Manual Rheem RJNA Series

50 pages 1.85 mb
Download

Go to site of 50

Summary
  • Rheem RJNA Series - page 1

    FORM NO . P1 1 -763 R EV . 1 Supersedes F orm No. P1 1 -763 P ACKAGE H EA T P UMP U NITS RJNA- HIGH EFFICIENCY SERIES NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] *Unit shown with optional louver panels installed. “CERTIFIED UNDER THE A.R.I. CERTIFICA TION PROGRAM—A.R.I. ST ANDARD 240” ISO 9001:2000 ...

  • Rheem RJNA Series - page 2

    2 T ABLE OF CONTENTS I nt r od uc ti on .................................................................................................. 3-4 Mo d el Id en t if ic a ti on Op t io ns............................................................................ 5-6 General Data R JN A- S er ie s ....................................................... ...

  • Rheem RJNA Series - page 3

    3 INTRODUCTION These qualit y features are included in the Rhe em Outdoor P acka g e Heat Pumps Evaporator Coil/Filter Access Optional Electric Heater Kit Compressor Access Control Box Access Blower Access ...

  • Rheem RJNA Series - page 4

    4 INTRODUCTION INTRODUCTION ENGI NEERI NG FEA TURES RJNA- Series P ackage He at Pumps 1. All models fe ature Copeland ® Scr oll ® compressors offering maximum r eliabilit y , ef ficiency , and quiet operati on. 2. One-piece top o ver the indoor se ction with drip lip, dra wn painted b ase pan, and 1 " [25.4 mm] raised fl anges for s upply/re ...

  • Rheem RJNA Series - page 5

    5 MODEL IDENTIFICA TION—RJNA- SERIES R JNA—A0 3 6JK 0 0 0 Electric Heat 000 = No Resistance Hea t 010 = 10 kW Resistance Hea t 015 = 15 kW Resistance Hea t 020 = 20 kW Resistance Hea t Drive P ackage K = Direct Driv e L = Belt Driv e M = Belt Driv e—High Static Electrical Designation J = 208-230 V , 1 PH, 60 Hz C = 208-230 V , 3 PH, 60 Hz D = ...

  • Rheem RJNA Series - page 6

    6 OPTIONS—RJNA- SERIES Option Code Low Ambient Reduced Height Baserails AA Side Flow AD AF x AK x Hail Guard x x BD x x CK x x x BX x AL x No Options Freeze Stat Time Delay x BS x F ACT OR Y I NST ALLED OPTION CODES FOR RJNA (3-5 T on) [1 0.6- 1 7 .6 kW] (A036, A042, A0 48, A060) Example: RJNA-A060CK000 XX X (where XX is factory installed option) ...

  • Rheem RJNA Series - page 7

    7 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A036CK A036CL A036CM A036DK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 37,600 [11] 37,600 [11] 37,600 [11] 37,600 [11] EER/SEER 2 11.6/13 11.6/13 11.6/13 11.6/13 Nominal CFM/ARI Rated CFM [L/s] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] ARI Net Coolin ...

  • Rheem RJNA Series - page 8

    8 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A036DL A036DM A036JK A042CK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 37,600 [11] 37,600 [11] 37,600 [11] 42,500 [12.5] EER/SEER 2 11.6/13 11.6/13 11.6/13 11.8/13 Nominal CFM/ARI Rated CFM [L/s] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] 1400/1400 [661/661] ARI Net Cool ...

  • Rheem RJNA Series - page 9

    9 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A042CL A042CM A042DK A042DL Cooling Performance 1 Gross Cooling Capacity Btu [kW] 42,500 [12.5] 42,500 [12.5] 42,500 [12.5] 42,500 [12.5] EER/SEER 2 11.8/13 11.8/13 11.8/13 11.8/13 Nominal CFM/ARI Rated CFM [L/s] 1400/1400 [661/661] 1400/1400 [661/661] 1400/1400 [661/661] 1400/1400 [661/661] ARI Ne ...

  • Rheem RJNA Series - page 10

    10 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A042DM A042JK A048CK A048CL Cooling Performance 1 Gross Cooling Capacity Btu [kW] 42,500 [12.5] 42,500 [12.5] 49,500 [14.5] 49,500 [14.5] EER/SEER 2 11.8/13 11.8/13 11.65/13 11.65/13 Nominal CFM/ARI Rated CFM [L/s] 1400/1400 [661/661] 1400/1400 [661/661] 1600/1600 [755/755] 1600/1600 [755/755] ARI ...

  • Rheem RJNA Series - page 11

    11 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A048CM A048DK A048DL A048DM Cooling Performance 1 Gross Cooling Capacity Btu [kW] 49,500 [14.5] 49,500 [14.5] 49,500 [14.5] 49,500 [14.5] EER/SEER 2 11.65/13 11.65/13 11.65/13 11.65/13 Nominal CFM/ARI Rated CFM [L/s] 1600/1600 [755/755] 1600/1600 [755/755] 1600/1600 [755/755] 1600/1600 [755/755] A ...

  • Rheem RJNA Series - page 12

    12 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A048JK A060CK A060CL A060CM Cooling Performance 1 Gross Cooling Capacity Btu [kW] 49,500 [14.5] 63,500 [18.6] 64,000 [18.8] 64,000 [18.8] EER/SEER 2 11.65/13 11.55/13 11.55/13 11.55/13 Nominal CFM/ARI Rated CFM [L/s] 1600/1600 [755/755] 2000/2000 [944/944] 2000/2000 [944/944] 2000/2000 [944/944] A ...

  • Rheem RJNA Series - page 13

    13 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A060DL A060DM A060JK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 64,000 [18.8] 64,000 [18.8] 63,500 [18.6] EER/SEER 2 11.55/13 11.55/13 11.55/13 Nominal CFM/ARI Rated CFM [L/s] 2000/2000 [944/944] 2000/2000 [944/944] 2000/2000 [944/944] ARI Net Cooling Capacity Btu [kW] 61,500 [18] 61,50 ...

  • Rheem RJNA Series - page 14

    14 GENERAL DA T A—RJNA- SERIES NOTES: 1 . Cooling Pe r forma nce is rated a t 95° F ambient, 80° F entering dry bulb, 67 ° F entering we t bulb. Gross cap acit y does not include the effect of f an motor he at. ARI capacity is net and include s the ef f ect of fan mot or heat. Units ar e suitable for opera tion to  20% of nominal cfm. Units ...

  • Rheem RJNA Series - page 15

    COOLING PERFORMANCE D A T A—RJNA-A036 HEA TI NG PERF ORMANCE D A T A—RJNA-A036 DR —Depression ratio dbE —Entering air dr y bulb wbE—Enter ing air wet bulb T ot al —T ot al capacit y x 1 0 00 BTUH Sens —Sensible capacit y x 1 0 00 BTUH Power—K W input NOTES: ➀ When the entering air dr y bulb is other than 80°F [27°C], adjust the ...

  • Rheem RJNA Series - page 16

    COOLING PERFORMANCE D A T A—RJNA-A0 42 HEA TI NG PERF ORMANCE D A T A—RJNA-A042 DR —Depression ratio dbE —Entering air dr y bulb wbE—Enter ing air wet bulb T ot al —T ot al capacit y x 1 0 00 BTUH Sens —Sensible capacit y x 1 0 00 BTUH Power—K W input NOTES: ➀ When the entering air dr y bulb is other than 80°F [27°C], adjust the ...

  • Rheem RJNA Series - page 17

    COOLING PERFORMANCE D A T A—RJNA-A0 48 DR —Depression ratio dbE —Entering air dr y bulb wbE—Enter ing air wet bulb T ot al —T ot al capacit y x 1 0 00 BTUH Sens —Sensible capacit y x 1 0 00 BTUH Power—K W input NOTES: ➀ When the entering air dr y bulb is other than 80°F [27°C], adjust the sensible capacit y from the table by addin ...

  • Rheem RJNA Series - page 18

    COOLING PERFORMANCE D A T A—RJNA-A060 HEA TI NG PERF ORMANCE D A T A—RJNA -A060 DR —Depression ratio dbE —Entering air dr y bulb wbE—Enter ing air wet bulb T ot al —T ot al capacit y x 1 0 00 BTUH Sens —Sensible capacit y x 1 0 00 BTUH Power—K W input NOTES: ➀ When the entering air dr y bulb is other than 80°F [27°C], adjust the ...

  • Rheem RJNA Series - page 19

    External Static Pressure—Inches W .C. [kPa] CFM [L/s] Air Delivery/RPM/Watts—208 Volts Side Discharge—W et Coil 4.0 [14.07] Low Blower Size/ Motor HP [w] & # of Speeds Nominal Cooling Capacity T ons [kW] 3.5 [12.30] Factory Motor Speed 1400/1800 Manufacturer Recommended Air -Flow Range (Min/Max) CFM Motor Speed 10x10 1/2 HP [373] 3 Speed ...

  • Rheem RJNA Series - page 20

    20 AIRFLOW PERFORMANCE—RJNA- SERIES 825 Models RJNA-A036 [10.55 kW] & A042 [12.31 kW]—Heat Pump (13 SEER) External Static Pressure—Inches of Water [kPa] 0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] 0.8 [.20] 0.9 [.22] 1.0 [.25] 1.1 [.27] 1.2 [.30] 1.3 [.32] 1.4 [.35] 1.5 [.37] RPM W RPM W RPM W RPM W RPM W RPM W R ...

  • Rheem RJNA Series - page 21

    BEL T -DRIVE AI RFL OW P ERFORMANCE COMPONENT AIR RESI ST AN CE NOTES: 1 . Performance shown with dr y coil, st andard 1" [25.4 mm] filters & side discharge. Add component resistance to determine tot al E.S.P . 2. St andard CFM @ .075 lbs./cu . f t. 3. Motor ef ficiency = 80% 4. BHP = Watt s x Motor Eff. 74 6 [ ] Des igna tes Met ric C onv ...

  • Rheem RJNA Series - page 22

    ELECTRICAL DA T A – RJNA SERIES Minimum Circuit Ampacity 19/19 Unit Information Unit Operating Voltage Range 187-253 Minimum Overcurrent Protection Device Size 25/25 Maximum Overcurrent Protection Device Size 25/25 Compressor Motor No. 1 Volts 208/230 Phase 3 HP 2.5 RPM 3450 Amps (RLA) 9.6/9.6 Amps (LRA) 77/77 Condenser Motor No. 1 Volts 208/230 ...

  • Rheem RJNA Series - page 23

    ELECTRICAL DA T A – RJNA SERIES Minimum Circuit Ampacity Minimum Overcurrent Protection Device Size 22/22 25/25 Maximum Overcurrent Protection Device Size 30/30 Compressor Motor No. 1 Volts 208/230 Phase 3 HP 3.5 RPM 3450 Amps (RLA) 12.4/12.4 Amps (LRA) Unit Information Unit Operating Voltage Range 88/88 187-253 Condenser Motor No. 1 Volts 208/23 ...

  • Rheem RJNA Series - page 24

    24 UNITS WITH HEA TER KITS—RJNA- SERIES * A10C+ * A10C+ 7.2/9.6 24.56/32.75 20.0/23.1 44/48 45/45 50/50 * A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80 * A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 48/52 50/50 60/60 * A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 56/62 60/60 70/70 *A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80 7.2/9.6 A036CK ...

  • Rheem RJNA Series - page 25

    25 UNITS WITH HEA TER KITS—RJNA- SERIES * A10C+ * A10C+ 7.2/9.6 24.56/32.75 20.0/23.1 43/47 45/45 50/50 * A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 68/75 70/70 80/80 * A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 47/51 50/50 60/60 * A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 55/61 60/60 70/70 * A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 68/75 70/70 80/80 7.2/9.6 A036C ...

  • Rheem RJNA Series - page 26

    26 UNITS WITH HEA TER KITS—RJNA- SERIES * A10C+ * A10C+ 7.2/9.6 24.56/32.75 20.0/23.1 44/48 45/45 50/50 * A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80 * A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 48/52 50/50 60/60 * A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 56/62 60/60 70/70 * A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80 7.2/9.6 A036C ...

  • Rheem RJNA Series - page 27

    27 UNITS WITH HEA TER KITS—RJNA- SERIES * A10D+ * A10D+ 9.6 32.75 11.6 24 25 25 * A20D+ 19.2 65.51 23.1 38 40 40 * A12D+ 11.2 38.21 13.5 26 30 30 * A15D+ 14.4 49.13 17.3 31 35 35 *A21D+ 19.2 65.51 23.1 38 40 40 9.6 A036DK No Heat — — — 9 15 15 32.75 11.6 24 * A06D+ 5.6 19.10 6.7 18 20 20 25 25 * A20D+ 19.2 65.51 23.1 39 40 40 * A12D+ 11.2 3 ...

  • Rheem RJNA Series - page 28

    28 UNITS WITH HEA TER KITS—RJNA- SERIES * A10D+ * A10D+ 9.6 32.75 11.6 24 25 25 * A20D+ 19.2 65.51 23.1 38 40 40 * A12D+ 11.2 38.21 13.5 26 30 30 * A15D+ 14.4 49.13 17.3 31 35 35 *A21D+ 19.2 65.51 23.1 38 40 40 9.6 A036DL No Heat — — — 9 15 15 32.75 11.6 24 * A06D+ 5.6 19.10 6.7 18 20 20 25 25 * A20D+ 19.2 65.51 23.1 39 40 40 * A12D+ 11.2 3 ...

  • Rheem RJNA Series - page 29

    29 UNITS WITH HEA TER KITS—RJNA- SERIES * A10D+ * A10D+ 9.6 32.75 11.6 24 25 25 * A20D+ 19.2 65.51 23.1 38 40 40 * A12D+ 11.2 38.21 13.5 26 30 30 * A15D+ 14.4 49.13 17.3 31 35 35 *A21D+ 19.2 65.51 23.1 38 40 40 9.6 A036DM No Heat — — — 9 15 15 32.75 11.6 24 * A06D+ 5.6 19.10 6.7 18 20 20 25 25 * A20D+ 19.2 65.51 23.1 39 40 40 * A12D+ 11.2 3 ...

  • Rheem RJNA Series - page 30

    A036JK No Heat — — — 25/25 30/35 30/35 * A10J+ 7.2/9.6 24.56/32.75 34.7/40.0 69/75 70/70 80/80 * A06J+ 4.2/5.6 14.33/19.10 20.2/23.3 51/55 60/60 60/60 *A11J+ 7.2/9.6 24.56/32.75 34.7/40.0 69/75 70/70 80/80 * A20J+ 14.4/19.2 49.13/65.51 69.3/80.0 112/125 125/125 125/125 * A12J+ 8.4/11.2 28.66/38.21 40.4/46.7 76/84 80/80 90/90 * A15J+ 10.8/14.4 ...

  • Rheem RJNA Series - page 31

    UNIT D IMENS IONS P A CKA GE HEA T PUMPS [ ] Des igna tes Me tric C onv ers ions 31 UNIT DIMENSIONS—RJNA- SERIES ...

  • Rheem RJNA Series - page 32

    UNIT D IMENS IONS P A CKA GE HEA T PUMPS [ ] Des igna tes Me tric C onv ers ions BOT TOM VIEW 32 UNIT DIMENSIONS—RJNA- SERIES ...

  • Rheem RJNA Series - page 33

    SELECTION PR OCEDURE 1 . Determine cooling and heating requirements at design conditions. Example: T otal cooling capacity ............43,600 BTUH [1 2.78 kW] Sensible cooling capacity ......34,00 0 BTUH [9.96 kW] Condenser ent ering air ..........95°F [35°C] E vaporat or entering air ..........63°F [1 7°C] wb/76°F [2 4°C] db Indoor air flow ...

  • Rheem RJNA Series - page 34

    Accessory Description Model Application 3 to 5 T on [10.6 to 17.6 kW] Accessory Model No. 3 to 5 T on [10.6 to 17.6 kW] Roofcurb Adapters RJNA- RXRX-BBCDB21 RXRX-BBCDB22 RXRX-BBCDB23 Economizer with Single Enthalpy ➀ RJNA- RXRD-KECM3 Time Delay RJNA- RXMD-B01 Low Ambient Control to 0°F [-18°C] RJNA- RXPZ-C01 Fresh Air Damper Manual RJNA- RXRF-F ...

  • Rheem RJNA Series - page 35

    Roofcurb Adapters Old Models OLD CURB MODEL ROOFCURB ADAPTER NEW MODEL MEDIUM C ABINET (3 TON [1 1 kW]) 21 SE RI ES RXP A-CA2 1 (1) RXRA-DB21 (2) RXRX -BBCDB21 RJNA (-)SNC, (-)SND, (-)SNE (-)RGE, (-)RGF , (-)RGG (-)PNC, (-)PND EX TRA LARGE CABINET (3.5-5 TON [1 2-1 8 kW]) 23 SE RIE S RXP A-CA23 (1) RXRA-DB23 (2) RXRX -BBCDB23 (-)SNC, (-)SND, (-)SNE ...

  • Rheem RJNA Series - page 36

    ROOFCURBS (F ull Perimeter) ■ Rheem’s ne w roofcurb design can be utiliz ed on 3 through 5 t on [1 0.6- 1 7 .6 kW] models. ■ T wo a vailable heights (1 4" [356 mm] and 2 4" [6 1 0 mm]) for ALL models. ■ Quick assembl y corners for simple and f ast assembl y . ■ Opening pro vided in bottom pan to ma tch the “Thru the Curb” el ...

  • Rheem RJNA Series - page 37

    [ ] Designates Metric Conversions ■ Fea tu re s Honeywell Cont rols ■ A vailable fact or y installed or field accessory ■ Gear Driv en Direct Drive Actua tor ■ F ully Modulating (0- 1 00%) ■ Low L eakage D ampers ■ Horiz ontal or Downflow Applica tions ■ Slip-In Design for E asy Installa tions ■ Plug-In P olarized 1 2-pin Electrical ...

  • Rheem RJNA Series - page 38

    Illustration ST -A0903-01 INTEGRAL PO WER EXHA UST FOR EC ONOM IZER (FIELD I NST ALLED ONL Y) RXRX -BFF0 4C—3-5 T on [10.6- 1 7 .6 kW] Models 208-230 V , 1 PH, 60 Hz ■ For RXRD-KECM3 E conomiz er ■ Downflow or hori zontal applica tions ■ Requires s eparat e power supply w ith disconnect ■ Adjustable s witch on economiz er , factory preset ...

  • Rheem RJNA Series - page 39

    DUCT AD APTERS (3 TO 5 TON [1 0.6 TO 1 7 .6 kW] MODELS) Rectangular to Round T ransitions (Downflow) RXMC-CB03 – 1 8" [457 mm] Round A vailable in 1 8 inch round to fit all units. Dr ops into a nd secures to RXK G- Series Roofcurbs. For use with Concentric Diffusers. [ ] Designates Metric Conversions 39 ACCESSORIES ...

  • Rheem RJNA Series - page 40

    SID E DISCHARGE CONCENTR IC DI FFUSER RXRN -F A60 (3 to 5 T on [10.6 t o 1 7 .6 kW] Models) For Use With Duct A dapter (RXMC) Model No. A B C D E F G H I J K Duct Size RXRN-F A60 47 5 / 8 " [1210 mm] 23 5 / 8 " [600 mm] 11 3 / 8 " [289 mm] 21 1 / 2 " [546 mm] 45 1 / 2 " [1156 mm] 22 1 / 2 " [572 mm] 11 1 / 2 " [29 ...

  • Rheem RJNA Series - page 41

    FLUSH MOUNT CONCENTRIC D IFFUSER RXRN -F A70 (3 to 5 T on [10.6 t o 1 7 .6 kW] Models) For Use With Duct A dapter (RXMC) DIMENSION AL D A T A ENGI NEERIN G D A T A Model No. A B C D E F G H Duct Size RXRN-F A70 47 5 / 8 " [1210 mm] 23 5 / 8 " [600 mm] 13 1 / 2 " [343 mm] 21" [533 mm] 45" [1143 mm] 22 1 / 2 " [572 mm] 1 ...

  • Rheem RJNA Series - page 42

    THERMOST A TS — P A CKA GE HE A T PUMPS RECOMMENDED HEA T P UMP THERM OST A T S Units Without Economizer Honeywell T7300A1005 T8611R1166 T874R T841A1209 T874G1881 Q674F1360 Included Q674F1360 Included Q7300C1006 1 1 1 1 1 2 2 2 2 2 Manufacturer Model Sub-Base Cooling Stages Heating Stages T8141A Included 1 2 General Electric 3AA T86B8A2 Included ...

  • Rheem RJNA Series - page 43

    43 WIRING SCHEMA TICS—RJNA- SERIES ...

  • Rheem RJNA Series - page 44

    44 WIRING SCHEMA TICS—RJNA- SERIES ...

  • Rheem RJNA Series - page 45

    45 WIRING SCHEMA TICS—RJNA- SERIES ...

  • Rheem RJNA Series - page 46

    46 WIRING SCHEMA TICS—RJNA- SERIES ...

  • Rheem RJNA Series - page 47

    47 WIRING SCHEMA TICS—RJNA- SERIES ...

  • Rheem RJNA Series - page 48

    48 WIRING SCHEMA TICS—RJNA- SERIES ...

  • Rheem RJNA Series - page 49

    49 WIRING SCHEMA TICS—RJNA- SERIES ...

  • Rheem RJNA Series - page 50

    GENERAL TERMS OF LI MITED W ARR ANT Y Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Pro vincial, and Local codes, regulations, and practices. RHEEM AIR CONDITIONING DIVISION 5600 Old Greenwood Road, Fort Smith, Arkansas 72908 “In keeping with its pol ...

Manufacturer Rheem Category Electric Heater

Documents that we receive from a manufacturer of a Rheem RJNA Series can be divided into several groups. They are, among others:
- Rheem technical drawings
- RJNA Series manuals
- Rheem product data sheets
- information booklets
- or energy labels Rheem RJNA Series
All of them are important, but the most important information from the point of view of use of the device are in the user manual Rheem RJNA Series.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Rheem RJNA Series, service manual, brief instructions and user manuals Rheem RJNA Series. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Rheem RJNA Series.

Similar manuals

A complete manual for the device Rheem RJNA Series, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Rheem RJNA Series by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Rheem RJNA Series.

A complete Rheem manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Rheem RJNA Series - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Rheem RJNA Series, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Rheem RJNA Series, that we can find in the current document
3. Tips how to use the basic functions of the device Rheem RJNA Series - which should help us in our first steps of using Rheem RJNA Series
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Rheem RJNA Series
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Rheem RJNA Series in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Rheem RJNA Series?

Use the form below

If you did not solve your problem by using a manual Rheem RJNA Series, ask a question using the form below. If a user had a similar problem with Rheem RJNA Series it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)