    Operating Instructions 8000012364 BAL, en Operating Instructions "UniVert 2" inverter and SBS option AEG Power Supply Systems GmbH Department: PPSD TED Name: Gleitsmann/Schenuit Revision: 01 Date: 06.08.2008 ...

  • AEG 8000012364 BAL - page 2

    "UniVert 2" inverter Page 2 of 42 8000012364 BAL, en Notes on these Operating Instructions Duty to Provide Information These operating instructions must be read carefully by all persons working with or on the inverter system prior to installation and initial start-up. These operating instructions are a composite part of the inverter syste ...

  • AEG 8000012364 BAL - page 3

    "UniVert 2" inverter Page 3 of 42 8000012364 BAL, en Abbreviations The following abbreviations are used in these instructions: INV = Inverter SBS = Static Bypass Switch DOU = Display and Operation Unit SMPS = Switch Mode Power Supply PSM = Power Supply Monitoring Hotline Do you have any suggestions for improving these operating instructio ...

  • AEG 8000012364 BAL - page 4

    "UniVert 2" inverter Page 4 of 42 8000012364 BAL, en Table of Contents Notes on these Operating Instructions ...........................................2 1 Safety Instructions!................................................................6 1.1 Important Instructions and Explanations ..................................6 1.2 Accident Preve ...

  • AEG 8000012364 BAL - page 5

    "UniVert 2" inverter Page 5 of 42 8000012364 BAL, en 6 Maintenance .........................................................................29 7 Troubleshooting ...................................................................30 7.1 No Output Voltage or Output Current Present (with connected load) ....................................... ...

  • AEG 8000012364 BAL - page 6

    "UniVert 2" inverter Page 6 of 42 8000012364 BAL, en 1 Safety Instructions! 1.1 Important Instructio ns and Explanations The instructions for operation and maintenance, as well as th e following safety regulations must be complied with to ensure the safety of personnel as well as the availability of the unit. All personnel installing/dism ...

  • AEG 8000012364 BAL - page 7

    "UniVert 2" inverter Page 7 of 42 8000012364 BAL, en 1.3 Danger during Maintenance and Repair Work CAUTION: The voltages applied to the INV can be fatal. Prior to start-up and/or maintenance work always disconnect the INV from the power supply and ensure that the unit cannot be switched on . The capacitors must be discharged. Free-standin ...

  • AEG 8000012364 BAL - page 8

    "UniVert 2" inverter Page 8 of 42 8000012364 BAL, en 1.5 Safety Awareness The qualified personnel defined in chapter 1.4 are responsible for safety. They are also responsible for ensuring that only suitably qualified persons are permitted access to the IN V system or the safety area. The following points must be observed: All working proc ...

  • AEG 8000012364 BAL - page 9

    "UniVert 2" inverter Page 9 of 42 8000012364 BAL, en 1.7 Liability No liability is accepted if the inverter system is used for applications not intended by the manufacturer. Any measures necessary for the prevention of injury, or damage to equipment is the responsibility of the operator or user. In the event of any claims in connection wi ...

  • AEG 8000012364 BAL - page 10

    "UniVert 2" inverter Page 10 of 42 8000012364 BAL, en 2 General Information 2.1 System Description Depending on the system design, the following versions of safe AC power supply are possible (Figure 1): • Individual INV operation • Parallel operation of several INVs • Individual or parallel operation with SBS DC A C load INV = ~ Ind ...

  • AEG 8000012364 BAL - page 11

    "UniVert 2" inverter Page 11 of 42 8000012364 BAL, en Individual INV operation: Here an INV is supplied with DC and itself supplies the AC load. In the event of INV fault or switch-off, the load is no longer supplied. Parallel INV operation: In order to increase redundancy or performance, up to 8 INVs of the same type and the same output ...

  • AEG 8000012364 BAL - page 12

    "UniVert 2" inverter Page 12 of 42 8000012364 BAL, en Parallel INV operation: Prerequisite for parallel operation is that the INVs on the DC and AC side are connected in parallel, interconnected via CAN bus (16-pin, X7) and correctly addressed. The general behaviour of an individual INV is as described in the previous paragraph. The loads ...

  • AEG 8000012364 BAL - page 13

    "UniVert 2" inverter Page 13 of 42 8000012364 BAL, en 2.3 Description of the INV Its electronic high-performance components make the INV suitable for universal applications. It has a very high degree of operational reliability, optimum efficiency and excellent communication capability with other systems thanks to integrated interfaces. Th ...

  • AEG 8000012364 BAL - page 14

    "UniVert 2" inverter Page 14 of 42 8000012364 BAL, en Figure 2 illustrates the principle of a n INV. In normal operation, the load is supplied "Online" by the INV. With systems comprising several parallel INVs, the load current is divided in accordance with the number of INVs. Depending on the system design, a power supply using ...

  • AEG 8000012364 BAL - page 15

    "UniVert 2" inverter Page 15 of 42 8000012364 BAL, en 2.5 Description of the SBS Its electronic high-performance components make the SBS highly overload-resistant and thus capable of quickly eliminating load short circuits. The SBS can be used as the central SBS for parallel operation of up to 8 INVs. Another outstanding characteristic of ...

  • AEG 8000012364 BAL - page 16

    "UniVert 2" inverter Page 16 of 42 8000012364 BAL, en 2.6 Principle of Operatio n of the SBS, Electrical If the SBS is supplied by connecting the mains or the load voltage, the corresponding operating status is automatically activated after 3 to 5 seconds. With mains operation, the DOU displays load voltage and SBS current. With all other ...

  • AEG 8000012364 BAL - page 17

    "UniVert 2" inverter Page 17 of 42 8000012364 BAL, en 3 Function of the Inverter For technical data or unit settings, refer to the Te chnical Data Sheet in chapter 8. 3.1 DC Input The inverter is operated with 48 V (or 60 V) DC voltage. The input voltage is fuse-protected outside the INV. For details, refer to the technical data. An integ ...

  • AEG 8000012364 BAL - page 18

    "UniVert 2" inverter Page 18 of 42 8000012364 BAL, en 3.7 ON/OFF Switch The inverter is set ready for operation using the DOU switch on the front panel. The monitoring functions with their respective messages are only active when the inverter is switched on. After switch-off, all faults are acknowledged. The settings of the DIL switches a ...

  • AEG 8000012364 BAL - page 19

    "UniVert 2" inverter Page 19 of 42 8000012364 BAL, en Switches S2.4, S2.5 and S2.6: Own Address (INV) The settings must be different on all INVs! Standard setting: Address 1: S2.4, S2.5 and S2.6 open S2.4 S2.5 S2.6 Address 1 0 0 0 Address 2 0 0 1 Address 3 0 1 0 Address 4 0 1 1 Address 5 1 0 0 Address 6 1 0 1 Address 7 1 1 0 Address 8 1 1 ...

  • AEG 8000012364 BAL - page 20

    "UniVert 2" inverter Page 20 of 42 8000012364 BAL, en 3.10 Signalling, Displays and Remote Signals The following signals are indicated via LEDs on the front panel: Display Colour Operating status Operation green INV operation U O OK green INV output voltage present U I < red Input voltage < 85% of rated voltage, INV has switched off ...

  • AEG 8000012364 BAL - page 21

    "UniVert 2" inverter Page 21 of 42 8000012364 BAL, en 4 Function of the SBS (optional) For the technical data or unit settings, refer to th e chapter “Technical Data”. 4.1 Operating Statuses The following operating statuses are possible: "PowerUp": Status after PowerUp or Reset. The control system checks the ambient conditio ...

  • AEG 8000012364 BAL - page 22

    "UniVert 2" inverter Page 22 of 42 8000012364 BAL, en 4.3 AC Mains Input (X1) The SBS is connected to a 230 V AC mains. The input voltage is fuse protected outside the S BS. For details refer to the technical data. The input voltage is continuously monitored (see chapter 4.4). When the mains voltage is present, the green "mains prese ...

  • AEG 8000012364 BAL - page 23

    "UniVert 2" inverter Page 23 of 42 8000012364 BAL, en 4.10 CAN Bus Interfaces (X6, X7) The unit can be controlled and monitored via the 10-pin CAN bus connector X6, if the SBS is installed in a power supply cabinet with PSM control unit. The CAN bus connector X7 is always required for communication with the INV when operated with SBS. In ...

  • AEG 8000012364 BAL - page 24

    "UniVert 2" inverter Page 24 of 42 8000012364 BAL, en Switches S3.7 and S3.8: number of redundant INVs S3.7 S3.8 0 INVs 0 0 1 INV 0 1 2 INVs 1 0 3 INVs 1 1 The settings must be the same on all INVs and the SBS! Standard setting: S3.7 and S3.8 open Switches S3.4 and S3.5: not used Switch S3.6: Switchover with gap (yes/no) Standard setting: ...

  • AEG 8000012364 BAL - page 25

    "UniVert 2" inverter Page 25 of 42 8000012364 BAL, en With SBS ready: "U=230.0V" Load voltage " ready" Operating status With SBS blocked: "U=230.0V" Load voltage "blocked" Operating status With SBS Power Up: " " (nothing displayed) "PowerUp" Operating status With SBS fault: " ...

  • AEG 8000012364 BAL - page 26

    "UniVert 2" inverter Page 26 of 42 8000012364 BAL, en Switchover with gap: The switchover from INV to SBS is carried out without interruption if the INV and SBS circuit are synchronous. If the INV and SBS circuit are not synchronous, the SBS does not block in this operating mode. If the INV is switched off due to asynchronism or if it fai ...

  • AEG 8000012364 BAL - page 27

    "UniVert 2" inverter Page 27 of 42 8000012364 BAL, en 5 Start-Up 5.1 Installation When installing the INV, the following regulations must be observed: • The INV has been designed for use in a dry room, practically free of dust. • It is imperative to observe the specifications concerning ambient temperature and site altitude (see chapt ...

  • AEG 8000012364 BAL - page 28

    "UniVert 2" inverter Page 28 of 42 8000012364 BAL, en Parallel INV operation: • Switch off the INV, switch on miniature circuit-breaker F1 • Set the DIL switches • Insert the AC fuses • Connect the DC supply • Switch on all INVs one after the other • (The output contactors K7 of the INVs start at the same time as soon as n-R I ...

  • AEG 8000012364 BAL - page 29

    "UniVert 2" inverter Page 29 of 42 8000012364 BAL, en 6 Maintenance Attention! Disconnect the unit from the power supply prior to all maintenance work. Always observe the safety instructions! (See chapter 1.) The INV consists of state-of-the-art components which are almost non-wearing. We do, however, recommend regular visual and function ...

  • AEG 8000012364 BAL - page 30

    "UniVert 2" inverter Page 30 of 42 8000012364 BAL, en 7 Troubleshooting Attention! All work on the unit may be carried out by specially trained qualified personnel only. Always observe the safety instructions! (See chapter 1.) 7.1 No Output Voltage or Output Current Present (with connected load) Individual INV operation: • DC present an ...

  • AEG 8000012364 BAL - page 31

    "UniVert 2" inverter Page 31 of 42 8000012364 BAL, en 8 Technical Data 8.1 General Data INV DC input current ............................ < rated input current DC fuse required ........................... gL 80 A with type 3.3 kVA 48 V gL 63 A with type 3.3 kVA 60 V gL 20 A with type 3.3 kVA 220 V gL 80 A with type 1.5 kVA 24 V gL 36 A ...

  • AEG 8000012364 BAL - page 32

    "UniVert 2" inverter Page 32 of 42 8000012364 BAL, en Messages ...................................... - Operation LED green - Output voltage ok LED green - Input undervoltage U E < LED red - Input overvoltage U E > LED red - Fault LED red - Overtemperature ϑ > LED red - Collective fault LED red Remote signals (X3) .............. ...

  • AEG 8000012364 BAL - page 33

    "UniVert 2" inverter Page 33 of 42 8000012364 BAL, en Mechanical stability and vibration resistance ................. To VDE 0160 Version 5.88 Item 7.2.2 Surface painted with ...................... RAL 7032 (front panel) Dimensions (w x h x d) .................. 483 x 174 x 460 mm (19" x 4 height modules) (type 1.5 and 3.3 kVA) 483 x ...

  • AEG 8000012364 BAL - page 34

    "UniVert 2" inverter Page 34 of 42 8000012364 BAL, en - Power cables ............................... Burst test in acc. with EN 61000-4-4, 2 kV Surge test in acc. with EN 61000-4-5, 2 kV asymmetrical - Control cables ............................. Burst test in acc. with EN 61000-4-4, 2 kV Surge test in acc. with EN 61000-4-5, 2 kV asymmet ...

  • AEG 8000012364 BAL - page 35

    "UniVert 2" inverter Page 35 of 42 8000012364 BAL, en Protection class ............................. IP 20 Cooling .......................................... Forced air cooling Intake air temperature ................... At rated current 0°C to 45°C, measured below the SBS Storage temperature ...................... -20°C to +70°C Ambie ...

  • AEG 8000012364 BAL - page 36

    "UniVert 2" inverter Page 36 of 42 8000012364 BAL, en 8.3 Electrical Data Typ e E-number G48 – 60 E230/14,4/2rfg-CFp3,3 3000000352 G220 E 230/14,4/2rfg-CFp3,3 300000601 Rated output capacity 3.3 kVA with power factor 0.8 Power factor range 0 inductive to 0 capacitive Rated output voltage 230 V ± 0.5 static, ± 3% dynamic at 100% load c ...

  • AEG 8000012364 BAL - page 37

    "UniVert 2" inverter Page 37 of 42 8000012364 BAL, en Typ e E-number G48 – 60 E230/6,5/2rfg-CFp1,5 3000000351 G24 E230/6,5/2rfg-CFp1,5 3000000602 Rated output capacity 1.5 kVA with power factor 0.8 Power factor range 0 inductive to 0 capacitive Rated output voltage 230 V ± 0.5 static, ± 3% dynamic at 100% load ch ange Output frequency ...

  • AEG 8000012364 BAL - page 38

    "UniVert 2" inverter Page 38 of 42 8000012364 BAL, en Typ e E-number G110 E230/10,9/2rfg-CFp2,5 3000000263 Rated output capacity 2.5 kVA with power factor 0.8 Power factor range 0 inductive to 0 capacitive Rated output voltage 230 V ± 0.5 static, ± 3% dynamic at 100% load ch ang e Output frequency 50 Hz ± 0.05% THD factor < 3% Rated ...

  • AEG 8000012364 BAL - page 39

    "UniVert 2" inverter Page 39 of 42 8000012364 BAL, en Typ e E-number E230 E230/115/2-VFp26,5-8 3000000646 Rated output capacity 26.5 kVA Power loss < 200 W AC rated input voltage 230 V AC rated input frequency 50 Hz Monitoring system s AC mains undervoltage, blocking of the SBS Fault < 90% nominal (207 V), without delay Acknowledgem ...

  • AEG 8000012364 BAL - page 40

    "UniVert 2" inverter Page 40 of 42 8000012364 BAL, en 9 Dimensional Dra wing Figure 6 Inverter dimensions (type 1.5 and 3.3 kVA) ...

  • AEG 8000012364 BAL - page 41

    "UniVert 2" inverter Page 41 of 42 8000012364 BAL, en Figure 7 Inverter dimensions (type 2.5 kVA) ...

  • AEG 8000012364 BAL - page 42

    "UniVert 2" inverter Page 42 of 42 8000012364 BAL, en Front vie w Rear vie w Air in let 483 7 PE connecti on X1, X2 X7 X6 X12 A ir ou tlet UniVert 2 460 11.5 37.7 101.6 177 (4 height mod. ) Figure 8 SBS dimensions ...

Fabbricante AEG Categoria Marine Battery

I documenti che otteniamo dal fabbricante del dispositivoAEG 8000012364 BAL possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici AEG
- manuali per l’uso 8000012364 BAL
- schede prodotto AEG
- opuscoli
- o etichette energetiche AEG 8000012364 BAL
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso AEG 8000012364 BAL.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione AEG 8000012364 BAL, manuali di manutenzione, brevi manuali o manuali utente AEG 8000012364 BAL. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto AEG 8000012364 BAL.

Manuali per l’uso simili

Manuale completo del dispositivo AEG 8000012364 BAL, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare AEG 8000012364 BAL dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti AEG 8000012364 BAL.

Il manuale per l’uso completo AEG, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale AEG 8000012364 BAL - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice AEG 8000012364 BAL, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per AEG 8000012364 BAL che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo AEG 8000012364 BAL - che ci dovrebbe aiutare nei primi passi durante l'uso AEG 8000012364 BAL
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del AEG 8000012364 BAL
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio AEG 8000012364 BAL in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su AEG 8000012364 BAL?

Utilizza il modulo sottostante

Se non hai risolto il problema con AEG 8000012364 BAL con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con AEG 8000012364 BAL è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)