Bedienungsanleitung Cisco Systems G18 G-.SP

24 Seiten 0.87 mb
Download

Zur Seite of 24

Summary
  • Cisco Systems G18 G-.SP - page 1

    BURNERS BRULEURS BRENNER QUEMADORES BRUCIA T ORI Complying with EMC 89/336/CEE LV 73/23/CEE T echnical Documentation CIB Unigas S.p.a. - Campodarsego (PD) M03978CA Rev . 00 10/99 MANUAL FOR - INST ALLA TION - OPERA TION - MAINTENANCE LIGHT OIL BURNERS G18 G-.SP PG25 G-.SP PG30 G-.TN FOREWORD Page 2 PARTE I: INSTALLATION Page 4 PARTE II: OPERATION P ...

  • Cisco Systems G18 G-.SP - page 2

    2 PREF ACE THIS MANUAL IS SUPPLIED AS AN INTEGRAL AND ESSENTIAL PART OF THE PRODUCT AND MUST BE DELIVERED TO THE USER. INFORMATION INCLUDED IN THIS SECTION ARE DEDICATED BOTH TO THE USER AND TO PERSONNEL FOLLOWING PRODUCT INSTALLATION AND MAINTENANCE. THE USER WILL FIND FURTHER INFORMATIONS ABOUT OPERATING AND USE RESTRICTIONS, IN THE SECOND SECTIO ...

  • Cisco Systems G18 G-.SP - page 3

    3 FOREWORD 3) GENERAL INSTRUCTIONS DEPENDING ON FUEL USED 3A) ELECTRICAL CONNECTION * For safety reasons the unit must be efficiently earthed and installed as required by current safety regulations. * It is vital that all saftey requirements are met. In case of any doubt, ask for an accurate inspection of electrics by qualified personnel, since the ...

  • Cisco Systems G18 G-.SP - page 4

    4 AB B L C C L D E G KH P M G1 8 S P 275 90 200 365 475 340 255 115 230 125 121÷134 M 8 Fig. 1 P ART I: INST ALLA TION MANUAL TECHNICAL DA T A BURNER MODEL IDENTIFICATION Burners are identified by burner type and model. Burner type identification is described as follow: Type: G18 Model: G-. SP. S. *. A. (1) (2) (3) (4) (5) (6) (1) BURNER TYPE G18 ...

  • Cisco Systems G18 G-.SP - page 5

    5 Fig. 1a Fig. 2 Fig. 3 Fig. 3a 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 6 8 10 12 14 16 18 20 -1 0 1 2 3 4 10 12 14 16 18 20 22 24 26 28 30 -1 -0 . 5 0 0.5 1 1.5 2 2.5 3 10 12 14 16 18 20 22 24 26 28 30 32 34 AB B L C C L D E FGKHP M PG 25 SP PG 30 SP 515 155 345 660 85 0 267 260 520 133 29 0 125 155 M 10 PERFORMANCE CURVES OVERALL DIMENSIONS INSTALLAT ...

  • Cisco Systems G18 G-.SP - page 6

    6 MOUNTINGS AND CONNECTIONS The burners are despatched in cardboard packages. The packaging contains the following items: 1 burner; 2 flexible light oil tubes; 1 light oil filter; 1 gasket to be inserted between the burner and the boiler; 1 this manual, the Guarantee Certificate and the test certificate. T o get rid of the burner’s packing and in ...

  • Cisco Systems G18 G-.SP - page 7

    7 G18SP PG25SP PG30TN Fig. 6 Fig. 5 Fig. 5b Fig. 5a ...

  • Cisco Systems G18 G-.SP - page 8

    8 BAR G P H 8 9 1 01 11 21 31 41 51 6 1 71 8 1. 75 6. 02 6. 38 6. 73 7. 05 7. 37 7. 67 7. 96 8. 24 8. 51 8. 77 9. 02 2. 00 6. 88 7. 29 7. 69 8. 06 8. 42 8. 77 9. 10 9. 42 9. 72 10. 02 10. 31 2. 25 7. 74 8. 20 8. 65 9. 07 9. 47 9. 86 10. 23 10. 59 10. 94 11. 28 11. 60 2. 50 8. 59 9. 12 9. 61 10. 08 10. 53 10. 96 11. 37 11. 77 12. 16 12. 53 12. 89 3. ...

  • Cisco Systems G18 G-.SP - page 9

    9 Fig. 7 Fig. 9 Fig. 8 LIGHT OIL PUMPS SUNTEC AS57C Suction height: 0.5 bar Advised value to prevent air separation from oil: 0.35 bar Rated speed: max. 2850 rpm Operation viscosity: from 2 to 12 cSt Inlet pressure: max. 2 bar DELTA VM2RL2 Suction height: 0.5 bar Advised value to prevent air separation from oil: 0.35 bar Rated speed: max. 3500 rpm ...

  • Cisco Systems G18 G-.SP - page 10

    10 VBS VBS + - Fig. 12 Fig. 11 Fig. 10 Fig. 12a AIR FLOW ADJUSTMENT Burner G18SP Loose the screw VBS and rotate the air damper in the desired position, to set the air flow. At the end of settings, tight the screw VBS. Burners PG25SP - PG30TN Loose the screw VBS and set the air flow, working directly on the air damper. At the end of settings, tight ...

  • Cisco Systems G18 G-.SP - page 11

    11 P ART II: OPERA TION MANUAL LIMIT A TIONS OF USE THE BURNER IS AN APPLIANCE DESIGNED AND CONSTRUCTED TO OPERA TE ONL Y AFTER BEING CORRECTL Y CONNECTED TO A HEA T GENERA TOR (E.G. BOILER, HOT AIR GENERA TOR, FURNACE, ETC.), ANY OTHER USE IS TO BE CONSIDERED IMPROPER AND THEREFORE DANGEROUS. THE USER MUST GUARANTEE THE CORRECT FITTING OF THE APPL ...

  • Cisco Systems G18 G-.SP - page 12

    12 C AR VRT R C V Fig. 13 Fig. 13a ABCD 6 0 ° 6446 4 5 ° 1 0 546 6 0 ° 8446 4 5 ° 1 2 546 6 0 ° 8446 4 5 ° 1 2 546 G1 8 S P PG 28 SP PG 30 TN P ART III: MAINTENANCE At least once a year carry out the following maintenance procedures. If servicing is on a seasonal basis, it is recommended at the end of the season; routine sevice should be carr ...

  • Cisco Systems G18 G-.SP - page 13

    13 Fig. 14 CHECK OF THE IONIZA TION CURRENT To check the detector signal follow the prcedure shown in fig. 14. If the signal is not within the prescribed range, check the electrical contacts; check also that the combustion head is clean and the photoelectric sensor is correctly positioned. Replace it if necessary. TERMINAL BLOCK MC Scale µA DC Min ...

  • Cisco Systems G18 G-.SP - page 14

    14 ELECTRICAL DIAGRAM code 01-369 BURNER G18SP ELECTRICAL DIAGRAM code 04-575 BURNER PG25SP 1 - Electric supply 230V 50Hz 2N a.c. 2 - Don't reverse Phase and Neutral 3 - Make sure that the burner is properly hearted 1 - Electric supply 230V 50Hz 2N a.c. 2 - Don't reverse Phase and Neutral 3 - Make sure that the burner is properly hearted ...

  • Cisco Systems G18 G-.SP - page 15

    15 ELECTRICAL DIAGRAM code 04-574 BURNER PG30TN EVG1 Light oil solenoid valve I st stage EVG2 Light oil solenoid valve II nd stage F Fuses FR Photoresistor IL Main switch L Phase LF Burner operation light LB Burner lockout light LEVG1 EVG1 opening signalization light LEVG2 EVG2 opening signalization light LOA24/BOA64 Flame monitor device MA Power s ...

  • Cisco Systems G18 G-.SP - page 16

    16 SP ARE P ARTS BURNER G18SP MAINTENANCE POS. D E SC RI PTIO N C OD E POS. D E SC R IPT IO N C OD E 1 HO USI NG 3010019 19 B LA ST T UB E 3090055 2 CO NDE NSE R 60 30004 20 CO M BUS T I O N HE A D 3060115 3 M O T O R 218000 9 21 E LECT RO DE S UPP O RT 228001 6 4 F LA M E CO NT RO L DEV I CE LO A 24 20 20445 22 G A SK ET 211003 1 5 S O CKE T F O R ...

  • Cisco Systems G18 G-.SP - page 17

    17 SP ARE P ARTS BURNERS PG25SP - PG30TN MAINTENANCE POS. D E SC R IPTI ON PG 2 5SP PG 30 TN 1 E LECT RI C BO A RD 610008 6 61 00086 2 T HERM A L RELA Y -- - -- - 3 S OC K E T F O R F LA M E CO NT RO L DE V I CE 203041 5 203041 5 4 F LA M E C O NT RO L DE V I CE 202044 5 2020445 5C O N T A C T O R - - - - - - 6 I G NI TI O N T RA NSF O RM ER 217010 ...

  • Cisco Systems G18 G-.SP - page 18

    18 APPENDIX: COMPONENTS CHARACTERISTICS FLAME CONTROL DEVICE LANDIS LOA24 Page 18 LIGHT OIL PUMPS Page 19 LANDIS AUTOMA TIC CONTROLLER LOA24 FOR LIGHT OIL BURNERS Use LOA... safety devices are intended for use in conjunction with QRB... photoresistors, for lighting and controlling low capacity forced air diesel burners with max. capacity 30 kg/h in ...

  • Cisco Systems G18 G-.SP - page 19

    19 T echnical characteristics Voltage 220V-15%..240V+10% or 100V -15%...110V+10% Frequency 50...60Hz +/- 6% External fuse max.10A slow action Contact flow: - terminal 1 5 A - terminal 3 5A (incl.capacity absorbed by motor and pre- heater) Terminal flow: - terminals 4, 5 &10 1A - terminals 6&7 2A - terminal 8 5A Absorbed cap 3VA Protection I ...

  • Cisco Systems G18 G-.SP - page 20

    20 SUNTEC AS oil pumps - Oil - Flow up to 75 1/h (c.600,000 kcal/h - 700 kW) - Twin-pipe system - Single-pipe system Technical data Mounting On flange or hub in acccordance with standards DIN 24220 and ISO/TC 109 SC 3 DP 5062F Threads round-headed in accordance with ISO R 228-NFE 03005(DIN2S9) Supply and return R 1/4" Delivery R 1/8" Pres ...

  • Cisco Systems G18 G-.SP - page 21

    21 Operation The gear-set draws oil from the tank through the built-in filter and transfers it to the valve that regulates the oil pressure or tne nozzle line. All oil which does not go through the nozzle line will be dumped through the valve back to the return line or, if it is a one-pipe installation, back to the suction port in the gear-set. The ...

  • Cisco Systems G18 G-.SP - page 22

    22 T win pipe installation Single pipe installation (remove the by-pass plug “P”) A Closed by-pass solenoid valve B Opened by-pass solenoid valve C Opened cut-off solenoid valve D Closed cut-off solenoid valve 1 Manometer plug 2 To nozzle 3 Shaft seal 4 Return to suction 5 By-pass plug 6 Return (twin pipe installation) 7 Suction (twin pipe inst ...

  • Cisco Systems G18 G-.SP - page 23

    23 ...

  • Cisco Systems G18 G-.SP - page 24

    Via C. Colombo, 9 - 35011 Campodarsego (PD) Italy Tel. +39-049-9200944 - Fax +39-049-9200945-9201269 Internet: www.cibunigas.it - E mail: cibunigas@cibunigas.it ...

Produzent Cisco Systems Kategorie Burner

Dokumente, die wir vom Produzenten des Geräts Cisco Systems G18 G-.SP erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Cisco Systems
- Bedienungsanleitungen G18 G-.SP
- Produktkarten Cisco Systems
- Informationsbroschüren
- oder Energieetiketten Cisco Systems G18 G-.SP
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Cisco Systems G18 G-.SP.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Cisco Systems G18 G-.SP, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Cisco Systems G18 G-.SP. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Cisco Systems G18 G-.SP ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Cisco Systems G18 G-.SP, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Cisco Systems G18 G-.SP hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Cisco Systems G18 G-.SP verständlich ist.

Eine gänzliche Bedienungsanleitung von Cisco Systems sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Cisco Systems G18 G-.SP bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Cisco Systems G18 G-.SP befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Cisco Systems G18 G-.SP, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Cisco Systems G18 G-.SP - die uns die ersten Schritte während der Nutzung von Cisco Systems G18 G-.SP erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Cisco Systems G18 G-.SP hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Cisco Systems G18 G-.SP im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Cisco Systems G18 G-.SP?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Cisco Systems G18 G-.SP nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Cisco Systems G18 G-.SP hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)