..................... ...................... ................. 9 Chilled Wate r Interior Compon ents (front of uni t) . . . . . . . . . . . . 10 Air-cooled Interior Comp onents (front of unit) . . . . . . . . . . . . . . 12 Air-cooled Interior Components (back of un it) . . . . . . . . . . . . . . 1 ...

  • APC ACRP101 - page 5

    1 InRow RP Technical Data Manual Overview The modular , row-based computer room cooling system offers ef ficient, predictable, and economical cooling for a variety of spaces. Critical environmen tal requ irements now reach far beyond the confines of the traditional data center or computer room to encompass a lar g er suite of applications, referred ...

  • APC ACRP101 - page 6

    InRow RP Technical Data Manual 2 Scalable Solution for Critical Environment s InRow Advant ages The row-based solution improves energy efficiency and cooling ability in a number of ways. First, the InRow RP draws air directly from the hot aisle, allowing the InRow RP to take advantage of higher heat tran sfer efficiency due to higher temperature di ...

  • APC ACRP101 - page 7

    3 InRow RP Technical Data Manual Hot Aisle Containment System Modular ceiling tiles and doors can b e used to enclose the hot aisle. This increases the densities that can be handled in a single rack enclosure by eliminating mixing of hot and cold ai r streams. This m ethod, called load neutral ization, removes the heat from the hot aisle, cools it, ...

  • APC ACRP101 - page 8

    InRow RP Technical Data Manual 4 S t andard Features Insulated Cabinet The frame is constructed of 1.5 mm (16 gauge) formed steel for maximum strength. Cabinet is serviceable from the front and rear . All exterior pan els and corner posts on the frame are powder coated for durability an d an attractive finish. Front and rear exterior panel are cons ...

  • APC ACRP101 - page 9

    5 InRow RP Technical Data Manual Dual Position Float Condensate Management The pump is factory wired and piped internally to the condensate drain pan and humidifier outlet. The pum p is capable of pumping a maximum of 18 m (60 ft) at 0.009 l/s (8.45 GPH), which may include a maximu m lift of 3.5 m (11.5 ft) of head. A dual position float is in clud ...

  • APC ACRP101 - page 10

    InRow RP Technical Data Manual 6 Optional Features Cable W ater Detector A leak detection cable is placed on the floor or subfloor around all possible leak sources. If water or other conductive liquids contact the cable anywhere along its length, the microprocessor controller announces the leak visually , audibly , and across the network. The 6.1 m ...

  • APC ACRP101 - page 11

    7 InRow RP Technical Data Manual Microprocessor Controller Microprocessor Controller The microprocessor controller is standard on each system. The controller provides precision control for the demanding requirements of: • Computer rooms • T elecommunication facilities • Clean rooms • Power equipment • Medical equipment rooms • LAN/W AN ...

  • APC ACRP101 - page 12

    InRow RP Technical Data Manual 8 Alarms The microprocessor controller shall activate a visible and audible alarm in the following occurrences: • Cool Fail • Rack inlet te mperature violat ion • Rack inlet temperature sensor fault • Air filter clogged • Air filter run hours exceeded • Filter DP sensor failure • Supply air sensor fault ...

  • APC ACRP101 - page 13

    9 InRow RP Technical Data Manual InRow RP Models  Hinged rear doors  Casters (all swivelin g)  Side panel lo ck  Door handle and l ock  Removable side panel  Display interface  Adjustable leveling foot  Hinged front door na182 4a ...

  • APC ACRP101 - page 14

    InRow RP Technical Data Manual 10 Chilled W ater Interior Components (front of unit)  Electric heater (for reheat)  Electrical panel  Fan  Supply temperature sensors  Fan guard  Main feed breakers  Humidifier  Ladder diagrams  Condensate drain pan  User interface connectors  Condensate pump  Supply humidity senso ...

  • APC ACRP101 - page 15

    11 InRow RP Technical Data Manual Chilled W ater Interior Components (back of unit)  Chilled w ater coil  Rear doors  Chilled water con trol actuator  Air filters  Chilled wa ter three-way valve body  Return humidity sensor  Flow meter  Return temperature sensor  Pipe chase na210 5a ...

  • APC ACRP101 - page 16

    InRow RP Technical Data Manual 12 Air-cooled Interior Component s (front of unit)  Electric heater (for reheat)  Main circuit breaker  Condensate drai n pan  Fan  Thermal expansion valve  Fan guard  Receiver  Electrical panel  Compressor  Ladder diagrams  V ariable Frequency Drive (for compressor)  Communication ...

  • APC ACRP101 - page 17

    13 InRow RP Technical Data Manual Air-cooled Interior Component s (back of unit)  Evaporator coil  Shutoff valves (top piping only)  Condensate drain pan  Air filters  Sight glass  Pipe chase  Filter dryer  Humidity sensor  Condensate pump  Return air temperature sensor  Humidifier na20 7 4a ...

  • APC ACRP101 - page 18

    InRow RP Technical Data Manual 14 Chilled W ater and Air-cooled User Interface Connections  Rack inlet temperature sensors 1, 2, 3  A-Link IN  A-Link OUT  Networ k port  Console port  Alarm output, NC (Normally Closed)  Alarm output, COM (Common)  Alarm output, NO (Normally Open)  Supply GND (Ground)  Supply 12 Vdc (cu ...

  • APC ACRP101 - page 19

    15 InRow RP Technical Data Manual Chilled W ater El ectrical Panel Note: ACRP501 shown.  Tr a n s f or me rs  User interface connectors  Main controller board  Relay board  Ground lug  Main circuit breaker — power feed A  Main circuit breaker — power feed B  Automatic transfer switch (A TS) contactors  A TS timers  ...

  • APC ACRP101 - page 20

    InRow RP Technical Data Manual 16 Air-cooled Electrical Panel Note: ACRP 101 shown.  Tr a n s fo r m e r s  User interface connectors  Main controller board  Relay board  Ground lug  Main circuit break er  Compressor fuse block (ACRP1 00, ACRP101)  Compressor circuit breaker (ACRP102)  Fan circuit breakers  Controller ...

  • APC ACRP101 - page 21

    17 InRow RP Technical Data Manual Performance S pecifications Chilled W ater Performance Spec ifications 5.5°C (42°F) EWT T emperatur e dry bulb (DB), wet bulb (WB) °C (°F) CW Delta T °C (°F) To t a l N e t Capacity kW (BTU/hr) Sensible Net Capacity kW (BTU/hr) Sensible H eat Ratio SHR CW Flow Rate l/s (GPM) To t a l C W Pressure Dr op kPa (f ...

  • APC ACRP101 - page 22

    InRow RP Technical Data Manual 18 Chilled W ater Performance Spec ifications 7.2°C (45°F) EWT T emperature dry bulb (DB), wet bulb (WB) °C (°F) CW Delta T °C (°F) T otal Net Capacity kW (BTU/hr) Sensible Net Capacity kW (BTU/hr) Sensible Heat Ratio SHR CW Flow Rate l/s (GPM) To t a l C W Pressure Dr op kPa (ft H 2 O)* 26.7°C DB, 17.1°C WB ( ...

  • APC ACRP101 - page 23

    19 InRow RP Technical Data Manual Chilled W ater Performance Spec ifications 8.9°C (48°F) EWT ( T emperatur e d ry bulb (DB), wet bulb (WB) °C (°F) CW Delta T °C (°F) T otal Net Capacity kW (BTU/hr) Sensible Net Capacity kW (BTU/hr) Sensible Heat Ratio SHR CW Flow Rate l/s (GPM) To t a l C W P r e s s u r e Drop kPa (ft H 2 O)* 26.7°C DB, 17 ...

  • APC ACRP101 - page 24

    InRow RP Technical Data Manual 20 Chilled W ater Performance Spec ifications 10°C (50°F) EWT T empe rature dry bulb (DB), wet bulb (WB) °C (°F) CW Delta T °C (°F) T otal Net Capacity kW (BTU/hr) Sensible Ne t Capacity kW (BTU/hr) Sensible H eat Ratio SHR CW Flow Rate l/s (GPM) To t a l C W Pressure Dr op kPa (ft H 2 O)* 26.7°C DB, 17.1°C WB ...

  • APC ACRP101 - page 25

    21 InRow RP Technical Data Manual Chilled W ater Performance Specif ications 12.8°C (55°F) EWT T e mperature dry bulb (DB), wet bulb (WB) °C (°F) CW Delta T °C (°F) To t a l N e t Capacity kW (BTU/hr) Sensible N et Capacity kW (BTU/hr) Sensible Heat Ratio SHR CW Flow Rate l/s (GPM) To t a l C W Pressure Drop kPa (ft H 2 O)* 26.7°C DB, 17.1° ...

  • APC ACRP101 - page 26

    InRow RP Technical Data Manual 22 Chilled W ater Performance Specif ications 15.5°C (60°F) EWT T empe rature dry bulb (DB), wet bulb (WB) °C (°F) CW Delta T °C (°F) T otal Net Capacity kW (BTU/hr) Sensible Net Capacity kW (BTU/hr) Sensible Heat Ratio SHR CW Flow Rate l/s (GPM) To t a l C W Pre ssur e Drop kPa (ft H 2 O)* 26.7°C DB, 17.1°C W ...

  • APC ACRP101 - page 27

    23 InRow RP Technical Data Manual Chilled W ater Data - General MODEL ACRP 500 Series MODULA TING V AL VES Size -3 W ay Ball V alve - NPT mm (in) 25.4 (1) AIR SYSTEM - F ANS (S ta ndard Filter Installe d) Air V olume - l/s (SCFM) 3162 (6700) Fan Motor - W (HP) 1 100 (1.5) Number of Fans 3 COOLING COIL - COPPER TUBE/ALUMINUM FIN Face Ar ea - m 2 (ft ...

  • APC ACRP101 - page 28

    InRow RP Technical Data Manual 24 Glycol Correction Factors Altitude Correction Factors for InRow Products Air-cooled Performanc e Sp ecifications Performance Criteria Glycol Solution Percent W eight of Solution *** 0 10% 20% 30% 40% 50% Capacity* Ethylene 1.00 0.97 0.93 0.88 0.81 0.75 Propylene 1.00 0.96 0.90 0.82 0.77 0. 74 Pressure Drop** Ethyle ...

  • APC ACRP101 - page 29

    25 InRow RP Technical Data Manual Air-cooled Dat a - General Note: Reduce airflow a nd cooling capacity spec ification s by 7% for cooling units run at low input voltage (380 V). MODEL ACRP 100 Series AIR SYSTEM - F AN (S tandard Filter Installed) Air V olume - l/s (SCFM) 2265 (4800) Fan Motor - W (HP) 1 100 (1.5) Number of Fans 2 COOLING COIL - CO ...

  • APC ACRP101 - page 30

    InRow RP Technical Data Manual 26 Sound Performance Data Electrical Data Chilled W ater T ested Sound Data Fan Speed% Airflow m 3 /s (SCFM) Sound Power dB at Frequency Hz re: 10 -12 W Lp Sound Pressure dB re: 20 microPa* 125 250 500 1000 2000 4000 8000 dBA dBA 35 1.13 (2500) 69.5 37.5 63.5 60.0 54.0 47.5 4 0.0 65.4 54.9 50 1.79 (3800) 84.0 79.0 75. ...

  • APC ACRP101 - page 31

    27 InRow RP Technical Data Manual Dimensional Dat a InRow RP Assembled Module Dimensions are shown in mm (in). na24 65a ...

  • APC ACRP101 - page 32

    InRow RP Technical Data Manual 28 SX to VX Height Adapter SX to 48U SX Height Adapter Dimensions are shown in mm (in). na244 5a na24 46a ...

  • APC ACRP101 - page 33

    29 InRow RP Technical Data Manual Piping and Mechanical Connections Chilled W ater Piping Diagram Flex hose or copper Circuit setter (field-installed) Copper tubing Hose end drain with cap Y - strainer with 20 mesh screen (field installed)* Isolation valve *Blow down may be installed on Y -strain er . na 2572a Bottom piping T op piping InRow RP InR ...

  • APC ACRP101 - page 34

    InRow RP Technical Data Manual 30 T op Chilled Water Pipi ng Access (top view) Note: T op or bottom entry can be chosen individu ally for each type of connectio n, i.e. power , condensate drain, humidifier water supply , ch illed water supply and ch illed water return. T op piping configuration will have the same valves and strainers as bottom pipi ...

  • APC ACRP101 - page 35

    31 InRow RP Technical Data Manual Bottom Chilled W ater Piping Acce ss (bottom view , looking up) Dimensions are shown in mm (in).  W ater supply to chiller  W ater supply from chiller  Condensate overflow  Communication connections—2 7.80 mm (1.09 in)  Power connections—dual feed  Condensate drain  Humidifier suppl y na21 ...

  • APC ACRP101 - page 36

    InRow RP Technical Data Manual 32 Air-cooled Piping Diagram Note: Shutof f valves shown nearest to th e condensers are not supplied by APC. Note: Route piping t hrough the top or bottom of the InRow RP . Note: T rap the vertical discharge line every 6 m (20 ft) to ensure proper oil return. Note: The maximum piping run is 61 m (200 ft) equivalent le ...

  • APC ACRP101 - page 37

    33 InRow RP Technical Data Manual Air-cooled Piping Access (top) Dimensions are shown in mm (in).  Refrigerant dischar ge line  Refrigerant liquid line  Pressure relief valve dischar ge line  T rou gh for communication cabl es  Power connections  Humidifier water supply  Condensate drain na 2071a 547 21.54 () 558 21.97 () 123 4 ...

  • APC ACRP101 - page 38

    InRow RP Technical Data Manual 34 Air-cooled Piping Access (bottom view , looking up) Dimensions are shown in mm (in).  Pressure relief valve access—27.80 mm (1.09 in)  Refrigerant liquid line  Refrigerant discharge line  Condensate overflow—50.00 mm (1.97 in)  Communication connectio ns—27.80 mm (1.09 in)  Power connections ...

  • APC ACRP101 - page 39

    35 InRow RP Technical Data Manual Air-Cooled Condensers Mechanical Da t a SKU Ambient Te m p Sound Pressure (dbA)* Sound Pressure (dbA) ** Air Quantity Fan Unit Connection Size W eight Capacity l/s (CFM) Qty . kW Hot Gas Liquid Kg (Lbs) MBH/1F TD kW/1C TD ACCD75201 95 (35) 67 62 4955 (10500) 1 2.2 1 3/8 in 1 3/8 in 163 (360) 8.8 4.6 ACCD75202 105 ( ...

  • APC ACRP101 - page 40

    InRow RP Technical Data Manual 36 ACCD75201 and ACCD75204 ACCD75202 and ACCD75205 ACCD75203 and ACCD75206 Dimensions are shown in mm (in). Note: All cond ensers shown on this page have ei ght 22 mm (0.875 in) mounting ho les on their lower rails. na24 4 9a na24 5 0a na2 051a ...

  • APC ACRP101 - page 41

    37 InRow RP Technical Data Manual ACCD75207 ACCD75208 and ACCD75209 Dimensions are shown in mm (in). All condensers shown on this page have 16 mm (0.63 in) mounting holes on each of their lower legs. Air-cooled Condenser Features A vailable in one to three fan configur ations, APC of fers air-cooled condensers with a vertical air discharge pattern. ...

  • APC ACRP101 - page 42

    InRow RP Technical Data Manual 38 Guide S pecifications P ART 1 — GENERAL 1.01 SUMMAR Y A. The en vironmental con trol syst em shall be designed specifica lly for precision temperature and humidity control appli cations. It will automatically monito r and control heating, cooling, humidifying, dehumidifying, and filtering functions for the condit ...

  • APC ACRP101 - page 43

    39 InRow RP Technical Data Manual B. V ARIABLE SPEED FAN ASSEMBLY 1 . V ariable Speed Fans: The unit is equipped w ith variable speed, electronically commutate d, 400 mm backward incline fans complete with Inlet V olute. 2 . Fan Protection: discharge finger guard. Outlet of the fan should include a cage type finger guard. C. AUTOMATIC T RANSFER SWI ...

  • APC ACRP101 - page 44

    InRow RP Technical Data Manual 40 k. Fan fault l. Fan run hours exceeded m. W ater detection fault n. Condensate pump fault o. Condensate run hours exceeded p. Humidifier water conductivity h igh violation q. Humidifier fault tolerance exceeded r . Humidifier low water s. Humidifier excessive output reduction t. Humidifier drain fault u. Humidifier ...

  • APC ACRP101 - page 45

    41 InRow RP Technical Data Manual ba. Air flow decreased while compressor off bb. S uction pressure senso r failure bc. Discharge pressure sensor failure bd. High pressure switch active be. Fan speed decreased to avoi d high pressure (event only) bf. Compressor speed decreased to avoid high pressure (event only) bg. Compressor high pressure bh. Oil ...

  • APC ACRP101 - page 46

    InRow RP Technical Data Manual 42 J. CONDENSA TE PUMP Factory installed and wired condensate pump shall pump at 31.99 l/h (8. 45 GPH) at 3.5 m (1 1.5 ft) of head. Pump shall have a dual po sition internal float and a reservoir made of polymeric materials to prevent corrosion. K. FIL TERS 1 . The standard filters shall be 30% efficient per ASHRAE S ...

  • APC ACRP101 - page 47

    43 InRow RP Technical Data Manual P . SELECT ABLE TOP OR BOTTOM P IPING (AIR-COOLED ONL Y) 1 . Pipe connections: The unit is equipped with field connection from either top or bottom of the unit. Unit connections shall be made internal to the unit. 2 . Pipe adapters: The unit shall include 1-in Rotolock to sweat adapte rs and associated T eflon seal ...

  • APC ACRP101 - page 48

    InRow RP Technical Data Manual 44 Guidelines for Inst allation The InRow RP provides reliable, accu rate temperature control of comp uter rooms, laboratories, and other environments that require cl ose tolerance control. The unit incorporates the latest system design innovations to provide you with optimum ef ficiency , reli ability , and accuracy ...

  • APC ACRP101 - page 49

    ...

  • APC ACRP101 - page 50

    9/2009 990-2469E-001 APC W orldwide Customer Support Customer support for this or any other APC product is available at no char ge in any of the following ways: • V isit the APC W eb site to acce ss documents in the APC Knowledg e Base and to submit customer support requests. – www .apc.com (Corporate Headquarters) Connect to localized APC W eb ...

Produzent APC Kategorie Water Dispenser

Dokumente, die wir vom Produzenten des Geräts APC ACRP101 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen APC
- Bedienungsanleitungen ACRP101
- Produktkarten APC
- Informationsbroschüren
- oder Energieetiketten APC ACRP101
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung APC ACRP101.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen APC ACRP101, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen APC ACRP101. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts APC ACRP101 ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts APC ACRP101, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von APC ACRP101 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von APC ACRP101 verständlich ist.

Eine gänzliche Bedienungsanleitung von APC sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von APC ACRP101 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von APC ACRP101 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich APC ACRP101, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts APC ACRP101 - die uns die ersten Schritte während der Nutzung von APC ACRP101 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit APC ACRP101 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von APC ACRP101 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich APC ACRP101?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit APC ACRP101 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit APC ACRP101 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)