    Single-Package Rooftop Products with Energy-Saving Features • Direct Spark Ignition • Low Sound Levels • Up to 81% AFUE • 12 SEER FEA TURE/BENEFITS One-piece heating and cooling units with low sound levels, easy installation, low maintenance, and dependable performance. EASY INST ALLA TION — Factory-assembled package is a compact, fully s ...

  • Bryant 583A - page 2

    jobsite. A nesting feature ensures a positive basepan to roof curb seal when the unit is roof mounted. A convenient 3 ⁄ 4 -in. wide perimeter flange makes frame mounting on a rooftop easy . Downflow Operation is easily provided in the field to allow ver- tical ductwork connections. The basepan utilizes knockout style seals on the bottom openin ...

  • Bryant 583A - page 3

    MODEL NUMBER NOMENCLA TURE CU — Copper ARI* CAP ACITIES COOLING CAP ACITIES AND EFFICIENCIES UNIT 583A NOMINAL TONS ST ANDARD CFM NET COOLING CAP ACITIES (Btuh) SEER† SOUND RA TINGS** (Bels) 024040 2 800 24,000 12.0 7.2 024060 030040 2 1 ⁄ 2 1000 30,000 12.0 7.2 030060 036060 3 1200 35,000 12.0 7.4 036090 042060 3 1 ⁄ 2 1400 42,000 12.0 7.4 ...

  • Bryant 583A - page 4

    ARI* CAP ACITIES (cont) HEA TING CAP ACITIES AND EFFICIENCIES UNIT 583A HEA TING INPUT (Btuh) OUTPUT CAP ACITY (Btuh) TEMPERA TURE RISE RANGE (°F) AFUE (%) 024040 40,000 32,040 20-50 80.1 030040 80.0 024060 60,000 47,040 35-65 78.4 030060 47,040 35-65 80.1 036060 47,220 25-55 78.7 042060 47,220 15-45 78.7 036090 88,000 71,910 45-75 79.9 042090 90, ...

  • Bryant 583A - page 5

    PHYSICAL DA T A UNIT SIZE 583A 024040 024060 030040 030060 036060 036090 042060 042090 NOMINAL CAP ACITY (ton) 22 2 1 ⁄ 2 2 1 ⁄ 2 33 3 1 ⁄ 2 3 1 ⁄ 2 OPERA TING WEIGHT (lb) 290 290 313 313 321 321 382 382 COMPRESSORS Scroll Quantity 1 REFRIGERANT (R-22) Quantity (lb) 3.4 3.4 4.4 4.4 5.2 5.2 6.4 6.4 REFRIGERANT METERING DEVICE Acutrol™ Devi ...

  • Bryant 583A - page 6

    OPTIONS AND ACCESSORIES F ACTORY -INST ALLED OPTIONS Louvered Grille provides hail and vandalism protection. See model number nomenclature for louvered grille options. Coil Options include copper/copper and vinyl-coated construc- tion for refrigerant coils. Units are shipped standard with copper tube/aluminum fin construction. See model number nom ...

  • Bryant 583A - page 7

    OPTIONS AND ACCESSORIES (cont) Economizer Filter Rack Manual Outside Air Damper DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT P ANEL 7 ...

  • Bryant 583A - page 8

    BASE UNIT DIMENSIONS — UNIT SIZES 024-036 REQ’D CLEARANCES FOR OPERA TION AND SER VICING. in. (mm) Evaporator coil access side .................... 3 6 (914) Power entry side (except for NEC requirements) .......... 3 6 (914) Unit top ............................ 4 8 (1219) Side opposite ducts ....................... 3 6 (914) Duct panel ...... ...

  • Bryant 583A - page 9

    BASE UNIT DIMENSIONS — UNIT SIZES 042-060 REQ’D CLEARANCES FOR OPERA TION AND SER VICING. in. (mm) Evaporator coil access side .................. 3 6 (914) Power entry side (except for NEC requirements) ......... 3 6 (914) Unit top .......................... 4 8 (1219) Side opposite ducts ..................... 3 6 (914) Duct panel ............. ...

  • Bryant 583A - page 10

    ACCESSOR Y DIMENSIONS UNIT 583A P ART NUMBER A in. [mm] B in. [mm] C in. [mm] D in. [mm] FLA T CURB 024-036 CPRFCURB006A00 8 [203] 1 1 27 ⁄ 32 [301] 30 5 ⁄ 8 [ 778] 28 3 ⁄ 4 [ 730] CPRFCURB007A00 14 [356] 1 1 27 ⁄ 32 [301] 30 5 ⁄ 8 [ 778] 28 3 ⁄ 4 [ 730] 042-060 CPRFCURB008A00 8 [203] 15 27 ⁄ 32 [402] 42 1 ⁄ 8 [1070] 40 1 ⁄ 4 [102 ...

  • Bryant 583A - page 11

    SELECTION PROCEDURE (WITH EXAMPLE) I DETERMINE COOLING AND HEA TING REQUIRE- MENTS A T DESIGN CONDITIONS: Given: Required Cooling Capacity (TC) .......... 35,000 Btuh Sensible Heat Capacity (SHC) ........... 25,000 Btuh Required Heating Capacity .............. 60,000 Btuh Condenser Entering Air T emperature ............9 5 F Indoor-Air T emperature ...

  • Bryant 583A - page 12

    PERFORMANCE DA T A NET COOLING CAP ACITIES 583A--024 T emp (F) Air Ent Condenser Evaporator Air — Cfm/BF 700/0.081 800/0.106 900/0.135 Evaporator Air — Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 22.3 24.9 27.6 22.9 25.3 28.1 23.3 25.6 28.3 SHC 20.2 16.9 13.6 21.7 18.0 14.2 23.0 19.0 14.7 kW 1.89 1.91 1.93 1.96 1.99 2.01 2.01 2.09 2.1 1 95 TC 21.4 ...

  • Bryant 583A - page 13

    PERFORMANCE DA T A (cont) NET COOLING CAP ACITIES (cont) 583A--036 T emp (F) Air Ent Condenser Evaporator Air — Cfm/BF 1050/0.1 1 1 1200/0.142 1350/0.181 Evaporator Air — Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 31.4 36.2 40.6 32.4 37.1 41.2 33.1 37.6 41.5 SHC 28.7 24.4 19.7 30.9 26.0 20.4 33.1 27.3 20.9 kW 2.82 2.88 2.93 2.93 3.01 3.06 3.03 3. ...

  • Bryant 583A - page 14

    PERFORMANCE DA T A (cont) NET COOLING CAP ACITIES (cont) 583A--048 T emp (F) Air Ent Condenser Evaporator Air — Cfm/BF 1400/0.050 1600/0.085 1800/0.119 Evaporator Air — Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 45.2 49.7 54.7 46.4 50.9 56.0 47.5 51.9 57.1 SHC 41.4 34.6 27.6 44.6 37.2 29.2 47.5 39.6 30.8 kW 4.04 4.08 4.12 4.05 4.09 4.13 4.06 4.10 ...

  • Bryant 583A - page 15

    PERFORMANCE DA T A (cont) DR Y COIL AIR DELIVER Y* — HORIZONT AL AND DOWNFLOW DISCHARGE — UNIT SIZES 024-060 (Deduct 10% for 208 V olts) 230 AND 460 VOL T Unit 583A Motor Speed External Static Pressure (in. wg) 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 024 Low W atts 2 8 1 2 8 2 2 8 1 2 7 8 2 7 6 —————— Cfm 8 9 9 8 2 8 7 5 7 6 9 1 ...

  • Bryant 583A - page 16

    PERFORMANCE DA T A (cont) 583A WET COIL PRESSURE DROP UNIT SIZE 583A AIRFLOW (cfm) PRESSURE DROP (in. wg) 024 700 0.0535 800 0.067 900 0.123 030 900 0.0687 1000 0.083 1 100 0.150 036 1 100 0.084 1200 0.100 1300 0.177 042 1300 0.099 1400 0.177 1500 0.204 048 1500 0.199 1600 0.137 1700 0.156 060 1900 0.108 2000 0.120 2100 0.132 ECONOMIZER/1-in. FIL T ...

  • Bryant 583A - page 17

    PERFORMANCE DA T A (cont) HIGH AL TITUDE COMPENSA TION NA TURAL GAS ONL Y ORIFICE CONVERSION — 3.5 in. wg MANIFOLD PRESSURE* AL TITUDE (ft) INPUT (Btuh) OUTPUT (Btuh) ORIFICE NUMBER† 0-2000 40,000 32,040 #44 60,000 47,040 #38 90,000 71,910 #38 1 15,000 93,265 #33 130,000 104,390 #31 2001-4500 33,290 27,130 #49 49,930 40,690 #43 74,900 61,040 #4 ...

  • Bryant 583A - page 18

    TYPICAL PIPING AND WIRING V ertical Discharge Horizontal Discharge NEC — National Electrical Code 18 ...

  • Bryant 583A - page 19

    APPLICA TION DA T A 1. Condensate trap — A 2-in. condensate trap must be field supplied. 2. Ductwork — Secure downflow discharge ductwork to roof curb. For horizontal discharge applications, attach ductwork to unit with flanges. 3. T o convert a unit to downflow discharge — Units are equipped with factory-installed inserts in the downflo ...

  • Bryant 583A - page 20

    ELECTRICAL DA T A UNIT SIZE 583A V -PH-Hz VOL T AGE RANGE COMPRESSOR OUTDOOR F AN MOTOR INDOOR F AN MOTOR POWER SUPPL Y FUSE OR HACR BRKR Min Max RLA LRA FLA FLA MCA MOCP* 024 208/230-1-60 187 253 10.3 56.0 0.8 2.0 15.7 25 030 208/230-1-60 187 253 13.5 73.0 0.8 2.1 19.8 30 208/230-3-60 187 253 9.0 63.0 0.8 2.1 14.2 20 036 208/230-1-60 187 253 16.7 ...

  • Bryant 583A - page 21

    TYPICAL WIRING SCHEMA TIC — 208/230-1-60 SHOWN LEGEND AHA — Adjustable Heat Anticipator BR — Blower Relay C— Contactor CAP — Capacitor COMP — Compressor Motor CR — Combustion Relay EQUIP — Equipment FS — Flame Sensor FU — Fuse GND — Ground GVR — Gas V alve Relay HS — Hall Effect Sensor HV — High Voltage Transformer TRAN ...

  • Bryant 583A - page 22

    TYPICAL WIRING SCHEMA TIC — 208/230-3-60 SHOWN LEGEND AHA — Adjustable Heat Anticipator BR — Blower Relay C— Contactor CAP — Capacitor COMP — Compressor Motor CR — Combustion Relay CS — Centrifugal Switch EQUIP — Equipment FS — Fusible Link FU — Fuse GND — Ground GV — Gas V alve GVR — Gas V alve Relay HS — Hall Effect ...

  • Bryant 583A - page 23

    TYPICAL WIRING SCHEMA TIC — 460-3-60 SHOWN LEGEND AHA — Adjustable Heat Anticipator BR — Blower Relay C— Contactor CAP — Capacitor COMP — Compressor Motor CR — Combustion Relay CS — Centrifugal Switch EQUIP — Equipment FS — Fusible Link FU — Fuse GND — Ground GV — Gas V alve GVR — Gas V alve Relay HS — Hall Effect Sens ...

  • Bryant 583A - page 24

    CONTROLS OPERA TING SEQUENCE Heating — When the thermostat calls for heating, terminal ‘‘W’ ’ is energized, starting the induced-draft motor . When the hall- effect sensor on the induced-draft motor senses that it has reached the required speed, the burner ignition sequence be- gins. The indoor (evaporator) fan motor (IFM) is energized 45 ...

  • Bryant 583A - page 25

    GUIDE SPECIFICA TIONS P ACKAGED GAS HEA TING/ELECTRIC COOLING UNITS CONST ANT VOLUME APPLICA TION HV AC GUIDE SPECIFICA TIONS SIZE RANGE: 2 to 5 T ONS, NOMINAL COOLING 40,000 T O 130,000 BTUH NOMINAL HEA TING INPUT BRY ANT MODEL NUMBER: 583A P ART 1 — GENERAL 1.01 SYSTEM DESCRIPTION Outdoor rooftop mounted, gas heating/electric cooling unit utili ...

  • Bryant 583A - page 26

    GUIDE SPECIFICA TIONS (cont) L. Motors: 1. Compressor motors shall be of the refrigerant-cooled type with line-break thermal and current overload protection. 2. All fan motors shall have permanently lubricated bear- ings, and inherent, automatic reset, thermal overload protection. 3. Condenser-fan motor shall be totally enclosed. M. Special Feature ...

  • Bryant 583A - page 27

    ...

  • Bryant 583A - page 28

    Copyright 1999 Bryant Heating & Cooling Systems SPECIFICA TIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INST ALLED IN ACCORDANCE WITH INST ALLA TION INSTRUCTIONS Printed in U.S.A. 4-99 5258-300 ...

Fabricant Bryant Catégorie Switch

Les documents que nous recevons du fabricant de l'appareilBryant 583A peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Bryant
- manuels d’utilisations 583A
- fiches produit Bryant
- dépliants
- ou étiquettes-énergie Bryant 583A
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Bryant 583A.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Bryant 583A, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Bryant 583A. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Bryant 583A.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Bryant 583A, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Bryant 583A par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Bryant 583A.

Le manuel d’utilisation complet Bryant, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Bryant 583A - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Bryant 583A, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lBryant 583A qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Bryant 583A - qui devraient nous aider dans les premières étapes lors de l'utilisation Bryant 583A
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Bryant 583A
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Bryant 583A dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Bryant 583A?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Bryant 583A, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Bryant 583A il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)