    Control Panel D9412GV4/D7412GV4 v2.00 en UL Installation Instructions ...

  • Bosch Appliances D9412GV4 - page 2

    ...

  • Bosch Appliances D9412GV4 - page 3

    Table of contents 1 Introduction 4 1.1 About documentation 4 1.2 Determine Bosch Security Systems, Inc. Product Manufacturing Dates 4 2 Installation 5 2.1 Installation Preparation 5 2.2 Enclosure Options 5 2.3 Mounting Enclosure 5 2.4 Installing the Control Panel 6 2.5 Connecting Earth Ground 7 2.5.1 Terminal 10 7 2.5.2 Ground Fault Detect Enable 7 ...

  • Bosch Appliances D9412GV4 - page 4

    Introduction About documentation Copyright This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved. Trademarks All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly. Determine Bosch Security Systems, I ...

  • Bosch Appliances D9412GV4 - page 5

    Installation Installation Preparation This section contains a general installation procedure and refers to other sections of the document for detailed instructions. Review this document and the D9412GV4/D7412GV4 Program Entry Guide (P/N: F01U265459) before beginning the installation to determine the hardware and wiring requirements for the features ...

  • Bosch Appliances D9412GV4 - page 6

    i Notice! Electromagnetic interference (EMI) can cause problems on long wire runs. Figure 2.1: Enclosure Mounting Callout - Description 1 - Point chart label 2 - Mounting skirt hooks (2) 3 - Module mounting holes (12) 4 - Tamper switch mounting holes (5) 5 - Skirt mounting hole (1) 6 - Enclosure mounting holes (5) 7 - Mounting skirt hook holes (2) ...

  • Bosch Appliances D9412GV4 - page 7

    Connecting Earth Ground Terminal 10 To help prevent damage from electrostatic charges or other transient electrical surges, connect the system to earth ground at Terminal 10 before making other connections. Recommended earth ground references are a grounding rod or a cold water pipe. ! Warning! Do not use telephone or electrical ground for the eart ...

  • Bosch Appliances D9412GV4 - page 8

    Figure 2.2: Ground Fault Detect (S4) Callout - Description 1 - S4 Locked (Closed). Control panels detects ground faults. 2 - S4 Unlocked (Open). Control panel does not detect ground faults. Ground Fault Impedance Specifications The table below provides the impedance specifications for detecting ground faults when any terminal or field wiring is sho ...

  • Bosch Appliances D9412GV4 - page 9

    Figure 2.3: Reset Pin Callout - Description 1 - Reset pin locked (closed) 2 - Reset pin normal (open) Control Panel Installation | en 9 Bosch Security Systens, Inc. UL Installation Instructions 2012.12 | 02 | F.01U.265.462 ...

  • Bosch Appliances D9412GV4 - page 10

    Diagrams Faceplates Figure 3.1: Faceplates Callout - Description Callout - Description 1 - Charging status LED (yellow) 8 - Ring 2 - Low battery LED (red) 9 - Operation monitor LED (green) 3 - Color-coded battery leads 10 - Accessory connector 4 - Ground fault detect enable 11 - Reset pin 5 - Phone LED (red) 12 - SDI interconnect wiring connector 6 ...

  • Bosch Appliances D9412GV4 - page 11

    Power Supply Side Wiring Diagrams D9412GV4/D7412GV4 Power Supply Side System Wiring Diagram (Power and Phone) Figure 3.2: Side System Wiring Diagram Callout - Description Callout - Description 1 - If required by local AHJ, connect D113 Battery Lead Supervision Module. 8 - To Output A or Output B 2 - Batteries 9 - Listed Audible Signaling Devices ra ...

  • Bosch Appliances D9412GV4 - page 12

    i Notice! For UL Certified accounts, additional power can be obtained using only a UL Listed auxiliary 12.0 VDC regulated, power-limited power supply. i Notice! All terminals accept for Outputs A, B, and C (Terminals 6, 7 and 8) are supervised. D9412GV4/D7412GV4 Input Points and Peripheral Devices System Wiring Diagram Figure 3.3: Input Points and ...

  • Bosch Appliances D9412GV4 - page 13

    i Notice! For D129, use zero retard except for waterflow devices. All external connections except Terminal 5 (battery positive) are power limited. Control Panel Diagrams | en 13 Bosch Security Systens, Inc. UL Installation Instructions 2012.12 | 02 | F.01U.265.462 ...

  • Bosch Appliances D9412GV4 - page 14

    SDI Devices Wiring Diagrams D9412GV4 SDI and Zonex Devices System Wiring Diagram Figure 3.4: D9412GV4 System Wiring Diagram, SDI and Zonex Devices Callout ᅳ Description Callout ᅳ Description 1 ᅳ Up to 16 supervised D1265, D1255 (all versions), D1255RB, D1256RB Keypads, or D1257RB Fire Annunciators, or up to 8 supervised D1260 Keypads (all ver ...

  • Bosch Appliances D9412GV4 - page 15

    i Notice! Terminals 24 through 36 are power limited, supervised. Fire and Intrusion devices must be on separate circuits. Refer to ICP-SDI-9114 Installation Instructions (P/N: F01U030068) D7412GV4 SDI and Zonex Devices System Wiring Diagram Figure 3.5: D7412GV4 SDI and Zonex Devices System Wiring Diagram Callout - Description 1 - Up to 16 supervise ...

  • Bosch Appliances D9412GV4 - page 16

    i Notice! Terminals 24 through 36 are power limited, supervised. Fire and Intrusion devices must be on separate circuits. Refer to ICP-SDI-9114 Installation In- structions (P/N: F01U030068). D9412GV4/D7412GV4 SDI2 Devices System Wiring Figure 3.6: SDI2 Devices System Wiring Diagram Callout - Description 1 - B208 Octo-input Modules 1 2 - B308 Octo-o ...

  • Bosch Appliances D9412GV4 - page 17

    Module D9412GV4 D7412GV4 4 BB810/B820 SDI2 Inovonics Interface Modules 1 1 B920 Two-line Alphanumeric Keypad 5 16 16 B930 ATM Style Alphanumeric Keypad (SDI2) 5 16 16 B520 Auxiliary Power Supply Module 8 8 1 For the D7412GV4, only 5 inputs are available on the Octo-input at address 7. 2 For the D7412GV4, only 4 outputs are available on the Octo-out ...

  • Bosch Appliances D9412GV4 - page 18

    SDI2 Bus Wiring Recommendations Use the following SDI2 bus wiring recommendations for SDI2 installation. The SDI2 bus is used by the GV4 Control Panel and corresponding modules to communicate with one another. Modules can be connected via home run, daisy chain, or single level T-tapped anywhere on the SDI2 bus. Please reference Figure 2.7 below. Fi ...

  • Bosch Appliances D9412GV4 - page 19

    Cable capacitance Overall cable length Cable capacitance Overall cable length Cable capacitance Overall cable length Cable capacitance Overall cable length pF/ft ft pF/ft ft pF/ft ft pFf/ft ft < 17 7500 22 6363 27 5185 32 4400 18 7500 23 6086 28 5000 33 4242 19 7350 24 5800 29 4828 34 4100 20 7000 25 5600 30 4700 35 4000 21 6666 26 5385 31 4516 ...

  • Bosch Appliances D9412GV4 - page 20

    Power Supply and Power Outputs Power Supply - Primary Primary (AC) Power Circuit The primary source is a 16.5 VAC, 40 VA, internally-fused transformer (Bosch Security Systems, Inc. Model D1640). The control panel draws 225 mA when idle and 300 mA when in an alarm state. The total available auxiliary current is 1.4 A. Transient suppressors and spark ...

  • Bosch Appliances D9412GV4 - page 21

    D8004 Transformer Enclosure Required for Fire Systems Use the D8004 Transformer Enclosure for the D1640 Transformer in fire and combined fire and burglary applications. i Notice! Check with the Authority Having Jurisdiction (AHJ) about mounting transformers on specific circuits. Power Terminals - Secondary Secondary (DC) Power A 12 V, 7 Ah (up to 1 ...

  • Bosch Appliances D9412GV4 - page 22

    ! Warning! High current arcs are possible. The positive (red) battery lead and Terminal 5 can create high current arcs if shorted to other terminals or the enclosure. Use caution when working with the positive lead and Terminal 5. Always disconnect the positive (red) lead from the battery before removing it from Terminal 5. ! Warning! The battery t ...

  • Bosch Appliances D9412GV4 - page 23

    Figure 4.2: Non-PowerLimited Wiring Callout ᅳ Description 1 ᅳ Conduit required for use with external batteries. 2 ᅳ Battery wires 3 ᅳ 0.25 in (6.4 mm) minimum. To ensure proper spacing, use tie-wraps or similar devices to secure wires. 4 ᅳ Relay output wires 5 ᅳ Input or Zone wires 6 ᅳ Standby battery Power Outputs - Circuit Protectio ...

  • Bosch Appliances D9412GV4 - page 24

    – Terminal 8: Output C (Switched Auxiliary Power) PTC CB5 protects Terminal 24: Zonex Power. PTC CB1 protects Terminal 32: SDI Power +. PTC CB3 protects Terminal 36: SDI2 Power +. Required by UL: – All devices powered from a power output are to be supervised. – Power outputs are not shared between fire and non-fire devices unless all devices ...

  • Bosch Appliances D9412GV4 - page 25

    F01U265459) contains complete instructions for programming outputs. Refer to Terminals 6 and 7, page 25 , Fire System Power Formula, page 25 , and Terminal 8, page 26 for descriptions of the functions of each terminal. Refer to the Bell Parameters section of the program to set the Fire Bell, Alarm Bell, and Gas Bell output responses for outputs. Fo ...

  • Bosch Appliances D9412GV4 - page 26

    Terminal 8 Terminal 8 provides continuous positive (+) 12.0 VDC Nominal power. Output C interrupts the power at Terminal 8 when activated. Use Terminal 8 to power smoke detectors or other devices that are reset by interrupting power. One self-resetting circuit breaker protects Terminals 6, 7, and 8 against shorts. Verification/Reset Output The defa ...

  • Bosch Appliances D9412GV4 - page 27

    Specifications Voltage Input (Power Supply) 1 Primary: Terminals 1 and 2 16.5 VAC 40 VA class 2 plug-in transformer (D1640) Secondary: Terminals 4 and 5 Sealed lead-acid rechargeable battery (12.0 VDC, 7 Ah or 12.0 VDC, 17.2 or 18 Ah). The control panel supports up to two 12.0 VDC, 7 Ah batteries using the D122/ D122L Dual Battery Harness or two D1 ...

  • Bosch Appliances D9412GV4 - page 28

    SDI Bus B-: 9 VDC 15000 (4572 m) maximum SDI2 Bus SDI2 Bus A+; 12 VDC nominal 7500 ft (2286 m) maximum 3 SDI2 Bus B-: 12 VDC nominal (7500 ft) (2286 m) maximum 3 Telephone Connections Connection: RJ31X or RJ38X jack can connect the control panels. Two telco lines: Bosch Security Systems, Inc. D928 Dual Phone Line Module required for two phone line ...

  • Bosch Appliances D9412GV4 - page 29

    B520 Specifications Voltage Input (Power Supply) Primary: 18 VAC terminal 18.0 VAC, 50 VA class 2 plug-in transformer -TR1850 (18.0 VAC, 50 VA class 2 plug-in transformer – TR1850-CA for Canada) Secondary: Batt 1, Batt 2 terminals The B520 Auxiliary Power Supply Module supports the connection of two independantly monitored sealed lead-acid rechar ...

  • Bosch Appliances D9412GV4 - page 30

    Recharge Cycle AC ON – Load shed relay resets, battery charging begins, Battery Trouble and AC Restoral Reports sent. 12.6 VDC – Battery Restoral Report sent, Low Battery LED off. Environmental Temperature: +32 ゚ F to +120 ゚ F (0 ゚ C to +49 ゚ C) Relative Humidity: Maximum 93% non-condensing Compatible Enclosures D8103 Universal Enclosur ...

  • Bosch Appliances D9412GV4 - page 31

    Terminal No Terminal Description Requirements 16 POINT 4 Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop resistance less than 100 Ω. 17 POINT 5 Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop resistance less than 100 Ω. 18 POINT 5/6 COMMON Terminal accommodates 14 to 22 AWG, use appropriate ...

  • Bosch Appliances D9412GV4 - page 32

    Terminal No Terminal Description Requirements 36 SDI2 POWER Terminal accommodates 14 to 22 AWG, use appropriate wire size based on peripheral device current. *D9412GV4 only. Terminals 25 and 26 are NOT USED on the D7412GV4 Control Panel. Compatibilities i Notice! Where the fire alarm transmitter is sharing on-premise communications equipment, the s ...

  • Bosch Appliances D9412GV4 - page 33

    Model Title UL 864 UL 985 Intrusion cUL Intrusion D1218 12 V, 17.2 Ah Rechargeable Battery D1255/D1255B Keypads (General Purpose) X X X D1255W Text Keypad (white) X X X D1260/ D1260B 2 Keypads X X X D1640 16.5 VAC 40 VA Transformer X X X D1640-CA 16.4 VAC 40 VA Transformer for Canada X D8004 Transformer Enclosure X X X D8125 POPEX Module X X X X D8 ...

  • Bosch Appliances D9412GV4 - page 34

    Model Title UL 864 UL 985 Intrusion cUL Intrusion 3 RFRP-A RADION repeater X X 3 RFPR-12-A RADION PIR X 3 RFPR-C12_A RADION PIR C X 3 RFUN RADION universal transmitter X 1 Where the fire alarm transmitter is sharing on-premise communications equipment, the shared equipment must be UL Listed (ITE or fire potective signaling). 2 Version 1.04 or above ...

  • Bosch Appliances D9412GV4 - page 35

    ...

  • Bosch Appliances D9412GV4 - page 36

    Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, NY 14450 USA www.boschsecurity.com © Bosch Security Systems, Inc., 2012 ...

メーカー Bosch Appliances カテゴリー Video Gaming Accessories

Bosch Appliances D9412GV4のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- D9412GV4の取扱説明書
- Bosch Appliancesの製品カード
- パンフレット
- またはBosch Appliances D9412GV4の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Bosch Appliances D9412GV4の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Bosch Appliances D9412GV4の取り付け説明書、サービスマニュアル、簡易説明書、またはBosch Appliances D9412GV4のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Bosch Appliances D9412GV4の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Bosch Appliances D9412GV4デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがBosch Appliances D9412GV4を使用するのを助ける技術的文書のことです。説明書は通常、全てのBosch Appliances D9412GV4ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Bosch Appliancesの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Bosch Appliances D9412GV4の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははBosch Appliances D9412GV4の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Bosch Appliances D9412GV4に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Bosch Appliances D9412GV4デバイスの基本機能を使うにあたってのヒント。 Bosch Appliances D9412GV4のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Bosch Appliances D9412GV4に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるBosch Appliances D9412GV4のメーカー/サービスへの連絡先に関する情報。

Bosch Appliances D9412GV4についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもBosch Appliances D9412GV4の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがBosch Appliances D9412GV4で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)