    Copyright 2010 Carrier Cor poration Form 23XR V -3PD Carrier’ s Ev ergreen ® 23XR V chiller is the world’ s first integ rated v ariable speed, water-cooled, screw chiller . It incorp or ates significant break- throughs in water-cooled chiller tech- nology to provide e xcellent reliability and achie v e superior efficiencies at true operating c ...

  • Carrier 23XRV - page 2

    2 V ariable speed capacity control elimi- nates slide valves, their associated loss- es, and their potential failure modes. Component count (both rotating and total) has been minimized assuring maximum relia bility under a wide range of operating conditions. High efficiency Per AHRI 550/590, chillers operate at design conditions less than one perce ...

  • Carrier 23XRV - page 3

    3 • Machine room cooling re quirements associated with air-cooled motors, which dissipate heat to the mechan- ical room. • High noise levels common with air- cooled motors, which radiate noise to the machine room and adjacent areas. • Shaft alignment problems that occur with open-drive designs during start- up and opera tion, when equipmen t ...

  • Carrier 23XRV - page 4

    4 feature also allows the machine to operate at reduced capacity, rather than shut down, when key safety limits are approached. Chilled liquid rese t — Reset can be accomplished manually or automatical- ly from the building management sys- tem. For a given capacity, reset allows operation at slower compresso r speeds, saving ener gy when war mer ...

  • Carrier 23XRV - page 5

    5 23XRV COMPRESSOR AND MOTOR WEIGHTS COMPONENT WEIGHTS LEGEND 23XR V HEA T EXCHANGER WEIGHTS COND — Condenser *Rigging weigh ts are for standard tube s of standard wall thickness (EDE and S pikefin 3, 0.025- in. [0.635 mm] wall). NO TE S : 1. Cooler incl udes the suction elbo w and 1 / 2 the distri b ut ion piping weight. 2. Condens er includes f ...

  • Carrier 23XRV - page 6

    6 ADDITIONAL WEIGHTS FOR 23XR V MARINE W A TERBOXES* 150 psig (1034 kPa) MARINE W A TERB OXES 300 psig (2068 kPa) MARINE W A TERB OXES *Add to cooler and condenser weights f or tota l weights. Cooler and condenser weights may be f ound in the 23XR V Heat Exchanger Weights tab le on page 5. The first dig it of the heat e xch anger code (first column ...

  • Carrier 23XRV - page 7

    7 *F actor y-installed. †Field-installed. ** S tandard waterbox nozzles are vi ctaulic type. Flanged nozzles are av ailable as an option with either nozzle-in-head type waterbo xes or marine waterbox es. ††Optional marine waterbox es av ailable for 23XR V heat exchanger frames 3-5 only . S tandard waterbo xes f or 23XR V are nozzle-in-head ty ...

  • Carrier 23XRV - page 8

    8 23XRV DIMENSIONS (NOZZLE-IN-HEAD W A TERBOX) 23XRV DIMENSIONS (MARINE W A TERBOX) *Assumes both cooler and condenser nozzles on same end of chiller . †1 or 3 pass length applies if c ooler is a 1 or 3 pa ss design. NO TE S : 1. S ervice access should be provided per America n S ociety of Heat- ing, Refrigerating, and Air Conditioning Engineers ...

  • Carrier 23XRV - page 9

    9 NOZZLE SIZE 23XR V HEA T EXCHANGER MIN/MAX FLOW RA TES* ENGLISH (GPM) *Flow rates based on standard tubes in the c ooler and condenser . Minimum flow based on tube velocity of 3 ft/sec (0.91 m/sec); maximum flow based on tube v elocity of 12 ft/sec (3.66 m/ sec). Consult the factory if variable primar y flow . SI (L/s) *Flow rates based on standa ...

  • Carrier 23XRV - page 10

    10 VFD FRAME SIZES *Maximum limits only . Additi onal applicatio n limits apply that will reduce these ampacities. AUXILIAR Y RA TINGS* *F actor y wired to VFD . †Minimum circuit ampacity of 15 amps. FRAME SIZE MAX INPUT CURRENT * MAX OUTPUT CUR RENT * AA 440 442 BA 520 442 BB 520 520 CC 60 8 60 8 ITEM V OL T A GE MAXIMUM PRO TECTIVE DEVICE SIZE ...

  • Carrier 23XRV - page 11

    11 Micropr ocessor contr ols Microprocessor controls provide the safety, interlock, ca- pacity control, indications and accessibility necessary to operate the chiller in a safe and efficient manne r . Control system The microprocessor control on each Carrier chiller is factory-mounted, factory-wired, and factory-tested to ensure machine protection ...

  • Carrier 23XRV - page 12

    12 Contr ols (cont) CONTROL P ANEL DISPLA Y (Front View) ICVC ENGLISH DI SPLA Y IN SI UNITS CONTROL P ANEL DISPLA Y (Front View) ICVC CHINESE D ISPLA Y IN METRIC UNIT S ...

  • Carrier 23XRV - page 13

    13 BLACK WHITE RED BLACK WHITE RED DRAIN WIRE DRAIN WIRE BLACK WHITE RED BLACK WHITE RED DRAIN WIRE GROUND DRAIN WIRE NO TE: Field-supplied ter minal strip must be located in control panel. LEGEND CCM — Chiller Control Module F actor y Wiring Field Wiring CCN COMMUNICA TION WIRING FOR M UL TIPLE CHILLERS (TYPICAL) a23-1649 ...

  • Carrier 23XRV - page 14

    14 Contro l sequence To s t a r t — Loca l start-up (man ual st art-up) is initiated by pressing the LOCAL or CCN menu softkey, which is indi- cated on the default inter nati onal chiller vis ual control (ICVC) screen. Time schedule 01 or 03, respectively, must be in the Occupied mode and the inter nal 15-minute start- to-start and the 1-minute s ...

  • Carrier 23XRV - page 15

    15 T ypical piping and wiring 1 1 1 6 7 8 TO CHILLED LIQUID PUMP TO CONDEN S ER LIQUID PUMP TO COOLING T OWER FAN 2 1 MAIN COMPRE SS OR MOTOR POWER FROM COOLING TOWER FROM LOAD TO COOLING TOWER TO LOAD 3 3 9 9 DRAIN 5 4 LEGEND 1— Disconnect 2— Unit-Mounted VFD/Control Center 3— Pressure Gages 4— Chilled Liquid Pump 5— Condenser Liquid Pum ...

  • Carrier 23XRV - page 16

    16 Contr ol wiring schematic 23XRV CO MPONENT ARRANGEMENT LEGEND CCM — Chiller Control Module CCN — Carrier Comfor t Network® ICVC — Internationa l Chiller Visual Controller GND — Gro und ...

  • Carrier 23XRV - page 17

    17 Application data F E Y Y * B G A VESSELS TYP . 0 ’ - 3 ” [76.2mm] ACCESSOR Y SOLEPLA TE 0 ’ -01/2” [1 3 mm] TYP . X X * VESSELS COND . COOLER C L C L C L C D  23XRV MACHINE FOOTPRINT * S ee detail on page 1 8 . 23XR V HEA T EXCHANGER SIZE DIMENSIONS (ft-in.) DIMENSIONS (mm) A BCDE F G A B C D E F G 30-32 12-10 3 / 4 5-4 1 / 4 0 0-3 ...

  • Carrier 23XRV - page 18

    18 Application data (cont) ELASTOMERIC P AD 23XRV ISOLA TION WITH ACCESSOR Y SOLEPLA TE P ACKAGE TYPICAL ISOLA T ION ST ANDARD ISOLA TION ACCESSORY SOLEPLA TE DET AIL VIEW X-X NO TE S : 1. Dimensions in ( ) are in millimeters. 2. Accessor y soleplate package includes 4 so leplates, 16 jacking scre ws and leveling pads. Requires isolation pac kage. ...

  • Carrier 23XRV - page 19

    19 12 11 10 9 8 7 6 5 4 3 2 1 23XRV NOZZLE ARRANGEMENTS NOZZLE-IN -HEAD W A TERBOXES FRAME 3 FRAMES 4 AND 5 NOZZLE ARRANGEMENT CODES FOR ALL 23XRV NOZZLE-I N-HEAD W A TERBOXES *Refer to certified drawings . PA S S COOLER W A TERBO XES In Out Arrangement Code * 1 8 5A 5 8 B 2 79 C 46 D 3 76 E 49 F PA S S CONDENSER W A TERBO XES In Out Arrangement Co ...

  • Carrier 23XRV - page 20

    20 Application data (cont) 23XR V NOZZLE ARRANGEMENTS (cont) MARINE W A TERBOXES FRAME 3 NOZZLE ARRANGEMENT CODES PA S S COOLER W A TERBO XES PA S S CONDENSER W A TERBOXES In Out Arrangement Code In Out Arrangement Code 1 8 5A 1 —— — 5 8 B— — — 2 79 C 2 10 12 R 46 D 1 3 S 3 76 E 3 —— — 49 F — — — FRAMES 4, AND 5 NOZZLE ARRAN ...

  • Carrier 23XRV - page 21

    21 23XRV W A TERBOX NOZZLE SIZES (Nozzle-In-Head and Marine W aterboxes RELIEF V AL VE LOCA TIONS * Coolers without optional isolat ion require 2 relief valves . NO TE: All valv es reliev e at 1 8 5 psig (1275 kPa). FRAME SIZE PRESSURE psig (kPa) PA S S NOMINAL PIPE SIZE (in.) A C TU AL PIPE ID (in.) Cooler Condenser Cooler Condenser 3 150/300 (103 ...

  • Carrier 23XRV - page 22

    22 V ent and drain connections Nozzle-in-head waterboxes have vent and drain connec- tions on covers. Marine waterboxes have vent and drain connections on waterbox shells. Provide high points of the chille r piping system with vents and the low points with drains. If shutoff valves are provid- ed in the main liquid pipes near the unit, a min imal a ...

  • Carrier 23XRV - page 23

    23 Insulation 23XR V MINIMUM FIELD-INST ALLED INSULA TION REQUIREMENTS Factory insulation — Ther mal insulation is factory- provided to the following areas: • Cooler (not including waterbox) • Suction line • Compressor and motor • Oil cooling line and oil retur n system line (oil and refrig- erant lines at or near evapo rator pressure are ...

  • Carrier 23XRV - page 24

    24 V ariable Speed Scre w Chiller HV AC Guide Specifications Size Range: 300 to 550 T ons (1055 to 1934 kW) Nominal Carrier Model Number: 23XR V Part 1 — General 1.01 SYSTEM DESCRIPTION A. Microprocessor -controlled l iquid chiller shall use a semi-her metic screw compressor using refrigerant HFC-134a only. Chiller refrigerant shall not have a pl ...

  • Carrier 23XRV - page 25

    25 D. Unit sh all be shipped with fir mly attached labels that indicate name of manufacturer , chiller model num- ber , chiller serial numb er , and refrigerant used. E. If the unit is to be exported, the manufacturer shall provide sufficient protection against sea water corro- sion, making the unit suitable for shipment in a standard open top ocea ...

  • Carrier 23XRV - page 26

    26 equipment to dissipate the motor heat as per the following for mula: Btuh = (FLkW motor) (0.05) (3413) Btuh = (FLkW motor) (171) and, alter nately T ons = Btuh/12,000 The additional piping, va lves, air -handling equipment, insulation, wiring, switchgear changes, ductwork, and coo rdination with other trades shall be the responsibility of the me ...

  • Carrier 23XRV - page 27

    27 input ter minals as the point of common cou- pling (PCC). b. The VFD full load effici ency shall meet or exceed 97% at 100% VFD rated ampacity. c. Active rectifier shall regulate unity displace- ment power factor to 0.99 or higher . d. V oltage boost capability to provide full mo tor voltage at reduced line voltage conditions. e. The VFD shall f ...

  • Carrier 23XRV - page 28

    28 liquid refrigerant to a reduced temperature, thereby increasing the refrigeration cycle efficiency. F . Refrigerant Flow Control: T o improve part load efficiency, liquid refrigerant shall be metered from the condenser to the cooler using a float-type metering valve to maintain the proper liquid level of refrigerant in the heat exchangers under ...

  • Carrier 23XRV - page 29

    29 displayed infor ming the operator that the chiller is operating in ramp loading mode. l. Chilled Water Reset: The control center shall allow re set of the chilled water temperature set point based on any one of the following criteria: 1) Chilled water reset base d on an exter nal 4 to 20 mA signal. 2) Chilled water reset based on a remote temper ...

  • Carrier 23XRV - page 30

    30 manual rotation of the lead chiller and a stag- gered restart of the chillers after a power fail- ure. The lead/lag system shall include load balancing if configured to do so. H. Electrical Requirements: 1. Electrical contractor shall supply and in stall main electrical power line, disconnect switches, circuit breakers, and electrical protection ...

  • Carrier 23XRV - page 31

    31 11. Cooler and Condenser T ubes: Contact a local Carrier Representa tive for other tube offerings. 12. Cooler and Condenser Passes: Unit manufacturer shall provide the cooler a nd/ or condenser with 1, 2 or 3 pass co nfiguration on the water side. 13. Nozzle-In-Head, 300 psig (2068 kPa): Unit manufacturer shall fur nish nozzle-in-head style wate ...

  • Carrier 23XRV - page 32

    Manufacturer reserves the right to dis continue, or change at any time, specifications or designs without notice and without inc urring obligations. Pg 32 Catalog No . 04-52230002-01 Printed in U . S .A. Form 23XRV -3PD Replaces: 23XR V -2PD S ection 9 Ta b 9 a Carrier Cor poration • S yracuse, New Y or k 13221 910 5-10 ...

メーカー Carrier カテゴリー Water Dispenser

Carrier 23XRVのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 23XRVの取扱説明書
- Carrierの製品カード
- パンフレット
- またはCarrier 23XRVの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Carrier 23XRVの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Carrier 23XRVの取り付け説明書、サービスマニュアル、簡易説明書、またはCarrier 23XRVのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Carrier 23XRVの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Carrier 23XRVデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがCarrier 23XRVを使用するのを助ける技術的文書のことです。説明書は通常、全てのCarrier 23XRVユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Carrierの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Carrier 23XRVの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははCarrier 23XRVの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Carrier 23XRVに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Carrier 23XRVデバイスの基本機能を使うにあたってのヒント。 Carrier 23XRVのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Carrier 23XRVに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるCarrier 23XRVのメーカー/サービスへの連絡先に関する情報。

Carrier 23XRVについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもCarrier 23XRVの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがCarrier 23XRVで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)