  • Cooper Lighting 1001 - page 1

    Lighting and Security 1 2 3 4 5 12345678 91 0 1 1 1 21 31 41 51 6 LUMINAIRE GROUPS SCROLL MUTE BUZZER POWER ON EMERGENCY MODE GENERAL FAUL T SYSTEM FAUL T TEST IN PROGRESS DISABLE ADDRESSABLE EMERGENCY LIGHTING CONTROL PANEL INST ALLA TION INSTRUCTIONS AND OPERA TING MANUAL EASICHECK™ 1001 Self Contained ...

  • Cooper Lighting 1001 - page 2

    CONTENTS Introduction Specification The SCAEL Interface W iring Powering Up Commissioning Setting Date/T ime User Menu Networking PC Software 2 EASICHECK™ ...

  • Cooper Lighting 1001 - page 3

    INDEX Page Contents 2 Index 3 1.0 Introduction 4 1.1 Specification 5 1.2 Features 6 SCAEL Interface 2.0 Programming 7 2.1 Installation 7 EasiCheck Panel 3.0 Installation 8 3.1 Installation guide 8 4.0 Loop Circuits 9 4.1 Isolators 9 4.2 Loop connection diagrams 10 5.0 Cable Requirement 1 1 5.1 Cable length - V olt drop 1 1 5.1.1 Spur circuit 1 1 5. ...

  • Cooper Lighting 1001 - page 4

    1.0 Introduction The EASICHECK™ Panel is designed to periodically test the functionality of your installed emergency . Once a week, once a month or 6 monthly , the EASICHECK™ will carry out tests to determine whether your emergency lighting is fully functional. For testing purposes, the luminaires can be designated to groups. The information fo ...

  • Cooper Lighting 1001 - page 5

    1.1 Specification " User T ext Display Address, location and fault description. " Dimensions H x W x D (mm) 270 x 332 x 90 " Maximum System Capacity 250 self contained luminaires depending on system type " W eight (Including Battery) 6 Kg " LED Indicators/LC Display LEDs are; Power On, Emergency Mode, General Fault, System ...

  • Cooper Lighting 1001 - page 6

    1.2 Features " 80 Character display showing the exact address and location of any fault identified. " 16 group capability with individual group indicators in addition to text display . " One loop giving a total of 250 address capacity . " T wo self contained 12 volt rechargeable batteries for 6 hour standby with a fully loaded l ...

  • Cooper Lighting 1001 - page 7

    2.0 Programming the EASICHECK™ SCAEL Interface. Before the SCAEL Interface is connected it must be programmed in order for the EASICHECK™ Panel to recognise it as part of the system. This is done with an EASICHECK™ hand held programming unit. The programming unit has two spring loaded connections which are to be held briefly on to the SCAEL I ...

  • Cooper Lighting 1001 - page 8

    3.0 Installation In common with all electronic equipment the panel should be installed in a clean, dry , reasonably well ventilated place, and not in direct sunlight. T emperatures in excess of 40°(C and below 5°(C may cause problems, if in doubt consult Cooper Lighting and Security Ltd. The panel should be located away from any potential hazard, ...

  • Cooper Lighting 1001 - page 9

    4.0 Loop Circuits The following recommendations apply specifically to EASICHECK™ loop circuits: " The EASICHECK™ Panel is a one loop Addressable emergency lighting test system. " The loop circuit has provision for a maximum of 250 SCAEL Interfaces. " Each SCAEL Interface has it’s own individual address which can be programmed b ...

  • Cooper Lighting 1001 - page 10

    4.2 Loop connection diagrams 10 EASICHECK™ S S S S S S S S S S I I I I I S S I I I I I I I Mixed Loops with Spurs (+ Isolators) Loop S S S S S S S S S S S S Mixed Loops with Spurs (No Isolators) Radial (+ Isolators) Loop Loop S S S S S Radial (No Isolators) Loop S S S S S I = Isolator , S = SCAEL Interface ...

  • Cooper Lighting 1001 - page 11

    5.0 Cable Requirement Cable type : T wo core or screened Recommended size : 1.0 to 2.5mm 2 (see V olt drop calculation) Maximum Resistance : 40 Ohms Maximum Capacitance : 2.0 µF / km Maximum cable length : 2 km (see V olt drop calculation) 5.1 Cable Length - V oltage drop 5.1.1 Spur Circuit. Make sure that the minimum voltage at the furthest point ...

  • Cooper Lighting 1001 - page 12

    Example 2 If the spur is wired with 1.0 mm 2 cable, using the go and return column of table 1, the Max cable length will be 33.3/36.2= 0.9 Km , for 1.5 mm 2 the Max cable length is 33.3/24.2 = 1.38 Km and finally for 2.5 mm 2 the cable length is 33.3/14.8= 2.25 Km. 5.1.2 Loop Circuit; Calculation as above but assume the loop is broken at one end. 5 ...

  • Cooper Lighting 1001 - page 13

    a) If the loop and spurs are wired with 1.0mm 2 cable and allowing for maximum permissible voltage drop with reference to table 1; Rspur = [ 10 - [ 3.62 x 250 x 0.0012 ] ] (6) 10 x 25 x 0.0012 This corresponds to a maximum spur cable length of 0.820 km Hence, the total system cable length is 8.3km compared to 0.9 km for a loop system (see example 2 ...

  • Cooper Lighting 1001 - page 14

    6.0 Mains Connection " Normal supply for the system should be derived from the public supply system. " When no public supply is available, privately generated power may be used. " The standby battery provides 3.2Ah which will maintain the system in operation for at least 6 hours upon a Mains failure. The EASICHECK™ draws a maximum ...

  • Cooper Lighting 1001 - page 15

    6.1 Battery Connection The two 12V Batteries are connected together in series. The Red wire from the EasiCheck is connected to the Red terminal of one of the Batteries, the link wire is then fitted to the Black terminal of that Battery , the other end of the link wire is fitted to the Red terminal of the other Battery , then finally the Black wire ...

  • Cooper Lighting 1001 - page 16

    7.0 System Wiring Connect all SCAEL Interfaces to the EASICHECK™ Panel by means of the TELE/LOOP connections. There are two connections (loop in & out on +). Interfaces are not polarity sensitive; 16 EASICHECK™ LN E 230 V AC Mains L OOP 26V N/O N/C C 0V TxD RxD TxD Tx- Tx+ REPEA TER CONNECTION FAU L T RELAY RS232 RS232 PRINTER 0V F+ S- F- S ...

  • Cooper Lighting 1001 - page 17

    Optional Accessories 8.0 Networking The EASICHECK™ can be fitted with an optional Network card for which there is already a reserved socket. This is a PCB that simply plugs on to the Power Supply Board and has four connections. These four connections wire to other Panels fitted with Network cards in a loop configuration (two in, two out). All Pan ...

  • Cooper Lighting 1001 - page 18

    8.1 Printer Connections. 18 EASICHECK™ Printer Connection PSU P anel connections Black wire FAU LT REL A Y RS485 RS232 RS232 PRTR N/C C N/O Tx- Tx+ 0V TxD TxD RxD 0V The Printer enables the user to printout Weekly test reports, Full Reports and the Event Log as needed. ...

  • Cooper Lighting 1001 - page 19

    9.0 Main Panel Operation There are two modes of operation; 1. Autolearn mode; System automatically searches for all SCAEL Interfaces connected to the loop. No text is available in this mode. This mode can be used for initial checking. (Note: SCAEL Interfaces must be programmed) 2. Commissioned Mode; The Panel is re-commissioned using a PC to downlo ...

  • Cooper Lighting 1001 - page 20

    9.3 Setting the T ime & Date Setting The Time; Enter the Engineer Passcode. The display will show; Press & , the display will show; Press & , % , $ or ( to adjust the current time. Upon completion, press ' to exit the menu. Setting The Date; Enter the Engineer Passcode. The display will show; Press % , the display will show; Press ...

  • Cooper Lighting 1001 - page 21

    21 9.4 T est Schedule Enter the Engineer Passcode. The display will show; Press $ , the display will show; Note: After each menu has been accessed, the passcode will have to be re-entered 9.4.1 W eekly T est; Press & , the display will show; Press & , % , $ or ( to adjust the test day and time. Once the time has been corrected, press ' ...

  • Cooper Lighting 1001 - page 22

    22 9.5 User Menu Options Enable/Disable (Fittings); Enter the User Passcode. The display shows; Press & , the display shows; Press & or % , the display shows; Press % and $ to select the required fitting then press & to enable/disable it. The display shows; Repeat pressing % and $ if further fittings require enabling/disabling. Press &a ...

  • Cooper Lighting 1001 - page 23

    23 User Menu Options continued... 9.5.2 Reset the Panel; Enter the User Passcode. The display will show; Press % , the display shows; All LEDs light up in turn and then switch off. The Panel returns to normal. 9.5.3 Print Options; Enter the User Passcode. The display will show; Press $ the display shows; Press $ the display shows; Ensure that the p ...

  • Cooper Lighting 1001 - page 24

    User Menu Options continued... 9.5.4 Discharge T est; Enter the User Passcode. The display will show; Press ( , the display shows; Press & , the display shows; Press & , % or $ , the display shows; If & is selected, the panel returns to normal display and starts test. If % is selected, the display shows; Press % or $ to select the requi ...

  • Cooper Lighting 1001 - page 25

    User Menu Options continued... 9.5.5 LED T est (on the fitting) Enter the User Passcode. The display will show; Press $ , the display shows; Press % , the display shows; Press & or % the LED changes colour . Press ' to return to normal. 9.5.6 V(V oltage) / I(Current) Display; Enter the User Passcode. The display will show; Press $ , the di ...

  • Cooper Lighting 1001 - page 26

    9.6 User menu flowchart EASICHECK™ Control Panel User Menu Structure Self-Contained 26 EASICHECK™ 1 ENABLE 2 HUNDREDS 3 TENS 4 UNITS 5 QUIT 1 SELECT 2 HUNDREDS 3 TENS 4 UNITS 5 QUIT 1 FIT ST A TUS 2 WEEKL Y TEST 3 FULL DIS 4 EVENT 5 QUIT 1 TEST 2 HUNDREDS 3 TENS 4 UNITS 5 QUIT 1 DISABLE 2 HUNDREDS 3 TENS 4 UNITS 5 QUIT 1 ENABLE 2 DISABLE 3 DISA ...

  • Cooper Lighting 1001 - page 27

    10.0 Up/Downloading using PC Software (Commissioning Engineer Operation) The PC software enables the address, location text, luminaire type and any comments to be downloaded to the EASICHECK™ Panel. Each luminaire can be assigned to a group for testing purposes. The software can download to all 64 networkable Panels. The PC is connected to each P ...

  • Cooper Lighting 1001 - page 28

    28 Site Configuration. Address Group T ype Area/Location Comment 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 ...

  • Cooper Lighting 1001 - page 29

    Site Configuration continued. 29 EASICHECK™ Address Group T ype Area/Location Comment 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 ...

  • Cooper Lighting 1001 - page 30

    30 Site Configuration continued. Address Group T ype Area/Location Comment 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 11 0 111 11 2 11 3 11 4 11 5 11 6 11 7 11 8 11 9 120 ...

  • Cooper Lighting 1001 - page 31

    Site Configuration continued. 31 EASICHECK™ Address Group T ype Area/Location Comment 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 ...

  • Cooper Lighting 1001 - page 32

    Site Configuration continued. 32 EASICHECK™ Address Group T ype Area/Location Comment 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 ...

  • Cooper Lighting 1001 - page 33

    Site Configuration continued. 33 EASICHECK™ Address Group T ype Area/Location Comment 201 202 203 204 205 206 207 208 209 210 21 1 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 ...

  • Cooper Lighting 1001 - page 34

    Site Configuration continued. 12.0 Group T esting 13.0 W eekly T est 34 EASICHECK™ Address Group T ype Area/Location Comment 241 242 243 244 245 246 247 248 249 250 Group T ime Day Month 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 T ime Day Of Week ...

  • Cooper Lighting 1001 - page 35

    4.0 EasiCheck Commissioning Request Form Project Title: ________________________________________ Prior to the commissioning being undertaken, it is necessary that the contractor completes the following information so as to aid system commissioning. With reference to the above project we confirm; Dedicated Mains Supply Installed Y es / No All Fittin ...

  • Cooper Lighting 1001 - page 36

    Lighting and Security www .cooper-ls.com Cooper Lighting and Security Ltd. Wheatley Hall Road, Doncaster , South Y orkshire, DN2 4NB, United Kingdom Sales General Export T el: +44 (0)1302 - 303222 +44 (0)1302 - 321541 +44 (0)1302 - 303250 Fax: +44 (0)1302 - 367155 +44 (0)1302 - 303220 +44 (0)1302 - 303251 Email: sales@cooper-ls.com technical@cooper ...

メーカー Cooper Lighting カテゴリー Landscape Lighting

Cooper Lighting 1001のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 1001の取扱説明書
- Cooper Lightingの製品カード
- パンフレット
- またはCooper Lighting 1001の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Cooper Lighting 1001の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Cooper Lighting 1001の取り付け説明書、サービスマニュアル、簡易説明書、またはCooper Lighting 1001のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Cooper Lighting 1001の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Cooper Lighting 1001デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがCooper Lighting 1001を使用するのを助ける技術的文書のことです。説明書は通常、全てのCooper Lighting 1001ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Cooper Lightingの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Cooper Lighting 1001の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははCooper Lighting 1001の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Cooper Lighting 1001に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Cooper Lighting 1001デバイスの基本機能を使うにあたってのヒント。 Cooper Lighting 1001のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Cooper Lighting 1001に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるCooper Lighting 1001のメーカー/サービスへの連絡先に関する情報。

Cooper Lighting 1001についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもCooper Lighting 1001の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがCooper Lighting 1001で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)