    BURNERS BRULEURS BRENNER QUEMADORES BRUCIA T ORI Complying with EMC 89/336/CEE LV 73/23/CEE T echnical Documentation CIB Unigas S.p.a. - Campodarsego (PD) M03978CA Rev . 00 10/99 MANUAL FOR - INST ALLA TION - OPERA TION - MAINTENANCE LIGHT OIL BURNERS G18 G-.SP PG25 G-.SP PG30 G-.TN FOREWORD Page 2 PARTE I: INSTALLATION Page 4 PARTE II: OPERATION P ...

  • Cisco Systems G18 G-.SP - page 2

    2 PREF ACE THIS MANUAL IS SUPPLIED AS AN INTEGRAL AND ESSENTIAL PART OF THE PRODUCT AND MUST BE DELIVERED TO THE USER. INFORMATION INCLUDED IN THIS SECTION ARE DEDICATED BOTH TO THE USER AND TO PERSONNEL FOLLOWING PRODUCT INSTALLATION AND MAINTENANCE. THE USER WILL FIND FURTHER INFORMATIONS ABOUT OPERATING AND USE RESTRICTIONS, IN THE SECOND SECTIO ...

  • Cisco Systems G18 G-.SP - page 3

    3 FOREWORD 3) GENERAL INSTRUCTIONS DEPENDING ON FUEL USED 3A) ELECTRICAL CONNECTION * For safety reasons the unit must be efficiently earthed and installed as required by current safety regulations. * It is vital that all saftey requirements are met. In case of any doubt, ask for an accurate inspection of electrics by qualified personnel, since the ...

  • Cisco Systems G18 G-.SP - page 4

    4 AB B L C C L D E G KH P M G1 8 S P 275 90 200 365 475 340 255 115 230 125 121÷134 M 8 Fig. 1 P ART I: INST ALLA TION MANUAL TECHNICAL DA T A BURNER MODEL IDENTIFICATION Burners are identified by burner type and model. Burner type identification is described as follow: Type: G18 Model: G-. SP. S. *. A. (1) (2) (3) (4) (5) (6) (1) BURNER TYPE G18 ...

  • Cisco Systems G18 G-.SP - page 5

    5 Fig. 1a Fig. 2 Fig. 3 Fig. 3a 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 6 8 10 12 14 16 18 20 -1 0 1 2 3 4 10 12 14 16 18 20 22 24 26 28 30 -1 -0 . 5 0 0.5 1 1.5 2 2.5 3 10 12 14 16 18 20 22 24 26 28 30 32 34 AB B L C C L D E FGKHP M PG 25 SP PG 30 SP 515 155 345 660 85 0 267 260 520 133 29 0 125 155 M 10 PERFORMANCE CURVES OVERALL DIMENSIONS INSTALLAT ...

  • Cisco Systems G18 G-.SP - page 6

    6 MOUNTINGS AND CONNECTIONS The burners are despatched in cardboard packages. The packaging contains the following items: 1 burner; 2 flexible light oil tubes; 1 light oil filter; 1 gasket to be inserted between the burner and the boiler; 1 this manual, the Guarantee Certificate and the test certificate. T o get rid of the burner’s packing and in ...

  • Cisco Systems G18 G-.SP - page 7

    7 G18SP PG25SP PG30TN Fig. 6 Fig. 5 Fig. 5b Fig. 5a ...

  • Cisco Systems G18 G-.SP - page 8

    8 BAR G P H 8 9 1 01 11 21 31 41 51 6 1 71 8 1. 75 6. 02 6. 38 6. 73 7. 05 7. 37 7. 67 7. 96 8. 24 8. 51 8. 77 9. 02 2. 00 6. 88 7. 29 7. 69 8. 06 8. 42 8. 77 9. 10 9. 42 9. 72 10. 02 10. 31 2. 25 7. 74 8. 20 8. 65 9. 07 9. 47 9. 86 10. 23 10. 59 10. 94 11. 28 11. 60 2. 50 8. 59 9. 12 9. 61 10. 08 10. 53 10. 96 11. 37 11. 77 12. 16 12. 53 12. 89 3. ...

  • Cisco Systems G18 G-.SP - page 9

    9 Fig. 7 Fig. 9 Fig. 8 LIGHT OIL PUMPS SUNTEC AS57C Suction height: 0.5 bar Advised value to prevent air separation from oil: 0.35 bar Rated speed: max. 2850 rpm Operation viscosity: from 2 to 12 cSt Inlet pressure: max. 2 bar DELTA VM2RL2 Suction height: 0.5 bar Advised value to prevent air separation from oil: 0.35 bar Rated speed: max. 3500 rpm ...

  • Cisco Systems G18 G-.SP - page 10

    10 VBS VBS + - Fig. 12 Fig. 11 Fig. 10 Fig. 12a AIR FLOW ADJUSTMENT Burner G18SP Loose the screw VBS and rotate the air damper in the desired position, to set the air flow. At the end of settings, tight the screw VBS. Burners PG25SP - PG30TN Loose the screw VBS and set the air flow, working directly on the air damper. At the end of settings, tight ...

  • Cisco Systems G18 G-.SP - page 11

    11 P ART II: OPERA TION MANUAL LIMIT A TIONS OF USE THE BURNER IS AN APPLIANCE DESIGNED AND CONSTRUCTED TO OPERA TE ONL Y AFTER BEING CORRECTL Y CONNECTED TO A HEA T GENERA TOR (E.G. BOILER, HOT AIR GENERA TOR, FURNACE, ETC.), ANY OTHER USE IS TO BE CONSIDERED IMPROPER AND THEREFORE DANGEROUS. THE USER MUST GUARANTEE THE CORRECT FITTING OF THE APPL ...

  • Cisco Systems G18 G-.SP - page 12

    12 C AR VRT R C V Fig. 13 Fig. 13a ABCD 6 0 ° 6446 4 5 ° 1 0 546 6 0 ° 8446 4 5 ° 1 2 546 6 0 ° 8446 4 5 ° 1 2 546 G1 8 S P PG 28 SP PG 30 TN P ART III: MAINTENANCE At least once a year carry out the following maintenance procedures. If servicing is on a seasonal basis, it is recommended at the end of the season; routine sevice should be carr ...

  • Cisco Systems G18 G-.SP - page 13

    13 Fig. 14 CHECK OF THE IONIZA TION CURRENT To check the detector signal follow the prcedure shown in fig. 14. If the signal is not within the prescribed range, check the electrical contacts; check also that the combustion head is clean and the photoelectric sensor is correctly positioned. Replace it if necessary. TERMINAL BLOCK MC Scale µA DC Min ...

  • Cisco Systems G18 G-.SP - page 14

    14 ELECTRICAL DIAGRAM code 01-369 BURNER G18SP ELECTRICAL DIAGRAM code 04-575 BURNER PG25SP 1 - Electric supply 230V 50Hz 2N a.c. 2 - Don't reverse Phase and Neutral 3 - Make sure that the burner is properly hearted 1 - Electric supply 230V 50Hz 2N a.c. 2 - Don't reverse Phase and Neutral 3 - Make sure that the burner is properly hearted ...

  • Cisco Systems G18 G-.SP - page 15

    15 ELECTRICAL DIAGRAM code 04-574 BURNER PG30TN EVG1 Light oil solenoid valve I st stage EVG2 Light oil solenoid valve II nd stage F Fuses FR Photoresistor IL Main switch L Phase LF Burner operation light LB Burner lockout light LEVG1 EVG1 opening signalization light LEVG2 EVG2 opening signalization light LOA24/BOA64 Flame monitor device MA Power s ...

  • Cisco Systems G18 G-.SP - page 16

    16 SP ARE P ARTS BURNER G18SP MAINTENANCE POS. D E SC RI PTIO N C OD E POS. D E SC R IPT IO N C OD E 1 HO USI NG 3010019 19 B LA ST T UB E 3090055 2 CO NDE NSE R 60 30004 20 CO M BUS T I O N HE A D 3060115 3 M O T O R 218000 9 21 E LECT RO DE S UPP O RT 228001 6 4 F LA M E CO NT RO L DEV I CE LO A 24 20 20445 22 G A SK ET 211003 1 5 S O CKE T F O R ...

  • Cisco Systems G18 G-.SP - page 17

    17 SP ARE P ARTS BURNERS PG25SP - PG30TN MAINTENANCE POS. D E SC R IPTI ON PG 2 5SP PG 30 TN 1 E LECT RI C BO A RD 610008 6 61 00086 2 T HERM A L RELA Y -- - -- - 3 S OC K E T F O R F LA M E CO NT RO L DE V I CE 203041 5 203041 5 4 F LA M E C O NT RO L DE V I CE 202044 5 2020445 5C O N T A C T O R - - - - - - 6 I G NI TI O N T RA NSF O RM ER 217010 ...

  • Cisco Systems G18 G-.SP - page 18

    18 APPENDIX: COMPONENTS CHARACTERISTICS FLAME CONTROL DEVICE LANDIS LOA24 Page 18 LIGHT OIL PUMPS Page 19 LANDIS AUTOMA TIC CONTROLLER LOA24 FOR LIGHT OIL BURNERS Use LOA... safety devices are intended for use in conjunction with QRB... photoresistors, for lighting and controlling low capacity forced air diesel burners with max. capacity 30 kg/h in ...

  • Cisco Systems G18 G-.SP - page 19

    19 T echnical characteristics Voltage 220V-15%..240V+10% or 100V -15%...110V+10% Frequency 50...60Hz +/- 6% External fuse max.10A slow action Contact flow: - terminal 1 5 A - terminal 3 5A (incl.capacity absorbed by motor and pre- heater) Terminal flow: - terminals 4, 5 &10 1A - terminals 6&7 2A - terminal 8 5A Absorbed cap 3VA Protection I ...

  • Cisco Systems G18 G-.SP - page 20

    20 SUNTEC AS oil pumps - Oil - Flow up to 75 1/h (c.600,000 kcal/h - 700 kW) - Twin-pipe system - Single-pipe system Technical data Mounting On flange or hub in acccordance with standards DIN 24220 and ISO/TC 109 SC 3 DP 5062F Threads round-headed in accordance with ISO R 228-NFE 03005(DIN2S9) Supply and return R 1/4" Delivery R 1/8" Pres ...

  • Cisco Systems G18 G-.SP - page 21

    21 Operation The gear-set draws oil from the tank through the built-in filter and transfers it to the valve that regulates the oil pressure or tne nozzle line. All oil which does not go through the nozzle line will be dumped through the valve back to the return line or, if it is a one-pipe installation, back to the suction port in the gear-set. The ...

  • Cisco Systems G18 G-.SP - page 22

    22 T win pipe installation Single pipe installation (remove the by-pass plug “P”) A Closed by-pass solenoid valve B Opened by-pass solenoid valve C Opened cut-off solenoid valve D Closed cut-off solenoid valve 1 Manometer plug 2 To nozzle 3 Shaft seal 4 Return to suction 5 By-pass plug 6 Return (twin pipe installation) 7 Suction (twin pipe inst ...

  • Cisco Systems G18 G-.SP - page 23

    23 ...

  • Cisco Systems G18 G-.SP - page 24

    Via C. Colombo, 9 - 35011 Campodarsego (PD) Italy Tel. +39-049-9200944 - Fax +39-049-9200945-9201269 Internet: www.cibunigas.it - E mail: cibunigas@cibunigas.it ...

Fabbricante Cisco Systems Categoria Burner

I documenti che otteniamo dal fabbricante del dispositivoCisco Systems G18 G-.SP possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Cisco Systems
- manuali per l’uso G18 G-.SP
- schede prodotto Cisco Systems
- opuscoli
- o etichette energetiche Cisco Systems G18 G-.SP
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Cisco Systems G18 G-.SP.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Cisco Systems G18 G-.SP, manuali di manutenzione, brevi manuali o manuali utente Cisco Systems G18 G-.SP. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Cisco Systems G18 G-.SP.

Manuali per l’uso simili

Manuale completo del dispositivo Cisco Systems G18 G-.SP, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Cisco Systems G18 G-.SP dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Cisco Systems G18 G-.SP.

Il manuale per l’uso completo Cisco Systems, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Cisco Systems G18 G-.SP - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Cisco Systems G18 G-.SP, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Cisco Systems G18 G-.SP che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Cisco Systems G18 G-.SP - che ci dovrebbe aiutare nei primi passi durante l'uso Cisco Systems G18 G-.SP
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Cisco Systems G18 G-.SP
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Cisco Systems G18 G-.SP in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Cisco Systems G18 G-.SP?

Utilizza il modulo sottostante

Se non hai risolto il problema con Cisco Systems G18 G-.SP con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Cisco Systems G18 G-.SP è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)