    558J SINGLE P ACKAGE ROOFT OP COOLING UNIT 3 TO 6 NOMINAL T ONS Pr oduct Data Thi s produ ct has been desi gned and man uf actur ed to meet Ener gy St ar ® criteria for ene rgy efficiency . However, proper ref ri gerant c harge and proper ai r fl ow are critical to achieve ra t e d capa city and e ffi ciency . Ins tallatio n of this prod uct shoul ...

  • Bryant 558J - page 2

    2 T ABLE OF CONTENTS P AGE FEA TUR ES AND BE NEFITS 3 .................... MODEL NUMB ER NOMENC LA TURE 4 ............ F A CTO R Y OPTIONS & ACCESSORIES 5 ........... ARI CAP ACITY RA T ING 8 ....................... SOUND PERFOR MANCE 10 ...................... PHYSICAL DA T A 1 1 ............................. BASE UNIT DI MENSIONS 16 .......... ...

  • Bryant 558J - page 3

    3 FEA TURES AND BENEFITS S Up to 28% lighter than s imilar industry units. Li ghter rooftops make eas ier replacement jobs. S 3- - 6 ton units fit on exis ting Bryant s mall roofto p curb . This sav es time and money o n replacement jobs. S Standardiz ed component s and layout. Sta ndardized c omponents and cont rols make servic e and stocking pa r ...

  • Bryant 558J - page 4

    4 MODE L NUMBE R NOMENCLA T URE 123456789 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 5 5 8 J E 0 6 A 0 0 0 A 1 A 0 A A A ____________ ______ ________ ______ Unit T yp e 558J = Std Ef ficiency RTU Design Revision Vol tag e A = First Rev ision E = 4 6 0 --- 3 --- 6 0 J = 208/230 - - - 1 - - - 60 Pa ck ag i ng P = 208/230 - - - 3 - - - 60 A=S t a n d a r d T ...

  • Bryant 558J - page 5

    5 T able 1 – F A CT OR Y - - INST ALLED OP TIONS AN D FIELD- -INST ALLED ACCESS ORIES CA TEGO RY ITEM FA C T O R Y INSTALLED OPTION FIELD INSTALLED ACCE S SOR Y Cabin et T h r u --- t h e --- b a s e e l e c t r i c a l c o n n e c t i o n s X X Coi l Optio ns Cu/Cu ind oor and/or ou tdoor coils X Pre - - - coa ted outd oor coils X Prem ium, E - ...

  • Bryant 558J - page 6

    6 F ACTOR Y OP TIONS AND/OR ACCESSORIES Economiz er (dry - -bulb or enthalpy) Economi zers save mone y . They bring in fresh, out s ide a ir for ventilation; and provide cool, outside air to cool your buildin g. This is the prefer red method of low- - ambient cooling. When coupled t o CO 2 s ensors, Ec onomizers c an prov ide even more saving s by ...

  • Bryant 558J - page 7

    7 and condensate pan. The short wave lengt h ul tra - - viol et band light inhibits and kills mold, fungus, and microbial growth. Alternate Mot ors and Drives Some a pplicat ions nee d larger horsepower m otors, some need more ai rflow , and some need bot h. Rega rdless of the case, Brya nt has a factory instal led combi nation to me et your applic ...

  • Bryant 558J - page 8

    8 T able 2 – AR I COOLING RA TING T A BLES UNI T NOM . CAP ACITY (TONS) NET COOLING CAP ACITY (KBTU / H R) TOT AL POWER (KW) SEER EER IPL V IEER 04 3 34.6 3.1 13.0 11.0 N/A N/A 05 4 45.0 4.0 13.0 11.0 N/A N/A 06 5 59.0 5.5 13.0 10.8 N/A N/A 07 6 70.0 6.4 N/A 11.0 N/A 11.4 LEGE ND AR I - - - Air - - - Conditioning & Refrigeration Institute ASH ...

  • Bryant 558J - page 9

    9 T able 3 – MIN IMU M - - MAX IMUM AIR FLOWS ELECTRIC HEA T UNI T COOLING ELECTRI C HEA TERS Minimum Maximum Minimum Maxi mum 04 900 1500 900 1500 05 1200 2000 1200 2000 06 1500 2500 1500 2500 07 1800 3000 1800 3000 558J ...

  • Bryant 558J - page 10

    10 T a ble 4 – SO UND PERFORMANCE T ABL E UNI T OUTDOOR SOU ND ( dB) A --- W e i g h t e d 63 125 250 500 1000 2000 4000 8000 04 80 90.6 80.9 80.2 76.0 74.6 71.3 68.5 63.9 05 81 90.9 84.6 79.5 77.9 76.5 71.1 66.9 62.5 06 78 84.0 82.2 76.3 74.8 72.5 68.8 65.6 61.8 07 78 88.8 81.8 76.9 74.4 73.3 69.8 66.3 62.7 LEGE ND dB - - - Decibel NOTES : 1. Ou ...

  • Bryant 558J - page 11

    11 T able 5 – PHYSIC AL DA T A (COOLING) 3 - - 6 TON S 558J*04 558J*05 558J*06 558J*07 Refr igeration System #C i r c u i t s/# C o m p ./T y p e 1/1/S c r o l l 1/1/S c r o l l 1/1/S c r o l l 1/1/S c r o l l Puron (R - - - 410a) charge A/B (lbs) 5.6 8.5 10.7 14.1 Oil A /B (o z) 25 42 42 56 Met eri ng Devi ce Ac utrol Acutrol Acutrol Acutrol Hig ...

  • Bryant 558J - page 12

    12 T able 6 – ELECTR IC HEA T - - ELECTRICAL D A T A 3 - - 6 TONS UNI T V --- P H --- H Z IFM TY PE ELECTRI C HEA TER PA R T N U M B E R CRHEA TERXXXXXX NOM INAL POWER (kW) APPLICATION POWER (kW) SINGLE POINT OR JUNCTION KIT P AR T NUMBER CRSIN GLE***A00 NO C. O. or UN PWRD C.O . w/ PWRD C.O . NO P .E. w/ P .E. (pwrd f r/uni t) NO P .E. w/ P .E. ...

  • Bryant 558J - page 13

    13 T able 6 - - ELECTRIC HEA T - - ELECTRICA L DA T A 3 - - 6 T ONS (CONT) UNI T V --- P H --- H Z IFM TY PE ELECTRI C HEA TER PA R T N U M B E R CRHEA TERXXXXXX NOM INAL POWER (kW) APPLICATION POWER (kW) SINGLE POINT OR JUNCTION KIT P AR T NUMBER CRSIN GLE***A00 NO C. O. or UN PWRD C.O . w/ PWRD C.O . NO P .E. w/ P .E. (pwrd f r/uni t) NO P .E. w/ ...

  • Bryant 558J - page 14

    14 T able 6 - - ELECTRIC HEA T - - ELECTRICA L DA T A 3 - - 6 T ONS (CONT) UNI T V --- P H --- H Z IFM TY PE ELECTRI C HEA TER PA R T N U M B E R CRHEA TERXXXXXX NOM INAL POWER (kW) APPLICATION POWER (kW) SINGLE POINT OR JUNCTION KIT P AR T NUMBER CRSIN GLE***A00 NO C. O. or UN PWRD C.O . w/ PWRD C.O . NO P .E. w/ P .E. (pwrd f r/uni t) NO P .E. w/ ...

  • Bryant 558J - page 15

    15 T able 6 - - ELECTRIC HEA T - - ELECTRICA L DA T A 3 - - 6 T ONS (CONT) UNI T V --- P H --- H Z IFM TY PE ELECTRI C HEA TER PA R T N U M B E R CRHEA TERXXXXXX NOM INAL POWER (kW) APPLICATION POWER (kW) SINGLE POINT OR JUNCTION KIT P AR T NUMBER CRSIN GLE***A00 NO C. O. or UN PWRD C.O . w/ PWRD C.O . NO P .E. w/ P .E. (pwrd f r/uni t) NO P .E. w/ ...

  • Bryant 558J - page 16

    16 CURBS & WEIGHTS DIMENSIONS - - CHASSIS 1 Corner D Corner A Corner B Corner C 6 1/8” 7” 10 1/2” 19 1/2” 22” 16 1/4” 11 3/8” C08001 21 1/4” 19 1/2” 33 3/8” 16” 74 3/8” J 4 5/8” K 6 5/8” C08000 T able 7 – BASE U NIT DI MEN SIONS - - CHASSIS 1 UNI T OPERATING WGT ( LB) SHIPPING WGT ( LB) J CORN ER WEIGHTS ( LB ) CE ...

  • Bryant 558J - page 17

    17 GASKET (SUPPLIED WITH CURB) NAIL COUNTER FLASHING (FIELD SUPPLIED) ROOFING FEL T (FIELD SUPPLIED) CANT STRIP (FIELD SUPPLIED) ROOFING FEL T (FIELD SUPPLIED) C07457 Fig . 1 - - C urb Insta llatio n Detail (T y pical) 18” (457) 42" (1067) 18" (457) 42" (1067) 1 Required bottom condensate drain connection. Otherwise, 36” (914mm) ...

  • Bryant 558J - page 18

    18 AP PLIC A TION D A T A Min operat ing ambient t emp (cooling) : In mecha nical c ooling mode, your Bryant rooftop ca n safely opera te down to an outdoor ambient te mperature of 25 _ F( - - 4 _ C ), with an accesso ry winter start kit. It is possible to provide c ooling at l ower outdoor a mbient temperatur es by using less outs ide air , econom ...

  • Bryant 558J - page 19

    19 SELECTION PROCEDURE (WITH 558J*07 EXAMP LE) I. Determ ine coo ling a nd h eating loa ds. Given: Mixed Air Drybulb 80 _ F( 2 7 _ C) Mixed Air W etbul b 67 _ F( 1 9 _ C) Ambient Drybulb 95 _ F( 3 5 _ C) THC Load 69.0 MBH SHC Loa d 51.0 MBH Supply Air 2100 CFM Heati ng Load 85.0 MBH Extern al Static Pr ess ure 0.67 in.w g Electrical Ch aracteris ti ...

  • Bryant 558J - page 20

    20 T a ble 8 – COOL ING CAP ACITIE S 3 TONS 558J*04 AMBI ENT TEMPERA TURE 85 95 105 115 EA T (d B) EA T (dB ) EAT ( dB) EA T (d B) 75 80 85 75 80 85 75 80 85 75 80 85 900 Cfm EAT (wB) 58 THC 28.1 28.1 31.7 26.3 26.3 29.8 24.5 24.5 27.7 22.6 22.6 25.5 SHC 24.4 28.1 31.7 22.9 26.3 29.8 21.3 24.5 27.7 19.6 22.6 25.5 62 THC 30.3 30.3 31.0 27.8 27.8 2 ...

  • Bryant 558J - page 21

    21 T a ble 9 – COOL ING CAP ACITIE S 4 TONS 558J*05 AMBI ENT TEMPERA TURE 85 95 105 115 EA T (d B) EA T (dB ) EAT ( dB) EA T (d B) 75 80 85 75 80 85 75 80 85 75 80 85 1200 Cfm EAT (wB) 58 THC --- --- --- --- --- --- 36.1 36.1 40.7 34.3 34.3 38.6 SHC --- --- --- --- --- --- 31.5 36.1 40.7 29.9 34.3 38.6 62 THC 43.1 43.1 43.1 40.8 40.8 40.8 38.4 38 ...

  • Bryant 558J - page 22

    22 T a ble 10 – COO LING CAP ACITI ES 5 TONS 558J*06 AMBI ENT TEMPERA TURE 85 95 105 115 EA T (d B) EA T (dB ) EAT ( dB) EA T (d B) 75 80 85 75 80 85 75 80 85 75 80 85 1500 Cfm EAT (wB) 58 THC 52.9 52.9 60.0 49.9 49.9 56.6 46.6 46.6 52.9 43.1 43.1 48.9 SHC 45.8 52.9 60.0 43.2 49.9 56.6 40.4 46.6 52.9 37.3 43.1 48.9 62 THC 56.2 56.2 57.6 52.2 52.2 ...

  • Bryant 558J - page 23

    23 T a ble 1 1 – COOL ING CAP ACITIE S 6 TONS 558J*07 AMBI ENT TEMPERA TURE 85 95 105 115 EA T (d B) EA T (dB ) EAT ( dB) EA T (d B) 75 80 85 75 80 85 75 80 85 75 80 85 1800 Cfm EAT (wB) 58 THC 64.9 64.9 73.3 62.1 62.1 70.0 58.9 58.9 66.4 55.6 55.6 62.7 SHC 56.6 64.9 73.3 54.1 62.1 70.0 51.4 58.9 66.4 48.5 55.6 62.7 62 THC 68.7 68.7 70.3 64.9 64. ...

  • Bryant 558J - page 24

    24 T a ble 12 – S T A TIC PRES SURE ADDE RS (Factory Op tion s and /or Accesso ries) CFM 600 800 1000 1250 1500 1750 2000 2250 2500 2750 3000 Vertical Economizer 0.01 0.02 0.035 0.045 0.065 0.08 0.12 0.145 0.175 0.22 0.255 Horizon tal Economizer --- --- --- --- --- 0.1 0.125 0.15 0.18 0.225 0.275 CFM 600 900 1200 1400 1600 1800 2000 2200 2400 260 ...

  • Bryant 558J - page 25

    25 F AN PERF ORMANCE T ab le 13 – 558J*04 1 PHAS E 3 T ON HORIZONT AL SUPPL Y CFM A V A I L A B L EE X T E R N A LS T A T I CP R E S S U R E( I N .W G ) 0.2 0.4 0. 6 0.8 1.0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BH P F i e l d --- S u p p l i e d D r i v e 1 Standard Static Option Medium St atic Opt ion 900 554 0.14 681 0.22 783 0.32 870 0.42 947 0 ...

  • Bryant 558J - page 26

    26 F AN PERF ORMANCE (cont . ) T ab le 15 – 558J*04 3 PHAS E 3 T ON HORIZONT AL SUPPL Y CFM A V A I L A B L EE X T E R N A LS T A T I CP R E S S U R E( I N .W G ) 0.2 0.4 0. 6 0.8 1.0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BH P F i e l d --- S u p p l i e d D r i v e 1 Standard Static Option Medium St atic Opt ion 900 554 0.14 681 0.22 783 0.32 870 ...

  • Bryant 558J - page 27

    27 F AN PERF ORMANCE (cont . ) T ab le 17 – 558J*05 1 PHAS E 4 T ON HORIZONT AL SUPPL Y CFM A V A I L A B L EE X T E R N A LS T A T I CP R E S S U R E( I N .W G ) 0.2 0.4 0. 6 0.8 1. 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BH P Standard Static Option Medium St atic Opt ion 1200 643 0.23 762 0.35 860 0.46 944 0.58 1020 0.71 1300 674 0.28 791 0.40 88 ...

  • Bryant 558J - page 28

    28 F AN PERF ORMANCE (cont . ) T ab le 19 – 558J*05 3 PHAS E 4 T ON HORIZONT AL SUPPL Y CFM A V A I L A B L EE X T E R N A LS T A T I CP R E S S U R E( I N .W G ) 0.2 0.4 0. 6 0.8 1. 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BH P Standard Static Option Medium St atic Opt ion 1200 643 0.23 762 0.35 860 0.46 944 0.58 1020 0.71 1300 674 0.28 791 0.40 88 ...

  • Bryant 558J - page 29

    29 F AN PERF ORMANCE (cont . ) T ab le 21 – 558J*06 1 PHAS E 5 T ON HORIZONT AL SUPPL Y CFM Ava ila ble E xte rna l Sta tic Pre ssu re (i n. wg) 0.2 0.4 0. 6 0.8 1. 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BH P F i e l d --- S u p p l i e d D r i v e 1 Standard Static Option 1500 724 0.33 837 0.45 937 0.59 1028 0.74 1111 0.91 1625 765 0.40 873 0.53 ...

  • Bryant 558J - page 30

    30 F AN PERF ORMANCE (cont . ) T ab le 23 – 558J*06 3 PHAS E 5 T ON HORIZONT AL SUPPL Y CFM Ava ila ble E xte rna l Sta tic Pre ssu re (i n. wg) 0.2 0.4 0. 6 0.8 1. 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BH P F i e l d --- S u p p l i e d D r i v e 1 Standard Static Option 1500 724 0.33 837 0.45 937 0.59 1028 0.74 1111 0.91 1625 765 0.40 873 0.53 ...

  • Bryant 558J - page 31

    31 F AN PERF ORMANCE (cont . ) T ab le 25 – 558J*07 3 PHAS E 6 T ON HORIZONT AL SUPPL Y CFM A V A I L A B L EE X T E R N A LS T A T I CP R E S S U R E( I N .W G ) 0.2 0.4 0. 6 0.8 1. 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BH P F i e l d --- S u p p l i e d D r i v e 1 Standard Static Option 1800 822 0.51 927 0.66 1018 0.82 1100 0.98 1174 1.15 1950 ...

  • Bryant 558J - page 32

    32 F AN PERF ORMANCE (cont . ) T able 27 – P ULLEY A DJU STMENT UNI T MOTOR/D RIVE COMB O MOTOR PULLEY T URNS OPEN 0.0 0.5 1.0 1. 5 2.0 2.5 3.0 3.5 4. 0 4.5 5.0 04 1p h a s e Stand ard Static 854 825 795 766 736 707 678 648 619 589 560 Mediu m Static 1175 1135 1094 1054 1013 973 932 892 851 811 770 High Stat ic --- --- --- --- --- --- --- --- --- ...

  • Bryant 558J - page 33

    33 ECONOMIZER, BAROMETRI C RELIEF AND P E PERFORMANCE 0 0.1 0.2 0.3 0 500 1000 1500 2000 2500 3 - 6 Ton STATI C PR ESSURE LOSSES (in. wg) SU PPLY A IR (cfm ) C08006 Fig. 5 - - Bar ometr ic Re lie f Flow Capaci ty 0 0.1 0.2 0.3 0.4 0.5 0 5 10 15 20 25 30 3 - 6 Ton SU PPLY AI R (cfm) STATI C PRESSU RE LO SSES (in. wg) C08007 Fig. 6 - - Outdoor Ai r D ...

  • Bryant 558J - page 34

    34 ELECTRICAL INFO RMA TION T ab le 28 – 558J*04 3 TONS V --- P h --- H z VOL TAGE RANGE COMP ( ea) OFM (ea) IFM RLA LRA WAT T S FLA TYPE Max WAT T S Max AMP Draw EFF at Ful l Load FLA MIN MAX 2 0 8 --- 1 --- 6 0 187 253 16.6 79 325 1.5 Std Static 1000 5.1 70% 4.9 Med Static 1000 5.1 70% 4.9 2 3 0 --- 1 --- 6 0 187 253 16.6 79 325 1.5 Std Static ...

  • Bryant 558J - page 35

    35 ELECTRICAL INFORMA TION ( CONT) T ab le 30 – 558J*06 5 TONS V --- P H --- H Z VOL TAGE RANGE COMP ( ea) OFM (ea) IFM RLA LRA WAT T S FLA TYPE Max WAT T S Max AMP Draw EFF at Ful l Load FLA MIN MAX 2 0 8 --- 1 --- 6 0 187 253 26.2 134 325 1.5 Std Static 1000 5.1 70% 4.9 Med Static 1850 7.4 78% 7.0 2 3 0 --- 1 --- 6 0 187 253 26.2 134 325 1.5 St ...

  • Bryant 558J - page 36

    36 T able 32 – MCA /MOCP DETER MIN A TION NO C.O. OR UNP WRD C .O. UNI T V --- P H --- H Z IFM TYPE ELECTRI C HEA TER NO C. O. or UN PWRD C.O . kW FLA NO P .E. w/ P .E. (pwrd f r/uni t) MCA MOCP DISC . SIZE MCA MOCP DISC . SIZE FLA LRA FLA LRA 558J* 04 208/230 - - - 1 - - - 60 STD --- --- 27.2 40 26 95 29.1 45 29 97 3.3/4.4 15.9/18.3 27.2/29.0 40 ...

  • Bryant 558J - page 37

    37 T able 33 – MCA /MOCP DETER MIN A TION NO C.O. OR UNP WRD C .O. UNI T V --- P H --- H Z IFM TYPE ELECTRI C HEA TER NO C. O. or UN PWRD C.O . kW FLA NO P .E. w/ P .E. (pwrd f r/uni t) MCA MOCP DISC . SIZE MCA MOCP DISC . SIZE FLA LRA FLA LRA 558J* 05 208/230 - - - 1 - - - 60 STD --- --- 33.7 50 32 133 35.6 50 35 135 3.3/4.4 15.9/18.3 33.7/33.7 ...

  • Bryant 558J - page 38

    38 T able 34 – M CA/ MOC P DETER MIN A TION W/ PW RD C .O. UNI T V --- P H --- H Z IFM TYPE ELECTRI C HEA TER NO C. O. or UN PWRD C.O . kW FLA NO P .E. w/ P .E. (pwrd f r/uni t) MCA MOCP DISC . SIZE MCA MOCP DISC . SIZE FLA LRA FLA LRA 558J* 06 208/230 - - - 1 - - - 60 STD --- --- 39.2 60 37 150 41.1 60 40 152 4.9/6.5 23.5/27.1 39.2/40.0 60/60 37 ...

  • Bryant 558J - page 39

    39 T able 35 – M CA/ MOC P DETER MIN A TION W/ PW RD C .O. UNI T V --- P H --- H Z IFM TYPE ELECTRI C HEA TER NO C. O. or UN PWRD C.O . kW FLA NO P .E. w/ P .E. (pwrd f r/uni t) MCA MOCP DISC . SIZE MCA MOCP DISC . SIZE FLA LRA FLA LRA 558J* 07 208/230 - - - 3 - - - 60 STD --- --- 30.5 45 30 157 32.4 50 32 159 4.9/6.5 13.6/15.6 30.5/30.5 45/45 30 ...

  • Bryant 558J - page 40

    40 T able 36 – M CA/ MOC P DETER MIN A TION W/ PW RD C .O. UNI T V --- P H --- H Z IFM TYPE ELECTRI C HEA TER w / PWRD C.O . kW FLA NO P .E. w/ P .E. (pwr d fr/u nit) MCA MOCP DISC . SIZE MCA MOCP DISC . SIZE FLA LRA FLA LRA 558J* 04 208/230 - - - 1 - - - 60 STD --- --- 32.0 45 32 100 33.9 50 34 102 3.3/4.4 15.9/18.3 32.0/35.0 45/45 32/32 100/100 ...

  • Bryant 558J - page 41

    41 T able 37 – M CA/ MOC P DETER MIN A TION W/ PW RD C .O. UNI T V --- P H --- H Z IFM TYPE ELECTRI C HEA TER w / PWRD C.O . kW FLA NO P .E. w/ P .E. (pwr d fr/u nit) MCA MOCP DISC . SIZE MCA MOCP DISC . SIZE FLA LRA FLA LRA 558J* 05 208/230 - - - 1 - - - 60 STD --- --- 44.0 60 43 155 45.9 60 45 157 4.9/6.5 23.5/27.1 44.0/46.0 60/60 43/43 155/155 ...

  • Bryant 558J - page 42

    42 T able 38 – M CA/ MOC P DETER MIN A TION W/ PW RD C .O. UNI T V --- P H --- H Z IFM TYPE ELECTRI C HEA TER w / PWRD C.O . kW FLA NO P .E. w/ P .E. (pwr d fr/u nit) MCA MOCP DISC . SIZE MCA MOCP DISC . SIZE FLA LRA FLA LRA 558J* 06 208/230 - - - 3 - - - 60 STD --- --- 35.3 50 35 162 37.2 50 37 164 4.9/6.5 13.6/15.6 35.3/35.3 50/50 35/35 162/162 ...

  • Bryant 558J - page 43

    43 T able 39 – M CA/ MOC P DETER MIN A TION W/ PW RD C .O. UNI T V --- P H --- H Z IFM TYPE ELECTRI C HEA TER w / PWRD C.O . kW FLA NO P .E. w/ P .E. (pwr d fr/u nit) MCA MOCP DISC . SIZE MCA MOCP DISC . SIZE FLA LRA FLA LRA 558J* 07 208/230 - - - 1 - - - 60 STD --- --- 38.5 60 38 138 40.4 60 40 140 3.3/4.4 15.9/18.3 38.5/38.5 60/60 38/38 138/138 ...

  • Bryant 558J - page 44

    44 C08054 Fig. 13 - - T ypic al Power Di agr am LEGE ND C --- C o n t a c t o r , c o m p r e s s o r CAP - - - Cap acitor CB - - - Circuit break er CCH - - - Cra nkcase heater COM P - - - Com pressor motor DDC - - - Direct digital control F U --- F u s e GND - - - Groun d HPS - - - Hig h pressure switch IA Q - - - I ndoor a ir quality sensor s IF ...

  • Bryant 558J - page 45

    45 C08055 Fig. 14 - - T ypic al Wi ri ng Di agram NOT ES : T erminal board schemati c layout does not matc h actual termi nal board to sim plify circui t traces. Ensur e desi gnated jumpers on t ermi nal board are cut wh en adding sm oke det ectors , phase los s relay and rem ote s hutdown. ECONOMIZ ER NOTES: 1. 620 ohm , 1 watt , 5% re si ster s h ...

  • Bryant 558J - page 46

    46 SEQUENCE OF OPERA TION General The sequenc e below describe s the sequence of opera tion for a n elect ro- - me chanica l uni t with and wit hout a fa ctory installed EconoMi$er IV ( called “economizer” in this sequence ). For informati on regarding a di rect digital controll er , see the start - - up, opera tions, and troubleshooti ng manua ...

  • Bryant 558J - page 47

    47 GUIDE SPECIFICA T IONS - - 558J*04 - - 07 Note about t his specifica tion: Bryant wrote this specific ation in t he 2004 version of the “Maste rformat” as published by the Construc tion Specifi cation Institute. Pleas e feel free to copy this speci fication directly in to your building spec. HV AC Guide Specifica tions Siz e Range : 3 to 6 N ...

  • Bryant 558J - page 48

    48 7. Shall ha ve an LED displa y independent ly showing the status of seria l communic ation, running, e rrors, pow er , all digi tal outputs, a nd all analog input s. 8. Shall accept the follo wing inputs: Space temperature, Set point adjustment, O utdoor Ai r temperature, indoor Air quality , outdoor air quality , compre ssor lock- - out, fire s ...

  • Bryant 558J - page 49

    49 4. F ilters shall be acces sible through an access panel with “no - - tool” remova l as described in the unit cabinet section of thi s s pe cifica tion (23 81 19.13. H). 23 81 19 Self - - Contained Air Conditioners 23 81 19.13 Small- - Capacity Sel f- - Contained Air Conditioners (558J*04- - 07) 23 81 19.13.A. General 1. Outdoor , rooftop mo ...

  • Bryant 558J - page 50

    50 1. Unit ca binet shall be construct ed of galvani zed steel , and shall be bonderi zed and coated with a pre - - pai nted baked enamel finish on all ex ternally expos ed surfaces. 2. Unit cabi net exteri or paint shall be: fil m thickness, (dry) 0.003 inche s minimum , gloss (per ASTM D523, 60 _ F/1 6 _ C): 60, Hardness: H- - 2H Pencil hardness. ...

  • Bryant 558J - page 51

    51 3. Optional Copper - - fin coi ls: a. Shall be c onstructed of coppe r fins mechani cally bonde d to copper tube s and copper tube shee ts. b. G alvanized s teel tube s heets sh all not b e acceptable. c. A p olymer s trip s hall prevent co il ass embly from con tacting the sheet metal co il pan to minimize potential for galv anic corros ion bet ...

  • Bryant 558J - page 52

    52 d. C ompr ess ors shall be protected f rom an ov er- - temperatur e and over- - amperage con dition s by an inter nal, motor overl oad device . e. Compre ss or sha ll be fact ory mounted on rubber grom mets. f. Compressor motors shall have int ernal line bre ak thermal and c urrent overload protec tion. g. Crankca se heaters shall not be require ...

  • Bryant 558J - page 53

    53 l. The economizer shall maintain minimum airflow into the building du ring occupied per iod and provid e desig n ventilation rate for full o ccupancy . A remo te potentiometer may b e used to over ride the damper s et point. m. Dampe rs s hall be com pletel y closed when the uni t is in the unoc cupied mode . n. Economizer controller shall accep ...

  • Bryant 558J - page 54

    54 m. Ou tlet sh all be acces sible f rom o uts ide the un it. 8. Thru - - t he- - Ba se Connectors: a. Kits shall provide conne ctors to permi t gas and ele ctrica l connect ions to be brought t o the uni t t hrough the unit b asepan . b. Minimum of four conne ction loc ations per unit . 9. F an/F ilter Status S witch: a. Sw itch shall provide sta ...

  • Bryant 558J - page 55

    55 a. Kit shall provi de connectors to permi t gas and electri cal connec tions to be brought to the unit through the basepan. 22. Fan/Filter S tatus S witch : a. Provides s tatus of indoor (e vaporator) fan (ON / OFF) or filter (CLEAN /DIR TY ). Sta tus shall be displayed over com municati on bus w hen used with di rect digit al control s or w ith ...

Fabricant Bryant Catégorie Fan

Les documents que nous recevons du fabricant de l'appareilBryant 558J peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Bryant
- manuels d’utilisations 558J
- fiches produit Bryant
- dépliants
- ou étiquettes-énergie Bryant 558J
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Bryant 558J.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Bryant 558J, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Bryant 558J. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Bryant 558J.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Bryant 558J, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Bryant 558J par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Bryant 558J.

Le manuel d’utilisation complet Bryant, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Bryant 558J - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Bryant 558J, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lBryant 558J qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Bryant 558J - qui devraient nous aider dans les premières étapes lors de l'utilisation Bryant 558J
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Bryant 558J
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Bryant 558J dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Bryant 558J?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Bryant 558J, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Bryant 558J il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)