    Inst allation Smart-UPS ® VT XR Battery Enclosure 10-40 kV A 380/400/415 V 10-30 kV A 208/220 V 10-30 kV A 200/208 V ...

  • APC 10-40 KVA 380/400/415 V - page 2

    ...

  • APC 10-40 KVA 380/400/415 V - page 3

    Content s Smart-UPS VT ® 10-40 kVA 380/4 00/415 V, 2 08/220 V, 200/208 V Battery Ins tallation i Safety .......... ............ ......... ................ ............... ............. .... 1 IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Prepare for Floor-Anchoring (op tional) ...

  • APC 10-40 KVA 380/400/415 V - page 4

    Smart-UPS VT ® 1 0-40 kVA 380/400/41 5 V, 208/220 V, 200 /208 V Bat tery Insta llation ii Final Mechanical Assemb ly ........ ......... ......... ................ 20 Level the Enc losures (L-shaped Floor Anchoring Brackets) and Instal l Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 0 Level the enclosures . ...

  • APC 10-40 KVA 380/400/415 V - page 5

    1 Smart-UPS VT ® 10-40 k VA 380/400/415 V, 208/220 V, 200/208 V Battery Installation Safety IMPORT ANT SAFETY INSTRUCTIONS - S A VE THESE INSTRUCTIONS W arning: • ALL safety instructio ns in the Safety Sheet (9 90-2822) must be r ead, understoo d, and followed when instal ling the UPS s ystem. Failu re t o do so could r esult in e quipment damag ...

  • APC 10-40 KVA 380/400/415 V - page 6

    Smart-UPS VT ® 10-40 kVA 380/400 /415 V, 208/220 V, 2 00/208 V Batte ry Installation 2 Prep are for Floor-Anchoring (optional) Note: If floor anchoring and batter y securing is required, rea d this section. If not, see “Pr epar e for Cables ” on page 5. Note: Allow f or enough wor king space behind the enclosure f or electrical work to be carr ...

  • APC 10-40 KVA 380/400/415 V - page 7

    3 Smart-UPS VT ® 10-40 k VA 380/400/415 V, 208/220 V, 200/208 V Battery Installation Hole positions for a stand-alone UPS en closu re with L-shaped anchoring br ackets Note: Recommende d minimum number of scre ws per encl osure for the L-shaped bra ckets is four; one in each corner . Recommended flo or bolt size: M8. Model wi dth: 352 mm (1 3.85 i ...

  • APC 10-40 KVA 380/400/415 V - page 8

    Smart-UPS VT ® 10-40 kVA 380/400 /415 V, 208/220 V, 2 00/208 V Batte ry Installation 4 Hole position s for up to four UPS unit s in p arallel with U-shaped an choring brackets. Note: Recommended minimum number of f loor screws for the below two configurati ons is 10. Model wi dth: 352 mm (1 3.85 in) . Model wi dth: 523 mm (2 0.59 in) . T op vi ew ...

  • APC 10-40 KVA 380/400/415 V - page 9

    5 Smart-UPS VT ® 10-40 k VA 380/400/415 V, 208/220 V, 200/208 V Battery Installation Prep are for Cables Remove the front panel 1. T urn th e scre w to t he right t o the un locked position . 2. Pul l the top of the front panel away from the UPS. 3. Lif t the fr ont panel free of the two slots at th e bottom o f the encl osure. 4. Lif t the batter ...

  • APC 10-40 KVA 380/400/415 V - page 10

    Smart-UPS VT ® 10-40 kVA 380/400 /415 V, 208/220 V, 2 00/208 V Batte ry Installation 6 Remove the cable landin g cover and bo ttom plates T o access the cable landing ar ea in the UPS and th e XR Battery Enclosu re(s), f ollow this procedure : 1. Loos en the si x M 4 screws from the cable l anding cove r plate o n the UPS and the XR Batt ery Enclo ...

  • APC 10-40 KVA 380/400/415 V - page 11

    7 Smart-UPS VT ® 10-40 k VA 380/400/415 V, 208/220 V, 200/208 V Battery Installation Remove the XR Battery Modu les Heavy: Use t wo people t o lift the batter y modules. Not e: The XR Battery Enc losures ship wit h two ba ttery modu les. All ba ttery modules in the UPS and the X R Batter y Enclosur e(s) must b e removed bef ore interc onnecting th ...

  • APC 10-40 KVA 380/400/415 V - page 12

    Smart-UPS VT ® 10-40 kVA 380/400 /415 V, 208/220 V, 2 00/208 V Batte ry Installation 8 Anchor the UPS and additional XR Battery or UPS Enclos ure( s) (op tiona l) Note: Enclos ures can be kept apart or assembled and anchored with in terconnection p lates and brackets : SUVTOP T004: 352 mm (13.8 5 in) UPS enclosure to XR enclos ure, SUVTOP T005: 52 ...

  • APC 10-40 KVA 380/400/415 V - page 13

    9 Smart-UPS VT ® 10-40 k VA 380/400/415 V, 208/220 V, 200/208 V Battery Installation Note: The U-s haped interconne ction bra ckets are 1-2 mm hig her than the openi ng below the enclosur e to inact ivate the cast ers. Ther efore, the enclo sure must be til ted when pla cing the U- shaped int erconnection br ackets un der the enclosur e. 3. In eac ...

  • APC 10-40 KVA 380/400/415 V - page 14

    Smart-UPS VT ® 10-40 kVA 380/400 /415 V, 208/220 V, 2 00/208 V Batte ry Installation 10 6. In sert the interco nnection plates betwee n the two enclosur es. One is positio ned toward the front an d the other toward the re ar . Not e how the “win gs” on the in terconne ction plates r est in slot s at the top of the inner panel on t he XR Batter ...

  • APC 10-40 KVA 380/400/415 V - page 15

    11 Smart-UPS VT ® 10-40 kV A 380/400/4 15 V, 208/220 V, 20 0/208 V Battery Ins tallation Run the Cables Connect Power in Inst allations wi th Busbars W arning: Befo re carry ing out t he ste ps b elow , you m ust foll ow th e T ota l Pow er O ff proce dure in the Oper ation manual. Inst all isolators See “Spec ifications ” on page 23 fo r torq ...

  • APC 10-40 KVA 380/400/415 V - page 16

    Smart-UPS VT ® 10-40 kVA 380/400 /415 V, 208/220 V, 2 00/208 V Batte ry Installation 12 Inst a ll busbars 523 mm (20 .59 in) UPS Sys tem with the UPS placed to the l eft ( seen fr om the fro nt). 1. In stall the followi ng baying ki t busbar s between t he UPS and XR1: 880-1607 be tween the vertic al busbar N on the UPS and busbar 4 on XR1 880-160 ...

  • APC 10-40 KVA 380/400/415 V - page 17

    13 Smart-UPS VT ® 10-40 kV A 380/400/4 15 V, 208/220 V, 20 0/208 V Battery Ins tallation 523 m m (20. 59 in) U PS sys tem w ith the UP S pla ced to the righ t (seen from the front ). 1. In stall the followi ng baying ki t busbar s between t he UPS and XR1: 880-1607 be tween the vertic al busbar N on the UP S and busbar 3 on XR1 880-1605 be tween v ...

  • APC 10-40 KVA 380/400/415 V - page 18

    Smart-UPS VT ® 10-40 kVA 380/400 /415 V, 208/220 V, 2 00/208 V Batte ry Installation 14 352 m m (13. 85 in) U PS sys tem w ith the UP S plac ed to th e righ t (seen fro m the fro nt). 1. In stall the followi ng baying ki t busbar s between t he UPS and XR1: 880-1604 be tween the vertic al busbar N on the UPS and busbar 4 on XR1 880-0939 be tween t ...

  • APC 10-40 KVA 380/400/415 V - page 19

    15 Smart-UPS VT ® 10-40 kV A 380/400/4 15 V, 208/220 V, 20 0/208 V Battery Ins tallation 352 m m (13. 85 in) U PS sy stem w ith the UPS pla ced to the left (see n from the fron t). 1. In stall the followi ng baying ki t busbar s between t he UPS and XR1: 880-1604 be tween the vertic al busbar N on the UP S and busbar 3 on XR1 880-1604 be tween the ...

  • APC 10-40 KVA 380/400/415 V - page 20

    Smart-UPS VT ® 10-40 kVA 380/400 /415 V, 208/220 V, 2 00/208 V Batte ry Installation 16 Connect Power in Inst allations wi th Cables Inst a ll power cables See “Recomme nded cable sizes” on p age 23 . Inst all po wer cables bet ween the U P S and t he XR Bat t ery En closure. 1. In the UPS, feed the ca ble up through the conduit box or throug ...

  • APC 10-40 KVA 380/400/415 V - page 21

    17 Smart-UPS VT ® 10-40 kV A 380/400/4 15 V, 208/220 V, 20 0/208 V Battery Ins tallation Inst all po wer cable s betw een two XR B attery Enclos ures. 1. Fee d the cable up throu gh the condu it box on XR1 or throu gh the transpar ent cable route br acket (not show n) to the cable connec tion area . 2. Conne ct the (-) cab le to busb ar no. 5 (-), ...

  • APC 10-40 KVA 380/400/415 V - page 22

    Smart-UPS VT ® 10-40 kVA 380/400 /415 V, 208/220 V, 2 00/208 V Batte ry Installation 18 Connect Co mmunicatio n Cables 1. Fee d the cable from pi n connect ion J10 6 in the UPS do w n throu gh the conduit (i f appliccable ). 2. Run t he cable u p into the XR condui t and conne ct it to pin con nection J200 in t he XR Batter y Enclosure . 3. If you ...

  • APC 10-40 KVA 380/400/415 V - page 23

    19 Smart-UPS VT ® 10-40 kV A 380/400/4 15 V, 208/220 V, 20 0/208 V Battery Ins tallation Connect the EPO Connect the EPO to the UPS and the XR Battery Enclosure 1. Conne ct the EPO ( Em er gency Power Off) to J10 8 in the UPS a nd to J203 in the XR Bat tery Enclosure by guiding the cable th rough conduits . 2. Conne ct the EPO by using this conf i ...

  • APC 10-40 KVA 380/400/415 V - page 24

    Smart-UPS VT ® 10-40 kVA 380/400 /415 V, 208/220 V, 2 00/208 V Batte ry Installation 20 Final Mechanical Assembly Level the Enclosures ( L-shaped Floor Anchoring Bracket s) and Inst all Bat teries Note: The le veling feet and the L-sh aped flo or anch oring brac ets (re use of tr ansportation brackets ) are use d in some conf igurati ons inst ead ...

  • APC 10-40 KVA 380/400/415 V - page 25

    21 Smart-UPS VT ® 10-40 kV A 380/400/4 15 V, 208/220 V, 20 0/208 V Battery Ins tallation Inst a ll battery-secu ring and floor-ancho ring brackets 1. In stall the batt eries by pushing them al l the way i nto th e enclosur e. 2. If requir ed, install t he battery s ecuring bra ckets t o hold the bat teries firml y in pla ce. Note! Do not install t ...

  • APC 10-40 KVA 380/400/415 V - page 26

    Smart-UPS VT ® 10-40 kVA 380/400 /415 V, 208/220 V, 2 00/208 V Batte ry Installation 22 Reinst all the Enclosure Plat es Reinstall the cable landing cov er plates and the bottom plates 1. Rei nstall t he cable landin g cover plates on the XR Battery Encl osure(s) 2. In stall the upper part of t he conduit box (i f applicable) on all enclosur es. 3 ...

  • APC 10-40 KVA 380/400/415 V - page 27

    23 Smart-UPS VT ® 10-40 kV A 380/400/4 15 V, 208/220 V, 20 0/208 V Battery Ins tallation S pecifications Bat ter y volt age and cu rrent Recommended cab le sizes Note: Power t erminal lug di ameter: minimum 6 mm (0.2 in). T orque value: 45 lbf-in/ 7 Nm. Note: Use Mol ex lug type or equiva lent, and f ollow the manufactur er ’ s specif i cations ...

  • APC 10-40 KVA 380/400/415 V - page 28

    Smart-UPS VT ® 10-40 kVA 380/400 /415 V, 208/220 V, 2 00/208 V Batte ry Installation 24 Post-Inst allation Checklist Use the f ollowing checkli st to ver ify that the XR Batt ery Enclos ure has been inst alled cor rectly: Note: If a problem occurs, cal l Customer Support (see the back cover). See also t he Operati on Manual loc a ted in t he docum ...

  • APC 10-40 KVA 380/400/415 V - page 29

    ...

  • APC 10-40 KVA 380/400/415 V - page 30

    ...

  • APC 10-40 KVA 380/400/415 V - page 31

    ...

  • APC 10-40 KVA 380/400/415 V - page 32

    11 / 2 0 0 9 990-1740D-001 *990-1740D-001* APC W orldwide Customer Support Customer s upport for this or any oth er APC product i s availab l e at no c harge in any of the followin g ways: • V isit the APC W eb site to a ccess docu m ents i n the APC Knowled ge Base and to s ubmit custo m er support requests. – www .apc.com ( Corporate Headquar ...

メーカー APC カテゴリー Power Supply

APC 10-40 KVA 380/400/415 Vのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 10-40 KVA 380/400/415 Vの取扱説明書
- APCの製品カード
- パンフレット
- またはAPC 10-40 KVA 380/400/415 Vの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、APC 10-40 KVA 380/400/415 Vの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、APC 10-40 KVA 380/400/415 Vの取り付け説明書、サービスマニュアル、簡易説明書、またはAPC 10-40 KVA 380/400/415 Vのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、APC 10-40 KVA 380/400/415 Vの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

APC 10-40 KVA 380/400/415 Vデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがAPC 10-40 KVA 380/400/415 Vを使用するのを助ける技術的文書のことです。説明書は通常、全てのAPC 10-40 KVA 380/400/415 Vユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

APCの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. APC 10-40 KVA 380/400/415 Vの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははAPC 10-40 KVA 380/400/415 Vの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。APC 10-40 KVA 380/400/415 Vに関してこのドキュメントで見つけることができる全てのヒントの目次
3. APC 10-40 KVA 380/400/415 Vデバイスの基本機能を使うにあたってのヒント。 APC 10-40 KVA 380/400/415 Vのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。APC 10-40 KVA 380/400/415 Vに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるAPC 10-40 KVA 380/400/415 Vのメーカー/サービスへの連絡先に関する情報。

APC 10-40 KVA 380/400/415 Vについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもAPC 10-40 KVA 380/400/415 Vの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがAPC 10-40 KVA 380/400/415 Vで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)