    FieldPoint ™ Operating Instructions FP-AI-110 and cFP-AI-110 Eight-Channel, 16-Bit Analog Input M odules These operating instructions descri be ho w to install and use the FP-AI-110 and cFP-AI-110 analog input modules (referred to inclusiv ely as the [c]FP-A I-110). F or information about configuring and accessing the [c]F P- AI-110 ov er a netwo ...

  • National Instruments FP-Al-110 - page 2

    FP-AI-110 and cFP-AI-110 2 ni.com T o install the FP- AI-110, refer to Figure 1 and complete the follow ing steps: 1. Slide the terminal base key to either position X (used for an y module) or position 1 (used for the FP- AI-110). 2. Align the FP- AI-110 alignmen t sl ots with the guide rails on the terminal base. 3. Press firmly to seat the FP- AI ...

  • National Instruments FP-Al-110 - page 3

    © National Instruments Corp. 3 FP-AI-110 and cFP-AI-110 (10 lb ⋅ in.) of torque. The nylon coating on the screws pre vents them from loosening. Figure 2. Installing the cFP-AI-110 Wiring the [c]FP-AI-110 The FP-TB- x terminal base ha s connections for each of the eight input channels and for an external power su pply to power field de vice s. Th ...

  • National Instruments FP-Al-110 - page 4

    FP-AI-110 and cFP-AI-110 4 ni.com is 2 A or less and the maximum current through any V SUP terminal is 1 A or less . Install a 2 A maximum, fast-acting fuse between t he external power supply and the V terminal on each channel. The wiring diagrams in this document sho w fuses where appropriate. T able 1 lists the terminal assign ments for the signa ...

  • National Instruments FP-Al-110 - page 5

    © National Instruments Corp. 5 FP-AI-110 and cFP-AI-110 T aking Measurements with the [c]FP-AI-110 The [c]FP- AI-110 has eight single- ended input cha nnels. All eight channels share a common ground referen ce that is isolated from other modules in the FieldPoint system. Figure 3 shows the analog input circuitry on one channel. Figure 3. FP- AI-11 ...

  • National Instruments FP-Al-110 - page 6

    FP-AI-110 and cFP-AI-110 6 ni.com Figure 5 sho ws how to connect a v oltage source with an extern al power supply to one channel of the [c]FP-AI-110. Figure 5. Voltage Source with Ex ternal Powe r Supply Measuring Current with the [c]FP-AI-110 The input ranges for current sources are 0 –20, 4 –20, and ± 20 mA. The module reads current flowing ...

  • National Instruments FP-Al-110 - page 7

    © National Instruments Corp. 7 FP-AI-110 and cFP-AI-110 Figure 6. Current Source without External Power Supply Figure 7 sho ws how to connect a cu rrent sour ce with an external power supply to one channel of the [c]FP-AI-110. Figure 7. Current Source with Ex ternal Power Supply Input Ranges T o prev ent inaccurate readings, c hoose an input range ...

  • National Instruments FP-Al-110 - page 8

    FP-AI-110 and cFP-AI-110 8 ni.com Overranging The [c]FP- AI-110 has an overranging feature that meas ures a little beyond the nominal values of each rang e. For example, the actual measurement limit of the ± 10 V range is ± 10.4 V . The overrang ing feature enables the [c]FP- AI-110 to compensate for field de vices with span errors of up to + 4% ...

  • National Instruments FP-Al-110 - page 9

    © National Instruments Corp. 9 FP-AI-110 and cFP-AI-110 sampling rate is faster than th e rate at which the network module polls the [c]FP-AI-110 for data. Status Indicators The [c]FP-AI-110 has tw o green status LEDs, POWER and READY . After you insert the [c] FP-AI-110 into a terminal base or backplane and apply po wer to th e connected network ...

  • National Instruments FP-Al-110 - page 10

    FP-AI-110 and cFP-AI-110 10 ni.com working v oltages of 250 V rms 1 . Safety standards (such as those published by UL and IEC) requir e the use of double insulation between hazardous voltages and an y human-accessi ble parts or circuits. Never try to use any isolation produ ct between human-accessible parts (such as DIN rails or monito ring station ...

  • National Instruments FP-Al-110 - page 11

    © National Instruments Corp. 11 FP-AI-110 and cFP-AI-110 • Operate the [c]FP-AI-110 only at or belo w Pollution Degree 2. Pollution Degree 2 means th at only nonconductiv e pollution occurs in most case s. Occasionally , howe ver , a temporary conductivity caused by conde nsation must be e xpected. • Operate the [c]FP-AI-110 at or below Measur ...

  • National Instruments FP-Al-110 - page 12

    FP-AI-110 and cFP-AI-110 12 ni.com Safety Guidelines for Hazardous V oltages If hazardous voltages are connected to the module, take the follow ing precautions. A hazardous voltage is a v oltage greater than 42.4 V peak or 60 VDC to earth ground. Caution Ensure that hazardous voltage wiring is performed only by qualified personnel adhering to local ...

  • National Instruments FP-Al-110 - page 13

    © National Instruments Corp. 13 FP-AI-110 and cFP-AI-110 Effecti ve resolution by inpu t signal range and f ilter setting Input charac teristics by f ilter setting Normal-mode rejection .. .............. ..... 95 dB (with 50/60 Hz filter) Nonlinearity .......... ........... ......... ........ 0.0015% (monotonicity 1 guaranteed ov er the operating ...

  • National Instruments FP-Al-110 - page 14

    FP-AI-110 and cFP-AI-110 14 ni.com Input current 25 °C........... ...................... .......... 400 pA typ, 1 nA max 70 °C ............. ........... ........... ........ 3 nA typ, 15 nA max Input noise (with 50 or 60 Hz filter enabled) ± 60 mV range ...... ........... ........... . ± 3 LSB 1 peak-to-peak ± 300 mV range ...... ........... . ...

  • National Instruments FP-Al-110 - page 15

    © National Instruments Corp. 15 FP-AI-110 and cFP-AI-110 Note Full scale is the maximum value of the nominal input range. F or example, for the ± 10 V input range, full scale is 10 V and ± 0.01% of full scale is 1 mV . Gain error drift ........... ......... ........... ... ± 20 ppm/°C Offset error drift W ith 50 or 60 Hz filte r enabled ...... ...

  • National Instruments FP-Al-110 - page 16

    FP-AI-110 and cFP-AI-110 16 ni.com Physical Char acteristics Indicators ............ ........... ........... ........ Green POWER and READY indicators W eight FP-AI-110..... ............. .............. ... 140 g (4.8 oz) cFP-AI-110 ....... ............ .............. 110 g (3.7 oz) Power Requirements Power from network module ............ 350 mW S ...

  • National Instruments FP-Al-110 - page 17

    © National Instruments Corp. 17 FP-AI-110 and cFP-AI-110 Operating shock (IEC 60068-2-27)........... ........... ........ 50 g, 3 ms half sine, 18 shocks at 6 orientations; 30 g, 11 ms half sine, 18 shocks at 6 orientations Safety This product is designed to meet the requirements of the following standards of safety for electric al equipment for m ...

  • National Instruments FP-Al-110 - page 18

    FP-AI-110 and cFP-AI-110 18 ni.com CE Compliance This product meets the essentia l requirements of applicable European Directi ves, as amended for CE ma rking, as follows: Lo w-V oltage Directi ve (s afety). ..... ... 73/23/EEC Electromagnet ic Compatibility Directiv e (EMC) ... ........... ......... ........ 89/336/EEC Note Refer to the Declaratio ...

  • National Instruments FP-Al-110 - page 19

    © National Instruments Corp. 19 FP-AI-110 and cFP-AI-110 Where to Go for Support For more information about settin g up the FieldPoint system, refer to these National Instruments documents: • FieldPoint network module user manual • Other FieldPo int I/O m odule operating instructions • FieldPoint terminal base and connector block operating i ...

  • National Instruments FP-Al-110 - page 20

    © 2003–2005 Nati onal Instruments Corp. All rights reserved. 373280A-01 Jun05 National Instruments, NI, n i.com, and LabVIEW are trademarks of National I nstruments Corporation. Refer to the Terms of Use section on ni.com/legal for more information about National Instruments tra demarks. Other product and company names ment ioned herein are trad ...

Manufacturer National Instruments Category Music Mixer

Documents that we receive from a manufacturer of a National Instruments FP-Al-110 can be divided into several groups. They are, among others:
- National Instruments technical drawings
- FP-Al-110 manuals
- National Instruments product data sheets
- information booklets
- or energy labels National Instruments FP-Al-110
All of them are important, but the most important information from the point of view of use of the device are in the user manual National Instruments FP-Al-110.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals National Instruments FP-Al-110, service manual, brief instructions and user manuals National Instruments FP-Al-110. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product National Instruments FP-Al-110.

A complete manual for the device National Instruments FP-Al-110, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use National Instruments FP-Al-110 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of National Instruments FP-Al-110.

A complete National Instruments manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual National Instruments FP-Al-110 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the National Instruments FP-Al-110, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the National Instruments FP-Al-110, that we can find in the current document
3. Tips how to use the basic functions of the device National Instruments FP-Al-110 - which should help us in our first steps of using National Instruments FP-Al-110
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with National Instruments FP-Al-110
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of National Instruments FP-Al-110 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning National Instruments FP-Al-110?

Use the form below

If you did not solve your problem by using a manual National Instruments FP-Al-110, ask a question using the form below. If a user had a similar problem with National Instruments FP-Al-110 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)