    551J SINGLE P ACKAGE ROOFTOP COOLING ONL Y SIZ ES 04 - - 06 with PURON R (R - - 410A) RE FIRGERANT Installation Instructions NOTE : Read the entire instru ction manual before s tarting the ins tallation T ABLE OF CONTENTS SAFET Y CONSIDE RA TIONS 1 .................... INS T ALLA TION 5 ............................... Step 1 - - P lan for U nit Loc ...

  • Bryant 551J - page 2

    2 ELECTRIC AL SHOCK HAZARD Failure t o follow this warning c ould ca use pe rsonal injury or dea th. Before performi ng service or mainte nance opera tions on unit, turn off main power switch t o unit and instal l lockout ta g. Ensure ele ctric al servic e to rooftop uni t agrees w ith vo ltage and amperag e lis ted on the unit rating pla te. Unit ...

  • Bryant 551J - page 3

    3 Horizontal Connections / Economizer V ertical Connections / Economizer C10057 Fig. 1 - - Unit Dimensional Drawing 551J j ...

  • Bryant 551J - page 4

    4 C10058 Fig. 1 - - Unit Dimensional Drawing (c ont.) 551J j ...

  • Bryant 551J - page 5

    5 INST ALLA TION Jobsite Survey Complete th e follo wing checks befo re ins tallation. 1. Consult local buildi ng codes and the NEC (National Electrical Code) AN SI /NF P A 70 for special installa- tion requ irements . 2. Det ermine uni t locat ion (from project pl ans) or sele ct unit loca tion. 3. Chec k for possible overhea d obstructi ons which ...

  • Bryant 551J - page 6

    6 Pad- - mou nted in st allatio n — Prepare pa d and unit supports Check a nd tighte n the bottom conde nsate drain connectio n plug Rig and pla ce uni t Convert unit to side duct c onnect ion arrangem ent Install fie ld - - fa brica ted ductwork at unit duc t openings Install out door air hood Install c ondensate l ine tra p and piping Make elec ...

  • Bryant 551J - page 7

    7 NO TES: 1. Roof curb accesso ry is shipped disa ssembled. 2. Insu lated pane ls. 3. Dimensions in [ ] are in millimeters. 4. Roof curb: galvanized stee l. 5. At tach ductwork to cu rb (flang es of duct rest on curb ). 6. Se rvice cleara nce: 4 ft on each side. 7. Direction of airflow . ROOF CURB A CCESSOR Y A UNIT SIZE CRRFCURB001A01 1’-2” [3 ...

  • Bryant 551J - page 8

    8 A-B 0.5” (13) B-C 1.0” (25) A-C 1.0” (25) MAXIMUM ALL OWABLE DIFFERENCE IN. (MM) C06110 Fig. 4 - - Un it Levelin g T olerances Ste p 5 — Field Fabr icat e Duc tw ork Cabinet re turn-ai r static pressure (a negat ive condition) shall not exceed 0.35 in. wg (87 P a) w ith economizer or 0.45 in. wg (1 12 Pa) without e conomiz er . For verti ...

  • Bryant 551J - page 9

    9 P o s i t i o n i n go nC u r b— Po sition unit on roof curb so that the follow ing clearances are maintained : 1 / 4 in. (6.4 mm) clearance between th e roof curb and the base rail inside the front and rear , 0.0 in. clearance betw een the roof curb and th e base r ail inside on the duct en d of th e unit. This will result in the dis tance bet ...

  • Bryant 551J - page 10

    10 SEAL STRIP HOOD TOP SEAL STRIP HOOD SIDE SCREEN RET AINER HOOD SIDE SCREEN TRACKS OUTDOOR AIR INLET SCREEN SEAL STRIP OUTDOOR-AIR HOOD – UNASSEMBLED HOOD SIDES AND TOP ASSEMBLED TRACKS FOR AIR INLET SCREEN HOOD SIDE HOOD TOP C07504 Fig. 9 - - Outdoor - - Air Hood Detai ls Economize r Hood — NOTE : If the pow er exhaust acces so ry is to be i ...

  • Bryant 551J - page 11

    11 Ste p 9 — Insta ll Exte rnal Conde nsate T rap and Line The uni t has one 3 / 4 -in. conde nsate drai n connec tion on the e nd of the conde nsate pan a nd an alterna te connecti on on the bottom. See Fig. 13. Unit airfl ow configura tion does not dete rmine which drain c onnecti on to use. Eit her drain c onnecti on can be used with ve rtica ...

  • Bryant 551J - page 12

    12 C 11 23 Disconnect per NEC 208/230-1-60 or Disconnect per NEC 11 13 13 23 L1 L2 L3 TB C IFC Direct Drive IFM 208/230-3-60 460-3-60 575-3-60 Units Without Disconnect Option Units With Disconnect Option L1 L2 L3 2 4 6 1 3 5 Optional Disconnect Switch Disconnect factory test leads; discard. Factory Wiring 1-ph Belt Drive IFM C10056 Fig. 15 - - Powe ...

  • Bryant 551J - page 13

    13 Convenience Outlet GFCI Pwd-CO F use Switch Pwd-CO T ransformer Control Box Access Panel C08128 Fig. 17 - - Convenience O utlet Location In st alling W eatherp r oof C over – A weathe rproof while-in-use cover for the factory-i nstall ed convenienc e outlets is now required by UL standa rds. This c over cannot be factory-m ounted due its dep t ...

  • Bryant 551J - page 14

    14 NOTICE Convenience Outlet Utilization Maximum Intermittent use : 15 Amps 2 to 3 Hours Maximum Continuous use : 8 Amps 24/7 50HJ542739 3.0 A9225 Fig. 20 - - Conv enien ce Outlet Ut ilization N otice La bel Duty Cycle: the uni t - - powere d conve nienc e outlet has a duty cycle limitation. Th e trans former is intend ed to prov ide pow er on an i ...

  • Bryant 551J - page 15

    15 X C G W2 C W2 G W1 O/B/Y2 Y2 R W1 R Y1 Y1 T H E R M O S T A T (Note 1) (Note 2) Note 1: T ypical multi-function marking. Follow manufacturer’s configuration Instructions to select Y2. Note 2: Y2 to Y2 connection required on single-stage cooling units when integrated economizer function is desired. Field Wiring Central T erminal Board T ypical ...

  • Bryant 551J - page 16

    16 DISCONNECT MOUNTING LOCA TION EMT OR RIGID CONDUIT (FIELD-SUPPLIED) SINGLE POINT BOX CENTER POST HEA TER COVERS HEA TER MOUNTING BRACKET HEA TER MODULE (LOCA TION 2) HEA TER MODULE (LOCA TION 1) SINGLE POINT BOX MOUNTING SCREW BRACKET AND CONDUIT DRIP BOOT MAIN CONTROL BOX CONTROL WIRE TERMINAL BLOCK MANUAL RESET LIMIT SWITCH C08134 Fi g. 2 5 - ...

  • Bryant 551J - page 17

    17 Sm oke Det ectors — Smoke detec tors are avai lable a s factory - - i nstalle d options on 551J model s. Smoke detec tors ma y be spec ified for Supply Air only or for Return Air wit hout or with econom izer or i n combina tion of Supply Air and Return Air . Return Air smoke de tect ors are arranged for vert ica l return configura tions only . ...

  • Bryant 551J - page 18

    18 The sens or us es a process called dif ferential sens ing to prevent gra dual environm ental c hanges from trigge ring false ala rms. A rapid change in environm ental c onditions, such as s moke from a fire , causes the sensor t o signal an alarm state b ut dus t and debris accumulated over time does not. For install ati ons using two sensors, t ...

  • Bryant 551J - page 19

    19 Compl etin g Ins tall atio n of Return Air Smok e Sens or : 1. Unscrew t he two screws holdi ng the Re turn Air Sensor detect or plate. See Fig. 34. Save the screws. 2. Re move the Re turn Air Sensor and its det ector pl ate . 3. Rot ate the de tect or plate so t he sensor is facing outwards and the sampling t ube connec tion is on the bottom. S ...

  • Bryant 551J - page 20

    20 R TU- - MP c ontr ol system — The R T U- - MP controll er , see Fig. 36, provides expanded stand - - a lone opera tion of the HV AC system pl us connec tion and c ontrol through communica tion wit h several Building Automation System s (BAS) through popular thi rd - - pa rty network systems. T he availa ble network systems a re BACnet MP/TP , ...

  • Bryant 551J - page 21

    21 3 C10044 Fig. 38 - - RTU- - M P System Contr ol Wiring Diagram 551J j ...

  • Bryant 551J - page 22

    22 T abl e 3 – RTU- - M P Co ntroll er Inputs and O utputs POI NT N AM E BA Cne t OBJ ECT NAME TYPE OF I/O CON N ECTI ON PIN NUMB ERS INPU TS Space T em perature S ensor sptsens AI (10K T hermistor) J 2 0 --- 1 , 2 Supply Air T emperature sat AI (10K T hermistor) J2 - - - 1, 2 Loca l Outside Air T emperat ure Senso r oatsens A I (10K Therm istor) ...

  • Bryant 551J - page 23

    23 Outdoor Air T e mpera ture (OA T ) Sensor - - The OA T i s fact ory- - mounte d in the EconoMi$er2 (FIOP or access ory ). It is a n ominal 10 k ohm thermis tor attached to an eyelet moun ting ring . EconoMi$e r2 - - The R T U- - MP control is used wit h EconoMi$er2 (option or accessory) for outdoor air management. The damper position is contr ol ...

  • Bryant 551J - page 24

    24 SEN J20-1 J20-2 SEN SET Jumper J20-3 SET C08461 Fig. 43 - - RTU- - M P T - - 56 Sensor Connections Connect T - - 59 - - The T - - 59 space sensor require s a separat e, isola ted power supply of 24 V AC. S ee Fig. 44 for interna l connect ions at the T - - 59. Connect the SEN terminal (BLU ) to R TU - - MP J20- - 1. Conn ect the CO M terminal (B ...

  • Bryant 551J - page 25

    25 requirem ents and t ermina l loca tions. See Fig. 47 for typica l CO 2 sensor wiring schemat ic. 8 7 6 5 4 32 1 2 1 HG 24 V AC OR 24 VDC NC ALARM RELA Y CONT ACTS COM NO } 0-10VDC SIG COM 4-20mA + + - + - J3 J4 C08635 Fig. 47 - - Indoor/Outdoor Air Quality (CO 2 )S e n s o r (33ZCSENC O2) - - T ypical Wiring Diagram T o accurately monitor th e q ...

  • Bryant 551J - page 26

    26 On 551J unit s equi pped with fa ctory - - install ed Smoke Detector (s) , the smoke detecto r contro ller implements the unit shutdown through i ts NC cont act set conne cted to t he unit’ s CTB input. The FSD func tion is initiated via the smoke de tec tor ’ s Alarm NO c ontac t set. T he R TU - - MP controll er comm unicat es the smoke de ...

  • Bryant 551J - page 27

    27 SW3 Protocol Selection PROTOC OL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 BAC net M S/TP (Ma ster) Unused OF F OFF OFF ON OF F Select B au d Sele ct Bau d Modb us (Slave) Unused OF F OFF ON ON OFF Select Bau d Se lect Ba ud N2 (Slave) Unused OF F OFF OFF ON ON OFF OFF LonWorks Unuse d ON ON OFF ON OFF OF F OFF NOTE: DS = Dip Sw itch BACnet MS/TP SW3 exam ...

  • Bryant 551J - page 28

    28 T able 4 – LEDs The LEDs on the R TU- - M P s how the status of certain f unction s If th is LE D is on ... Statu s is ... Power The R TU MP has power Rx The RTU MP is receiving data from the network segment Tx The R TU MP is tran smitting d ata over the n etwork segm ent DO# The digital output is active The Run and Error LEDs indicate contr o ...

  • Bryant 551J - page 29

    29 T a b l e5U n i tW i r e / F u s eo rH A C RB r e a k e rS i z i n gD a t a UNI T N O M . V --- P h --- H Z IFM TY PE ELEC. HTR P. E . NO C .O. or U NPWR C.O. CRHEA TER*** NOM (KW) FLA FL A NO P .E. w/P .E. (pwrd fr /un it) MCA FUSE or HACR BRKR DISC. SIZE MCA FUSE or HACR BRKR DISC. SIZE FLA LRA FLA LRA 551J*04 208/230 - - - 1 - - - 60 D D --- ...

  • Bryant 551J - page 30

    30 T a b l e5U n i tW i r e / F u s eo rH A C RB r e a k e rS i z i n gD a t a( c o n t ) UNI T N O M . V --- P h --- H Z IFM TY PE ELEC. HTR P. E . w/ P WRD C.O . CRHEA TER*** NOM (KW) FLA FL A NO P .E. w/P .E. (pwrd fr /un it) MCA FUSE or HACR BRKR DISC. SIZE MCA FUSE or HACR BRKR DISC. SIZE FLA LRA FLA LRA 551J*04 208/230 - - - 1 - - - 60 D D -- ...

  • Bryant 551J - page 31

    31 T a b l e5U n i tW i r e / F u s eo rH A C RB r e a k e rS i z i n gD a t a( c o n t ) UNI T N O M . V --- P h --- H Z IFM TY PE ELEC. HTR P. E . NO C .O. or U NPWR C.O. CRHEA TER*** NOM (KW) FLA FL A NO P .E. w/P .E. (pwrd fr /un it) MCA FUSE or HACR BRKR DISC. SIZE MCA FUSE or HACR BRKR DISC. SIZE FLA LRA FLA LRA 551J*05 208/230 - - - 1 - - - ...

  • Bryant 551J - page 32

    32 T a b l e5U n i tW i r e / F u s eo rH A C RB r e a k e rS i z i n gD a t a( c o n t ) UNI T N O M . V --- P h --- H Z IFM TY PE ELEC. HTR P. E . w/ PWRD C. O. CRHEA TER*** NOM (KW) FLA FL A NO P .E. w/P .E. (pwr d fr/u nit) MCA FUSE or HACR BRKR DISC. SIZE MCA FUSE or HACR BRKR DISC. SIZE FLA LRA FLA LRA 551J*05 208/230 - - - 1 - - - 60 D D --- ...

  • Bryant 551J - page 33

    33 T a b l e5U n i tW i r e / F u s eo rH A C RB r e a k e rS i z i n gD a t a( c o n t ) UNI T N O M . V --- P h --- H Z IFM TY PE ELEC. HTR P. E . NO C .O. or U NPWR C.O. CRHEA TER*** NOM (KW) FLA FL A NO P .E . w/P .E. (pwr d fr /unit) MCA FUSE or HACR BRKR DISC. SIZE MCA FUSE or HACR BRKR DISC. SIZE FLA LRA FLA LRA 551J*06 208/230 - - - 1 - - - ...

  • Bryant 551J - page 34

    34 T a b l e5U n i tW i r e / F u s eo rH A C RB r e a k e rS i z i n gD a t a( c o n t ) UNI T N O M . V --- P h --- H Z IFM TY PE ELEC. HTR P. E . w/ P WRD C.O . CRHEA TER*** NOM (KW) FLA FL A NO P .E . w/P .E. (pwrd f r/u nit) MCA FUSE or HACR BRKR DISC. SIZE MCA FUSE or HACR BRKR DISC. SIZE FLA LRA FLA LRA 551J*06 208/230 - - - 1 - - - 60 D D - ...

  • Bryant 551J - page 35

    35 Lege nd and Note s for T able 5 LEG END: BRKR - - - Circuit breaker CO - - - Conve ni ent o utl et DD - - - Direct dr ive ind oor fan motor DISC - - - Discon nect FLA - - - Full loa d a mps IFM - - - In door fa n motor LRA - - - Locke d roto r amps MCA - - - Min imum circu it amp s P E --- P o w e r e x h a u s t PWRD CO - - - Powere d convenien ...

  • Bryant 551J - page 36

    36 Step 12 — In sta ll Acces sori es A vailable access ories in clude: Curb Thru - - ba se connec tion kit (must be i nstall ed before unit is set on curb) Elec tric he aters and singl e - - poi ng connec tion kit s Manual outside a ir dam per T wo- - Positio n motorized o utsid e air damper EconoMi$er IV (with cont rol) EconoMi$e r2 (without con ...

Fabbricante Bryant Categoria Fan

I documenti che otteniamo dal fabbricante del dispositivoBryant 551J possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Bryant
- manuali per l’uso 551J
- schede prodotto Bryant
- opuscoli
- o etichette energetiche Bryant 551J
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Bryant 551J.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Bryant 551J, manuali di manutenzione, brevi manuali o manuali utente Bryant 551J. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Bryant 551J.

Manuali per l’uso simili

Manuale completo del dispositivo Bryant 551J, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Bryant 551J dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Bryant 551J.

Il manuale per l’uso completo Bryant, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Bryant 551J - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Bryant 551J, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Bryant 551J che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Bryant 551J - che ci dovrebbe aiutare nei primi passi durante l'uso Bryant 551J
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Bryant 551J
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Bryant 551J in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Bryant 551J?

Utilizza il modulo sottostante

Se non hai risolto il problema con Bryant 551J con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Bryant 551J è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)