    FORM 201.24-EG1 (701) YCWS W A TER COOLED LIQUID CHILLER 91 TONS THROUGH 216 TONS 320 kW THROUGH 760 kW 60Hz STYLE A ...

  • York STYLE A YCWS - page 2

    2 YORK INTERNATIONAL Nomenclature YC W S 0140 S C 46 Y A YC= Y ork Chiller W= W ater cooled S= Screw Compressor Nominal Capacity in T ons Refrigerant C = R-22 V oltage Code: T ype Start: Y = Star-Delta Design Series: A S= Standard Efficiency 17 = 200-3-60 28 = 230-3-60 40 = 380-3-60 46 = 460-3-60 58 = 575-3-60 T able of Contents Introduction ...... ...

  • York STYLE A YCWS - page 3

    FORM 201.24-EG1 3 YORK INTERNATIONAL YORK YCWS Water-Cooled models provide chilled water for all air conditioning applications that use central station air handling or terminal units. They are completely self-contained and are designed for indoor (new or retrofit) installation. Each unit includes accessible semi-hermetic screw compressors, a liquid ...

  • York STYLE A YCWS - page 4

    4 YORK INTERNATIONAL GENERAL The Liquid Chiller will be completely assembled with all interconnecting refrigerant piping and internal wiring, ready for field installation. The unit will be pressure-tested, evacuated, and charged with Refrigerant-22, and York ‘L’ (POE) synthetic oil. There will be an operational test, with water flowing through ...

  • York STYLE A YCWS - page 5

    FORM 201.24-EG1 5 YORK INTERNATIONAL The Power and Control Panel shall be divided into a power section for each electrical system, a common input sec- tion and a control section. Each power panel shall contain: Compressor starting contactors, control circuit serving compressor capacity control, compressor contactor coils and compressor motor overlo ...

  • York STYLE A YCWS - page 6

    6 YORK INTERNATIONAL override for servicing. Print - Operating data or system fault shutdown history for last six faults. Printouts through an RS-232 port via a separate printer (by others). Program - • Low leaving liquid temperature cutout, 300 to 600 second anti-recycle timer, lag compressor start time delay, and average motor current unload po ...

  • York STYLE A YCWS - page 7

    FORM 201.24-EG1 7 YORK INTERNATIONAL AL TERNA TIVE REFRIGERANTS - Contact your nearest YORK of- fice for information and availability on alternative HFC refrigerants. ELECTRICAL OPTIONS: MUL TIPLE POINT POWER SUPPL Y CONNECTION - Standard field power wiring connection on all models is Multiple Point Power Connection to factory provided T erminal Bl ...

  • York STYLE A YCWS - page 8

    8 YORK INTERNATIONAL Design Parameters Min. Cooler Water Flow - l/sec 12.6 12.6 12.6 16.4 16.4 18.9 18.9 Max. Cooler Water Flow - l/sec 31.9 31.9 31.9 43.8 43.8 52.4 52.4 Min. Cond. Water Flow - l/sec 12.2 12.2 12.2 20.8 20.8 20.8 20.8 Max. Cond. Water Flow - l/sec 40.7 40.7 40.7 66.2 66.2 66.2 66.2 Min. Lvg. Liquid T emp. - °C 4.4 4.4 4.4 4.4 4.4 ...

  • York STYLE A YCWS - page 9

    FORM 201.24-EG1 9 YORK INTERNATIONAL Low-pressure liquid refrigerant enters the cooler tubes and is evaporated and superheated by the heat energy absorbed from the chilled liquid passing through the cooler shell. Low-pressure vapor enters the compressor where pressure and superheat are increased. High-pressure vapor is passed through the oil separa ...

  • York STYLE A YCWS - page 10

    10 YORK INTERNATIONAL 1 10 100 100 1000 10000 1 10 100 100 1000 Pressure Drops FIGURE 1 - COOLER WA TER PRESSURE DROP CURVES (ENGLISH) YCWS Model Number Cooler 0100SC, 0120SC, 0140SC 0180SC, 0200SC 0220SC, 0240SC O P Q YCWS Model Number Cooler FIGURE 3 - CONDENSER WA TER PRESSURE DROP CURVES (ENGLISH) Pressure Drop (H 2 O) Flow (GPM) Pressure Drop ...

  • York STYLE A YCWS - page 11

    FORM 201.24-EG1 11 YORK INTERNATIONAL 1 10 100 1000 10 100 1 10 100 1000 10 100 FIGURE 2 - COOLER WA TER PRESSURE DROP CURVES (SI) YCWS Model Number Cooler 0100SC, 0120SC, 0140SC 0180SC, 0200SC 0220SC, 0240SC O P Q FIGURE 4 - CONDENSER WA TER PRESSURE DROP CURVES (SI) Pressure Drop (kPa) Flow (l/s) S U Pressure Drop (kPa) Flow (l/s) Q P O 0100SC, 0 ...

  • York STYLE A YCWS - page 12

    12 YORK INTERNATIONAL GUIDE TO SELECTION Complete water chilling capacity ratings for YORK YCWS chillers are shown on the following pages to cover the majority of job requirements. For any application be- yond the scope of this Engineering Guide, consult your nearest YORK Office. SELECTION RULES 1. RATINGS - YCWS 200, 230 380, 460 & 575-3-60 ra ...

  • York STYLE A YCWS - page 13

    FORM 201.24-EG1 13 YORK INTERNATIONAL SAMPLE SELECTION Water Cooled Condenser (YCWS) GIVEN – Chill 200 GPM of water from 56ºF to 44ºF and 0.0001 evaporator fouling factor with 85ºF to 95ºF con- densing water available. Fouling factor of 0.0005 spe- cial field for the condenser. FIND – The required unit size capacity, kW, EER, and water pres ...

  • York STYLE A YCWS - page 14

    14 YORK INTERNATIONAL Ratings (R-22 English) NOTES: 1. Tons = Unit Cooling Capacity Output 2. kW = Compressor Input Power 3. MBH = Condenser heat rejection 4. EER = Chiller Energy Efficiency Ratio (Capacity [T ons x 12] ÷ kW) 5. LCWT = Leaving Chilled Water Temperature 6. Ratings based on 2.4 GPM cooler water per ton 7. Ratings certified in accord ...

  • York STYLE A YCWS - page 15

    FORM 201.24-EG1 15 YORK INTERNATIONAL YCWS0200SC YCWS0220SC YCWS0240SC IPL V = 21.8 IPL V = 20.8 IPL V = 21.2 NOTES: 1. Tons = Unit Cooling Capacity Output 2. kW = Compressor Input Power 3. MBH = Condenser heat rejection 4. EER = Chiller Energy Efficiency Ratio (Capacity [T ons x 12] ÷ kW) 5. LCWT = Leaving Chilled Water Temperature 6. Ratings bas ...

  • York STYLE A YCWS - page 16

    16 YORK INTERNATIONAL Ratings (R-22 SI) NOTES: 1. KWo = Unit kW Cooling Capacity Output 2. KWi = Compressor kW Input 3. COP = Coefficient of Performance 4. LCWT= Leaving Chilled Water Temperature 5. Ratings based on 0.047 l/s cooler water per kW. LEA VING CONDENSER W A TER TEMPERA TURE (°C) LCWT 30.0 35.0 40.0 (° C) KW o KW i KW COP KW o KW i KW ...

  • York STYLE A YCWS - page 17

    FORM 201.24-EG1 17 YORK INTERNATIONAL NOTES: 1. KWo = Unit kW Cooling Capacity Output 2. KWi= Compressor kW Input 3. COP = Coefficient of Performance 4. LCWT= Leaving Chilled Water Temperature 5. Ratings based on 0.047 l/s cooler water per kW. LEA VING CONDENSER W A TER TEMPERA TURE (°C) LCWT 30.0 35.0 40.0 (° C) KW o KW i KW COP KW o KW i KW COP ...

  • York STYLE A YCWS - page 18

    18 YORK INTERNATIONAL Ratings- Brine (30 % Ethylene Glycol) (R-22 English) NOTES: 1. Tons = Unit Cooling Capacity Output 2. kW = Compressor Input Power 3. MBH = Condenser heat rejection 4. EER = Chiller Energy Efficiency Ratio (Capacity [T ons x 12] ÷ kW) 5. LCWT = Leaving Chilled Water Temperature 6. Ratings based on 2.4 GPM cooler water per ton ...

  • York STYLE A YCWS - page 19

    FORM 201.24-EG1 19 YORK INTERNATIONAL NOTES: 1. Tons = Unit Cooling Capacity Output 2. kW = Compressor Input Power 3. MBH = Condenser heat rejection 4. EER = Chiller Energy Efficiency Ratio (Capacity [T ons x 12] ÷ kW) 5. LCWT = Leaving Chilled Water Temperature 6. Ratings based on 2.4 GPM cooler water per ton 7. Ratings certified in accordance wi ...

  • York STYLE A YCWS - page 20

    20 YORK INTERNATIONAL Ratings- Brine (30 % Ethylene Glycol) (R-22 SI) NOTES: 1. KWo = Unit kW Cooling Capacity Output 2. KWi = Compressor kW Input 3. COP = Coefficient of Performance 4. LCWT= Leaving Chilled Water Temperature 5. Ratings based on 0.047 l/s cooler water per kW. 6. For ratings other than 30% glycol, refer to the design 03 dxchill prog ...

  • York STYLE A YCWS - page 21

    FORM 201.24-EG1 21 YORK INTERNATIONAL NOTES: 1. KWo = Unit kW Cooling Capacity Output 2. KWi = Compressor kW Input 3. COP = Coefficient of Performance 4. LCWT= Leaving Chilled Water Temperature 5. Ratings based on 0.047 l/s cooler water per kW. 6. For ratings other than 30% glycol, refer to the design 03 dxchill program. LEA VING CONDENSER W A TER ...

  • York STYLE A YCWS - page 22

    22 YORK INTERNATIONAL Ratings- Brine (30 % Propylene Glycol) (R-22 English) NOTES: 1. Tons = Unit Cooling Capacity Output 2. kW = Compressor Input Power 3. MBH = Condenser heat rejection 4. EER = Chiller Energy Efficiency Ratio (Capacity [T ons x 12] ÷ kW) 5. LCWT = Leaving Chilled Water Temperature 6. Ratings based on 2.4 GPM cooler water per ton ...

  • York STYLE A YCWS - page 23

    FORM 201.24-EG1 23 YORK INTERNATIONAL NOTES: 1. Tons = Unit Cooling Capacity Output 2. kW = Compressor Input Power 3. MBH = Condenser heat rejection 4. EER = Chiller Energy Efficiency Ratio (Capacity [T ons x 12] ÷ kW) 5. LCWT = Leaving Chilled Water Temperature 6. Ratings based on 2.4 GPM cooler water per ton 7. Ratings certified in accordance wi ...

  • York STYLE A YCWS - page 24

    24 YORK INTERNATIONAL Ratings- Brine (30 % Propylene Glycol) (R-22 SI) NOTES: 1. KWo = Unit kW Cooling Capacity Output 2. KWi = Compressor kW Input 3. COP = Coefficient of Performance 4. LCWT= Leaving Chilled Water Temperature 5. Ratings based on 0.047 l/s cooler water per kW. 6. For ratings other than 30% glycol, refer to the design 03 dxchill pro ...

  • York STYLE A YCWS - page 25

    FORM 201.24-EG1 25 YORK INTERNATIONAL NOTES: 1. KWo = Unit kW Cooling Capacity Output 2. KWi = Compressor kW Input 3. COP = Coefficient of Performance 4. LCWT= Leaving Chilled Water Temperature 5. Ratings based on 0.047 l/s cooler water per kW. 6. For ratings other than 30% glycol, refer to the design 03 dxchill program. LEA VING CONDENSER W A TER ...

  • York STYLE A YCWS - page 26

    26 YORK INTERNATIONAL Part Load Ratings Rated in accordance with ARI Standard 550/590 English YCWS0100SC Load T ons k W EER 1. 0 91.3 72.0 15.2 0. 8 68.5 51.5 16.0 0. 5 45.7 24.5 22.3 0. 3 22.8 17.4 15.8 IPL V : 18.8 YCWS0200SC Load T o n s k W E E R 1. 0 183.2 126.0 17.5 0. 8 137.4 89.5 18.4 0. 5 91.6 42.1 26.1 0. 3 45.8 30.4 18.1 IP L V : 21. 8 Y ...

  • York STYLE A YCWS - page 27

    FORM 201.24-EG1 27 YORK INTERNATIONAL Rated in accordance with ARI Standard 550/590 SI YCWS0100SC Load kW o kW i C OP 100% 321.1 72.0 4.5 75 % 240.8 51.5 4.7 50 % 160.6 24.5 6.5 25 % 80.3 17.4 4.6 5.51 YCWS0120SC Load kW o k W i CO P 100% 387.9 86.2 4.5 75 % 290.9 61.4 4.7 50 % 193.9 31.3 6.2 25 % 97.0 23.4 4.1 5.32 YCWS0220SC Load k W o k W i COP ...

  • York STYLE A YCWS - page 28

    28 YORK INTERNATIONAL Physical Data MODEL YCWS 0100SC 0120SC 0140SC 0180SC 0200SC 0220SC 0240SC General Unit Data Nominal Unit Capacity (T ons) 91 1 10 131 160 183 200 216 Number of Independent Refrigerant Circuits 2 2 2 2 2 2 2 Refrigerant Charge, R22, Ckt 1/Ckt. 2 (lbs.) 100/100 100/120 120/120 210/220 220/220 220/240 240/240 Oil Charge, Ckt. 1/C ...

  • York STYLE A YCWS - page 29

    FORM 201.24-EG1 29 YORK INTERNATIONAL A B C Unit Panel D Weight Distribution by Model 1" Isolator Selections - VMC T ype CP-4- X Model A B C D YCWS0100SC 26 26 26 26 YCWS0120SC 26 26 26 26 YCWS0140SC 26 26 26 26 YCWS0180SC 31 31 31 31 YCWS0200SC 31 31 31 31 YCWS0220SC 31 31 31 31 YCWS0240SC 31 31 31 31 Isolator Selection Data Neoprene -VMC T y ...

  • York STYLE A YCWS - page 30

    30 YORK INTERNATIONAL Isolator Details 1” ISOLA TOR DET AILS NEOPRENE ISOLA TOR DET AILS TYPE MAX LOAD DEFL. SPRING & SIZE lbs. kg in. mm COLOR CP-4-26 2400 1088.6 1.17 29.7 Purple CP-4-31 4400 1995.8 0.83 21.0 Gray ENGLISH SI A B C D E F G ISOLA TOR MOUNTING BRACKET TYPE A C E H H D W X Y R-4 or 3" 6.250" 0.4" 1.625" 2.75 ...

  • York STYLE A YCWS - page 31

    FORM 201.24-EG1 31 YORK INTERNATIONAL Sound Data Sound Pressure Levels (SPL), dB re 20 microPa in accordance with ARI Standard 575-94 Note: All ‘A ’ weighted sound pressure data ± 3 dBA MODEL 6 3 125 250 500 1000 2000 4000 8000 Weighted dBA YCWS0100SC 7 6 7 2 71.5 76 7 5 7 3 6 4 6 2 79 YCWS0120SC 76 72 72 77 76 73 64 62 80 YCWS0140SC 7 6 7 2 7 ...

  • York STYLE A YCWS - page 32

    32 YORK INTERNATIONAL Dimensions (English) Center of gravity (inches) Model X Y Z YCWS0100SC 57 21 34 YCWS0120SC 58 22 34 YCWS0140SC 57 22 34 YCWS0180SC 80 24 36 YCWS0200SC 80 24 36 YCWS0220SC 80 24 37 YCWS0240SC 80 24 37 Mounting Dimensions Model AA BB CC YCWS0100SC 115-5/8 34 23-3/4 YCWS0120SC 115-5/8 34 23-3/4 YCWS0140SC 115-5/8 34 23-3/4 YCWS01 ...

  • York STYLE A YCWS - page 33

    FORM 201.24-EG1 33 YORK INTERNATIONAL DIMENSIONS NOTES: 1. CLEARANCES - Recommended YORK clearances to service the unit are as follows: Rear to Wall: 1’ 8” Front to Wall: 2’ 8” Top: 1’ 8” Tube cleaning and removal: 8’ (either end) 2. Shipping skids (not shown) will increase the height of the unit by 6”, but MUST be removed upon in- ...

  • York STYLE A YCWS - page 34

    34 YORK INTERNATIONAL All dimensions are in mm unless otherwise noted. Mounting Dimensions (mm) Model AA BB CC YCWS0100SC 2937 864 603 YCWS0120SC 2937 864 603 YCWS0140SC 2937 864 603 YCWS0180SC 4137 914 654 YCWS0200SC 4137 914 654 YCWS0220SC 4137 914 654 YCWS0240SC 4137 914 654 Center of gravity (mm) Model X Y Z YCWS0100SC 1442 545 862 YCWS0120SC 1 ...

  • York STYLE A YCWS - page 35

    FORM 201.24-EG1 35 YORK INTERNATIONAL NOTES: 1. CLEARANCES - Recommended YORK clearances to service the unit are as follows: Rear to Wall: 508mm Front to Wall: 813mm Top: 508mm Tube cleaning and removal: 2438mm (either end) 2. Shipping skids (not shown) will increase the height of the unit by 152mm, but MUST be removed upon installation. 3. Spring ...

  • York STYLE A YCWS - page 36

    36 YORK INTERNATIONAL Electrical Data MUL TIPOINT POWER SUPPL Y (SEE FIG 9 , P AGE 30) SYSTEM #1 (Each of the two field provided power supply circuits individually protected with branch circuit protection. Field connections to factory provided T erminal Block(std), Non-Fused Disconnects(opt) or individual system Circuit Breakers(opt) in each of the ...

  • York STYLE A YCWS - page 37

    FORM 201.24-EG1 37 YORK INTERNATIONAL YCWS0100SC 175 200 225 300 140 404 YCWS0120SC 227 250 300 400 181 591 YCWS0140SC 227 250 300 400 181 591 YCWS0180SC -17 284 400 350 500 227 708 YCWS0200SC 284 400 350 500 227 708 YCWS0220SC 337 400 450 600 269 708 YCWS0240SC 337 400 450 600 269 708 YCWS0100SC 153 150 200 250 122 354 YCWS0120SC 198 200 250 300 1 ...

  • York STYLE A YCWS - page 38

    38 YORK INTERNATIONAL Electrical Data - Cont . SINGLE POINT POWER SUPPL Y (SEE FIG 10 & 1 1 , P AGE 30 & 31) (One field provided power supply circuit to the control panel. Field connections to factory provided T erminal Blocks(opt) or Non-Fused Disconnect(opt). Individual system Circuit Breakers, Non-Fused Disconnects or Class ‘J’ Fuse/ ...

  • York STYLE A YCWS - page 39

    FORM 201.24-EG1 39 YORK INTERNATIONAL Incoming Wire Range Selections MODEL VOL T TERM TERM BLK N-F DIS SW N-F DIS SW NUMBER CODE BLK CUST . GROUND CUST . GROUND SYSTEM # 1 & #2 YCWS0100SC #2/0 - 500 KCM # 4 - 3/0 AWG 250 - 500 KCM # 4 - 3/0 AWG YCWS0120SC (2) #2 - 300 KCM (2) # 4 - 3/0 AWG (2) 250 - 500 KCM (2) # 4 - 3/0 AWG YCWS0140SC (2) #2 - ...

  • York STYLE A YCWS - page 40

    40 YORK INTERNATIONAL Incoming Wire Range Selections (Cont.) MUL TIPOINT WIRING SYSTEM #1 YCWS0100SC #2 - 4/0 AWG # 8 - 2 AWG #4 - 300 KCM # 6 - 1/0 AWG #6 - 350 KCM # 6 - 1/0 AWG YCWS0120SC #2 - 4/0 AWG # 8 - 2 AWG #4 - 300 KCM # 6 - 1/0 AWG #4 - 300 KCM # 6 - 1/0 AWG YCWS0140SC #2/0 - 500 KCM # 4 - 3/0 AWG #6 - 350 KCM # 6 - 1/0 AWG 250 - 500 KCM ...

  • York STYLE A YCWS - page 41

    FORM 201.24-EG1 41 YORK INTERNATIONAL MUL TIPOINT WIRING SYSTEM #2 YCWS0100SC #2 - 4/0 AWG # 8 - 2 AWG #4 - 300 KCM # 6 - 1/0 AWG #6 - 350 KCM # 6 - 1/0 AWG YCWS0120SC #2/0 - 500 KCM # 4 - 3/0 AWG #6 - 350 KCM # 6 - 1/0 AWG 250 - 500 KCM # 4 - 3/0 AWG YCWS0140SC #2/0 - 500 KCM # 4 - 3/0 AWG #6 - 350 KCM # 6 - 1/0 AWG 250 - 500 KCM # 4 - 3/0 AWG YCW ...

  • York STYLE A YCWS - page 42

    42 YORK INTERNATIONAL FIGURE 9 - MUL TIPOINT POWER SUPPL Y CONNECTION - ST ANDARD UNIT FIGURE 10 - SINGLE POINT POWER SUPPL Y WITH INTERNAL CIRCUIT BREAKER OR NON-FUSED DISCONNECT SWITCH Customer Wiring Data ...

  • York STYLE A YCWS - page 43

    FORM 201.24-EG1 43 YORK INTERNATIONAL FIGURE 1 1 - OPTIONAL SINGLE POINT POWER SUPPL Y WITH INTERNAL CLASS J FUSES/BLOCK LEGEND TERM BLOCK TERMINAL BLOCK (FACTORY MOUNTED) C.B. CIRCUIT BREAKER (FACTORY MOUNTED) NF DISC SW NON-FUSED DISCONNECT SWITCH (FACTORY MOUNTED) D.F. DUAL FUSE DISC SW DISCONNECT SWITCH HZ HERTZ MAX MAXIMUM MCA MINIMUM CIRCUIT ...

  • York STYLE A YCWS - page 44

    44 YORK INTERNATIONAL T ypical Control Panel Wiring ...

  • York STYLE A YCWS - page 45

    FORM 201.24-EG1 45 YORK INTERNATIONAL ...

  • York STYLE A YCWS - page 46

    46 YORK INTERNATIONAL UNIT LOCA TION Chillers may be placed on the ground floor or upper floor of the building. The floor must be level and capable of supporting 150% of the operating weight of the unit. Units should be located away from noise-critical areas. Ser- vice clearance must be allowed and include space for removing cooler or condenser tub ...

  • York STYLE A YCWS - page 47

    FORM 201.24-EG1 47 YORK INTERNATIONAL YORK Model YCWS ______ Packaged Chiller(s). The (each) unit shall have a cooling capacity of ______ tons with Compressor kW when cooling GPM of water from ______ °F (°C) to ______ °F (°C) and with ____ GPM of condensing water entering at ____ °F (°C) and leaving at _____ °F (°C), and a cooler fouling fa ...

  • York STYLE A YCWS - page 48

    48 YORK INTERNATIONAL each unit. All piping will be ACR copper with brazed joints. The liquid line will include: a shutoff valve with charging port; sightglass with moisture indicator; thermal expan- sion valve; solenoid valve; and high-absorption remov- able-core filter drier. The entire suction line and the liq- uid line between the expansion val ...

  • York STYLE A YCWS - page 49

    FORM 201.24-EG1 49 YORK INTERNATIONAL ...

  • York STYLE A YCWS - page 50

    50 YORK INTERNATIONAL ...

  • York STYLE A YCWS - page 51

    FORM 201.24-EG1 51 YORK INTERNATIONAL ...

  • York STYLE A YCWS - page 52

    Form 201.24-EG1 (701) New Release RPC 3M 701 4.16 Codes: DXS, ET ...

Manufacturer York Category Water Dispenser

Documents that we receive from a manufacturer of a York STYLE A YCWS can be divided into several groups. They are, among others:
- York technical drawings
- STYLE A YCWS manuals
- York product data sheets
- information booklets
- or energy labels York STYLE A YCWS
All of them are important, but the most important information from the point of view of use of the device are in the user manual York STYLE A YCWS.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals York STYLE A YCWS, service manual, brief instructions and user manuals York STYLE A YCWS. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product York STYLE A YCWS.

Similar manuals

A complete manual for the device York STYLE A YCWS, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use York STYLE A YCWS by users. Manuals are usually written by a technical writer, but in a language understandable to all users of York STYLE A YCWS.

A complete York manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual York STYLE A YCWS - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the York STYLE A YCWS, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the York STYLE A YCWS, that we can find in the current document
3. Tips how to use the basic functions of the device York STYLE A YCWS - which should help us in our first steps of using York STYLE A YCWS
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with York STYLE A YCWS
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of York STYLE A YCWS in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning York STYLE A YCWS?

Use the form below

If you did not solve your problem by using a manual York STYLE A YCWS, ask a question using the form below. If a user had a similar problem with York STYLE A YCWS it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)