Manuale per l’uso APC AR8136BLK200

44 pagine 2.88 mb
Scarica

Vai alla pagina of 44

Summary
  • APC AR8136BLK200 - page 1

    Operation Symmetra™ PX 48, 96, and 160 kW 400 V 100 kW 208 V test ...

  • APC AR8136BLK200 - page 2

    Legal Disclaimer The information presented in this manual is not warranted by the Schneider Electric IT Corporation to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specic development plan. Therefore, Schneider Electric IT Corporation assumes no liability for damag ...

  • APC AR8136BLK200 - page 3

    T able of Contents About this Manual .......................................................................................................... 1 Companion Manuals ................................................................................................... 1 Find Updates to this Manual ........................................................ ...

  • APC AR8136BLK200 - page 4

    T roubleshooting ..............................................................................................................32 Status and Alarm Messages .....................................................................................32 Display Messages ......................................................................................... ...

  • APC AR8136BLK200 - page 5

    About this Manual This manual is for: • Symmetra PX 48 kW 400 V UPS • Symmetra PX 96 and 160 kW 400 V UPS and Power Distribution Unit (PDU-XR) • Symmetra PX 100 kW 208 V UPS and Power Distribution Unit (PDU) • XR Battery Enclosure Companion Manuals For additional information, see the following Symmetra PX manuals: • Receiving and Unpackin ...

  • APC AR8136BLK200 - page 6

    Overview User Interface A LOAD POWERED LED When this LED is green, power to the load is on. When the LED is yellow , the load is supplied through the batteries. When the LED is ashing yellow , the unit is in bypass. B CHECK LOG LED When this LED is green, a new event has been added to the event log. C W ARNING LED When this LED is yellow , there ...

  • APC AR8136BLK200 - page 7

    Display Interface Overview Screens The Overview Screen is the main entrance to the user functions of the display interface. The UP/DOWN navigation keys take you from one screen to another . When the system is running, the display will scroll through screens showing information about the system and any active alarms. Note: The data values shown are ...

  • APC AR8136BLK200 - page 8

    Main Menu Screen From the main menu it is possible to congure and monitor the system through the sub menu screens: UPS , Power Dist , Switchgear , Envir onment , Alarms , Log , Admin , and Help . Use the UP and DOWN arrow keys to navigate through the menu screens. Main Scr een System Bypass State: UPS Operation UPS State: On Line 4 Symmetra™ P ...

  • APC AR8136BLK200 - page 9

    Menu T ree The menu tree provides a quick overview of the functions and views you may access. UPS Power Control UPS UPS Status UPS T ests & Diags UPS Conguration T otal Loading Power Dist Modular Loading V olt-Meter Subfeeds Switchgear Status Factory Input Contacts Environment Output Relays Alarm Relay Map Env Monitoring Card Alarms All Acti ...

  • APC AR8136BLK200 - page 10

    Caution: The display provides access to more functions than described in this manual. Those functions should not be accessed without the assistance of Schneider Electric Customer Support in order to avoid unwanted load impacts. For Schneider Electric W orld-W ide Customer Support, refer to the back cover of this manual. If you by accident go beyond ...

  • APC AR8136BLK200 - page 11

    Operation Modes In an installation that does not include a maintenance bypass panel, the UPS has three operation modes: normal operation, battery operation and static bypass operation. If the installation includes a PDU, a PDU-XR, or an external maintenance bypass panel, the mode maintenance bypass operation also becomes available. Normal Operation ...

  • APC AR8136BLK200 - page 12

    Perform a T otal Power Off W ARNING: This pr ocedure will disconnect the load. Note: If shutdown via the display is disabled, then you cannot perform this procedure and the message: Command not allowed, UPS congur ed to never shutdown appears. If you want to enable shutdown via the display , this is done by a Field Service Engineer via the UPST ...

  • APC AR8136BLK200 - page 13

    7. Set the UPS SYSTEM ENABLE switch to the OFF position. 8. Set the Q2 switch to the OFF position. 9. Set the Q1 switch to the OFF position. 10. Set the Q5 breaker to the OFF position (if applicable). 1 1. V erify that the maintenance bypass switch (Q3) is in the OFF position. 7 12. Set the DC DISCONNECT switch on all of the XR Battery Enclosures a ...

  • APC AR8136BLK200 - page 14

    Start the System after T otal Power Off 1. Set the upstream utility/mains power to the ON or LOCKED IN position. If the UPS has a dual mains supply , set both supplies to the ON or LOCKED IN position. 2. Set the DC DISCONNECT switch to the ON position on all XR Battery Enclosures and the PDU-XR (if applicable) and on the main frame (only PX 48). 3. ...

  • APC AR8136BLK200 - page 15

    10. Conrm by selecting Y es, T urn UPS On and press ENTER. Confirm: Turn UPS On ? >NO, ABORT → >Yes, Turn UPS On 1 1. W ait for the UPS to turn on. Turning UPS on, Please wait... 990–3015E-001 Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation 1 1 ...

  • APC AR8136BLK200 - page 16

    T urn the UPS Load Off 1. Select UPS and press ENTER. → UPS Alarms Power Dist Log Switch Gear Admin Environment Help 2. Select UPS Power Control and press ENTER. → UPS Power Control UPS Status UPS Tests & Diags UPS Configuration 3. Select T urn UPS Off and press ENTER. → Turn UPS Off Reboot UPS UPS Into Bypass UPS To Sleep 4. Select No, D ...

  • APC AR8136BLK200 - page 17

    T urn the UPS Load On 1. Select UPS and press ENTER. → UPS Alarms Power Dist Log Switch Gear Admin Environment Help Press 2. Select UPS Power Control and press ENTER. → UPS Power Control UPS Status UPS Tests & Diags UPS Configuration Press 3. Select T urn UPS On and press ENTER. → Turn UPS On UPS On Into Bypass Press 4. Conrm by select ...

  • APC AR8136BLK200 - page 18

    T ransfer the UPS into Maintenance Bypass Operation Note: If shutdown via the display is disabled, then you cannot perform this procedure and the message: Command not allowed, UPS congur ed to never shutdown appears. If you want to enable shutdown via the display , this is done by an Field Service Engineer via the UPST uner . 1. Select UPS and p ...

  • APC AR8136BLK200 - page 19

    9. Select UPS and press ENTER. → UPS Alarms Power Dist Log Switch Gear Admin Environment Help 10. Select UPS Power Control and press ENTER. → UPS Power Control UPS Status UPS Tests & Diags UPS Configuration 1 1. Select T urn UPS Off and press ENTER. → Turn UPS Off Reboot UPS UPS into Bypass UPS to Sleep 12. Select No, Don’t Notify and p ...

  • APC AR8136BLK200 - page 20

    PDU XR (if applicable) and on the main frame (only PX 48). Return to Normal Operation from Maintenance Bypass Operation 1. Set the DC DISCONNECT switch to the ON position on all XR Battery Enclosures and the PDU-XR (if applicable) and on the main frame (only PX 48). 2. Set the Q1 switch to the ON position. 3. Set the SYSTEM ENABLE switch on the UPS ...

  • APC AR8136BLK200 - page 21

    8. Select T urn UPS On into Bypass and press ENTER. Turn UPS On → UPS On into Bypass 9. Select Continue T urn On and press ENTER. Battery back-up not available in bypass! >Cancel → >Continue Turn On 10. Conrm by selecting Y es, On Into Bypass and press ENTER. Confirm: UPS on Into Bypass >NO, ABORT → >Yes, On Into Bypass 1 1. W ...

  • APC AR8136BLK200 - page 22

    18. Select UPS out of Bypass and press ENTER. Turn UPS Off Reboot UPS → UPS out of Bypass UPS to Sleep 19. Conrm by selecting Y es, Out of Bypass and press ENTER. Confirm: UPS out of Bypass? >NO, ABORT → >YES, Out of Bypass 20. W ait for the UPS to transfer out of bypass. Putting UPS out of Bypass, please wait.... 21. The UPS is now ou ...

  • APC AR8136BLK200 - page 23

    View the Status Screens 1. Select UPS and press ENTER. → UPS Alarms Power Dist Log Switch Gear Admin Environment Help 2. Select UPS Status and press ENTER. UPS Power Control → UPS Status UPS Tests & Diags UPS Configuration 3. Use the UP and DOWN arrow keys to navigate through the Status screens. Symmetra PX 160 kW Status: On Line No UPS Ala ...

  • APC AR8136BLK200 - page 24

    Conguration System Settings Set Up the Network 1. Select Admin and press ENTER. UPS Alarms Power Dist Log Switch Gear → Admin Environment Help 2. Select Network Setup and press ENTER. → Network Setup Local Interface Date/Time Device ID 3. Select Mode and press ENTER. Stat: → Mode: IP: SM: 4. Select Fixed IP Addr to give a specic IP addr ...

  • APC AR8136BLK200 - page 25

    Change the Display Interface Settings 1. Select Admin and press ENTER. UPS Alarms Power Dist Log Switch Gear → Admin Environment Help 2. Select Local Interface and press ENTER. Network Setup → Local Interface Date/Time Device ID 3. Select Display Behavior and press ENTER. Local Password → Display Behaviour Alarm Beeper 4. Select Contrast, Key ...

  • APC AR8136BLK200 - page 26

    Change the Date and T ime 1. Select Admin and press ENTER. UPS Alarms Power Dist Log Switch Gear → Admin Environment Help 2. Select Date/T ime and press ENTER. Network Setup Local Interface → Date/Time Device ID 3. Select Date or T ime and change the settings by using the UP and DOWN arrow keys. Press ENTER to save the changes. Mode: Manual For ...

  • APC AR8136BLK200 - page 27

    Congure Output Relays 1. Select Envir onment and press ENTER. UPS Alarms Power Dist Log Switch Gear Admin → Environment Help 2. Select Output Relays and press ENTER. Input Contacts → Output Relays Alarm Relay Map 3. Select desired output relay , 1 through 4, select Conguration , and press ENTER. Input Contact:xof4 <relay name> Statu ...

  • APC AR8136BLK200 - page 28

    Maintenance Life Cycle Monitoring (LCM) The Life Cycle Monitoring (LCM) function provides UPS maintenance advice to guarantee installation availability for the user . The display gives three messages enabling the following to be identied. Display Message Status Contact APC for secure start-up Start-up check is recommended – Please call the APC ...

  • APC AR8136BLK200 - page 29

    T o return a failed module to Schneider Electric, pack the module in the original shipping materials, and return it by insured, prepaid carrier . The Schneider Electric Customer Support representative will provide the destination address. If you no longer have the original shipping materials, ask the representative about obtaining a new set. Pack t ...

  • APC AR8136BLK200 - page 30

    Replacement Parts W ARNING: All safety instructions in the Safety sheet (990-2984) should be read, understood, and followed prior to handling the system. Failure to do so could r esult in equipment damage, serious injury , or death. W ARNING: Only trained persons familiar with the construction and operation of the equipment, as well as the electric ...

  • APC AR8136BLK200 - page 31

    Replace a Power Module W ARNING: Befor e r emoving any power modules, make sur e that the r emaining power modules can support the load. W ARNING: T wo people ar e needed to lift components weighing between 18–32 kg (40–70 lbs). 1. T urn the locking latch until the arrow points downwards. 2. Unscrew the spring-activated knobs on both sides of t ...

  • APC AR8136BLK200 - page 32

    Replace a Battery W ARNING: Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the r equired pr ecautions. Caution: When replacing batteries, replace with same type and number of batteries or battery packs. Caution: Risk of explosion if battery is replaced by an incorrect type. Dispose of the bat ...

  • APC AR8136BLK200 - page 33

    Storage of the battery modules: The battery modules must be stored indoors and with their protective packaging still in place. Ambient temperature: -15 to 40 °C (5 to 104 °F) Relative humidity: 25–85% Non-condensing Store in a place free from: vibration, dust, direct sunlight, and moisture Stored batteries must be rechar ged at regular interval ...

  • APC AR8136BLK200 - page 34

    Note: When replacing batteries, always replace both batteries A+B or C+D (see illustration above) as they are interconnected in pairs. For four batteries in a row it is recommended to replace all four at the same time to ensure optimal run-time (Example 1). The batteries can also be replaced in twos, but always A+B (Example 2) or C+D (Example 3). F ...

  • APC AR8136BLK200 - page 35

    Replace a Power Distribution Module Note: The load that is connected to the actual power distribution module will not be supported when the locking latch on the module is opened. 1. Switch the breakers to the OFF position. 2. Disconnect the power cable from the power distribution module’ s extension cable or Rack-Mount PDU. 3. Open the locking la ...

  • APC AR8136BLK200 - page 36

    T roubleshooting W ARNING: Only trained persons familiar with the construction and operation of the equipment, as well as the electrical and mechanical hazards involved, may install and r emove system components. Status and Alarm Messages This section lists the status and alarm messages that the UPS might display . The messages are listed in alphab ...

  • APC AR8136BLK200 - page 37

    Display Message Meaning Corrective Action Extended Run Frame Fault One of the battery enclosures has failed. Contact Schneider Electric Customer Support (see the back cover). External DC Disconnect Switch Open The external DC DISCONNECT switch tripped. Battery power is not available or the runtime is lower than expected. Close the external DC DISCO ...

  • APC AR8136BLK200 - page 38

    Display Message Meaning Corrective Action No Power Modules Detected No power modules are available. Option 1 : Ensure that the power modules are properly installed, the two fastening screws are tight, and the locking latch is engaged. Option 2 : Check for other communication alarm messages in the log. Not Synchronized Fault System cannot synchroniz ...

  • APC AR8136BLK200 - page 39

    Display Message Meaning Corrective Action Static Bypass Switch Module Removed The system no longer detects a static bypass switch module. Option 1 : Ensure that the static bypass switch module is installed properly . Option 2 : Call Schneider Electric Customer Support for replacement of the static bypass switch module. System in Maintenance Bypass ...

  • APC AR8136BLK200 - page 40

    Modular Distribution Fault List The display interface will identify the number of the power distribution modules that has caused an alarm or warning. Display Message Meaning Corrective Action High Module Current Alarm The threshold of the high module current has been exceeded. Evaluate the threshold setting. If necessary , adjust it for your situat ...

  • APC AR8136BLK200 - page 41

    PDU Fault List Display Message Meaning Corrective Action System In Maintenance Bypass The system is in maintenance bypass: the Q2 switch is open and the Q3 switch is closed. No corrective action necessary . Min Output V oltage Alarm Phase-to-neutral output voltage for phase <L-N> has dropped below the congured limit. Evaluate the threshold ...

  • APC AR8136BLK200 - page 42

    ...

  • APC AR8136BLK200 - page 43

    ...

  • APC AR8136BLK200 - page 44

    Worldwide Customer Support Customer support is available at no charge via e-mail or telephone. Contact information is available at www .apc.com/support/contact © Schneider Electric. APC and the APC logo are owned by Schneider Electric Industries S.A.S. or their af liated companies. All other trademarks are property of their respective owners. 9 ...

Fabbricante APC Categoria Network Hardware

I documenti che otteniamo dal fabbricante del dispositivoAPC AR8136BLK200 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici APC
- manuali per l’uso AR8136BLK200
- schede prodotto APC
- opuscoli
- o etichette energetiche APC AR8136BLK200
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso APC AR8136BLK200.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione APC AR8136BLK200, manuali di manutenzione, brevi manuali o manuali utente APC AR8136BLK200. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto APC AR8136BLK200.

Manuali per l’uso simili

Manuale completo del dispositivo APC AR8136BLK200, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare APC AR8136BLK200 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti APC AR8136BLK200.

Il manuale per l’uso completo APC, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale APC AR8136BLK200 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice APC AR8136BLK200, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per APC AR8136BLK200 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo APC AR8136BLK200 - che ci dovrebbe aiutare nei primi passi durante l'uso APC AR8136BLK200
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del APC AR8136BLK200
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio APC AR8136BLK200 in un dato paese, se il problema non può essere risolto da noi stessi.