    SINGLE-PACKAGED GAS HEATING/ELECTRIC COOLING UNITS Model 574B Sizes 024-060 2 to 5 Nominal Tons Low NOx Models Available Form No. PDS 574B.24.1 Single-Packaged Rooftop Products with Energy-Saving Fea- tures and Puron® refrigerant. • Direct Spark Ignition • Low Sound Levels • Up to 81% AFUE • 13 SEER • Variable Speed Blower Standard • F ...

  • Bryant 574B - page 2

    — 2 — Corporate thermostats include the Time Guard ® II anti-short cycle protection circuitry. If a non-corporate thermostat without anti-short cycle protection is used the Time Guard II field in- stalled anti-short cycle kit is recommended. Refrigerant system is designed to provide dependability. Liquid filter dryers are used to promote clean ...

  • Bryant 574B - page 3

    — 3 — ARI* CAPACITIES COOLING CAPACITIES AND EFFICIENCIES UNIT 574B NOMINAL T ONS ST ANDARD CFM NET COOLING CAP A CITIES (Btuh) EER @A‡ SEER† SOUND RA TINGS** (dB) 024040 2 800 24,000 11.0 13.0 72 030040 036060 2-1/2 036060 036090 3 1150 36,000 11.0 13.0 72 042060 042090 3-1/2 11.0 048090 048115 048130 4 1450 45,000 11.0 13.0 78 060090 0601 ...

  • Bryant 574B - page 4

    — 4 — ARI* CAPACITIES (cont) HEATING CAPACITIES AND EFFICIENCIES LEGEND AFUE — Annual Fuel Utilization Efficiency NOTE: Before purchasing this appliance, read important energy cost and efficiency information available from your retailer. OUTDOOR SOUND: OCT A VE B AND D A T A — DECIBELS (Lw(A)) UNIT 574B HEA TING INPUT (Btuh) OUTPUT CAP A CI ...

  • Bryant 574B - page 5

    — 5 — PHYSICAL DATA † Required filter sizes sho wn are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated cooling air- flo w or the heating airflow v elocity of 300 ft/min for thro waw ay type or 450 ft/min for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in ...

  • Bryant 574B - page 6

    — 6 — PHYSICAL DATA (cont) † Required filter sizes shown are based on the lar ger of the ARI (Air Conditioning & Refrigeration Institute) rated cooling air - flo w or the heating airflow v elocity of 300 ft/min for thro waw ay type or 450 ft/min for high-capacity type. Air filter pressure drop for non-standard filters must not exceed ...

  • Bryant 574B - page 7

    — 7 — OPTIONS AND ACCESSORIES Factory-installed options Coil options include Tin-Plated* indoor hairpins, copper/copper and vinyl-coated construction for refrigerant coils. Units are shipped standard with copper tube/aluminum fin construction. See model number nomenclature for coil options. *Tin-Plated indoor coils are built with special hairpi ...

  • Bryant 574B - page 8

    — 8 — FIL TER ACCESS DOOR (HORIZONT AL APPLICA TION ONL Y .) DO NOT REMO VE FROM DO WNFLOW DISCHARGE. REPLACEMENT P ANEL HOLE FOR ECONOMIZER WIRING HARDNESS DOOR LA TCH ANGLE HINGED FIL TER ACCESS DOOR INST ALL FIL TER ACCESS DOOR STICKER ALUMINUM FIL TER RAINHOOD 17 13/32 (442mm) 16 1/4 ” (413mm) 11 13/32 ” (290mm) A99315 Filter Rack A9931 ...

  • Bryant 574B - page 9

    — 9 — BASE UNIT DIMENSIONS — 574B024-036 REQ ’ D CLEARANCES FOR OPERA TION AND SERVICING. in. (mm) Evaporator coil access side .................. 3 6 (914) P ower entry side (except for NEC requirements) ......... 3 6 (914) Unit top .......................... 4 8 (1219) Side opposite ducts ..................... 3 6 (914) Duct panel ........ ...

  • Bryant 574B - page 10

    — 10 — REQUIRED CLEARANCE FOR OPERA TION AND SERVICING in. [mm] EV AP . COIL ACCESS SIDE..............................................................36.00 [914.0] POWER ENTR Y SIDE ......................................................................36.00 [914.0] (EXCEPT FOR NEC REQUIREMENTS) UNIT T OP ........................................ ...

  • Bryant 574B - page 11

    — 11 — ACCESSORY DIMENSIONS C00076 Gasket around outer edge Insulated deck pan Gasket around duct S/A R/A HV A C unit base *Gasketing outer flange Flashing field supplied Roofing material field supplied Cant strip field supplied *Provided with roofcurb Roof Duct work field supplied Insulation (field supplied) Roofcurb* Wood nailer* Gasketing in ...

  • Bryant 574B - page 12

    — 12 — SELECTION PROCEDURE (WITH E XAMPLE) I DETERMINE COOLING AND HEATING REQUIREMENTS AT DESIGN CONDITIONS: Given: Required Cooling Capacity (TC)....................... 34,500 Btuh Sensible Heat Capacity (SHC)......................... 26,000 Btuh Required Heating Capacity............................... 60,000 Btuh Condenser Entering Air Tempe ...

  • Bryant 574B - page 13

    — 13 — PERFORMANCE DATA STANDARD INDOOR ECM MOTOR COOLING CAPACITIES 574B024 COOLING PERFORMANCE T ABLE T emp (F) Outdoor Air Entering Condenser Evaporator Air — CFM / BF 800/0.026 900/0.032 1000/0.04 Evaporator Air — Ewb (F) 62 63* 67 72 62 63* 67 72 62 63* 67 72 75 TC SHC kW 24.0 24.5 26.5 29.1 24.6 25.1 27.1 29.8 25.1 25.5 27.4 30.4 21.9 ...

  • Bryant 574B - page 14

    — 14 — PERFORMANCE DATA (cont) STANDARD INDOOR ECM MOTOR COOLING CAPACITIES (cont) See Legend and Notes on page 15. 574B036 COOLING PERFORMANCE T ABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air — CFM/BF 1100/0.06 1225/0.07 1400/0.08 Evaporator Air — Ewb (F) 62 63* 67 72 62 63* 67 72 62 63* 67 72 75 TC SHC kW 36.2 36.8 39.7 43.8 ...

  • Bryant 574B - page 15

    — 15 — PERFORMANCE DATA (cont) STANDARD INDOOR ECM MOTOR COOLING CAPACITIES (cont) 574B048 COOLING PERFORMANCE T ABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air — CFM/BF 1260/0.06 1400/0.06 1600/0.08 Evaporator Air — Ewb (F) 62 63* 67 72 62 63* 67 72 62 63* 67 72 75 TC SHC kW 45.0 45.8 49.6 54.7 46.7 47.3 51.2 56.3 48.1 48.7 52. ...

  • Bryant 574B - page 16

    — 16 — FIL TER SIZE CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 20 X 20 X 1 0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15 ————————— — — 20 X 24 X 1 —— — — 0.09 0.10 0.11 0.13 0.14 0.15 0.16 —————— — — 24 X 30 X 1 —— — — — — — 0.07 0.08 0.09 0 ...

  • Bryant 574B - page 17

    — 17 — 574B COOLING DRY COIL ECM AIRFLOW — SMALL CABINET 574B COOLING DRY COIL ECM AIRFLOW — LARGE CABINET 574B HEATING ECM AIRFLOW — SMALL CABINET 574B HEATING ECM AIRFLOW — LARGE CABINET UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC PRESSURE RANGE 0.0 – 0.39 0.4 – 0.69 0.7 – 1.0 0.0 – 0.39 0.4 – 0.69 ...

  • Bryant 574B - page 18

    — 18 — 574B ECM AIR FLOW VS. TEMPERATURE RISE CHART PERFORMANCE DATA (CONT) ECONOMIZER/1-IN. FIL TER PRESSURE DROP (in. wg) UNIT COOLING SIZE RA TED GAS INPUT RA TE (X 1000) AIRFLO W SETTING EAST SELECT ™ (SCFM) CALCULA TED TEMPERA TURE RISE MIN. TEMP RISE MAX TEMP RISE MAX DISCH. TEMP 574B 024 40 800 36.5 20 50 175 574B 030 40 800 36.5 20 50 ...

  • Bryant 574B - page 19

    — 19 — TYPICAL PIPING AND WIRING INDOOR THERMOST A T DISCONNECT PER NEC* FROM POWER SOURCE RETURN AIR T OP CO VER FROM GAS LINE *NEC - NA TIONAL ELECTRICAL CODE ROOF RETURN-AIR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BO X (FIELD-SUPPLIED) SUPPL Y -AIR FLEXIBLE DUCT ROOF-MOUNTING CURB C00022 C00023 ...

  • Bryant 574B - page 20

    — 20 — APPLICATION DATA Condensate trap — A 2-in. condensate trap must be fi eld supplied. Ductwork — Secure down fl ow discharge ductwork to roof curb . For horizontal discharge applications , attach ductwork to unit with fl anges. T o con vert a unit to down fl ow disc harge — Units are equipped with f actor y-installed inserts in t ...

  • Bryant 574B - page 21

    — 21 — C99024 ELECTRICAL DATA 574B (STANDARD) ELECTRICAL DATA UNIT SIZE 574B V -PH-Hz V O LTA G E RANGE COMPRESSOR OUTDOOR F AN M OTOR INDOOR F AN MO T OR PO WER SUPPL Y Min Max RLA LRA FLA FLA MCA MAX FUSE OR BKR 024 208/230 – 1 – 60 187 253 13.5 61.0 0.8 4.3 22.0/22.0 30/30 030 208/230 – 1 – 60 187 253 16.9 73.0 0.8 4.3 25.0/25.0 30/3 ...

  • Bryant 574B - page 22

    — 22 — TYPICAL WIRING SCHEMATIC — 208/230-1-60 SHOWN C01035 YEL BLK YEL BLU YEL YEL BLK BRN I BLK ...

  • Bryant 574B - page 23

    — 23 — TYPICAL WIRING SCHEMATIC — 208/230-3-60 SHOWN C99077 C03025 ...

  • Bryant 574B - page 24

    — 24 — OPERATING SEQUENCE Heating — On a call for heating, terminal “ W ” of the thermostat is energized, starting the induced-draft motor. When the hall- effect sensor on the induced-draft motor senses that it has reached the required speed, the burner sequence begins. This function is performed by the integrated gas control (IGC). The e ...

  • Bryant 574B - page 25

    — 25 — ...

  • Bryant 574B - page 26

    — 26 — ...

  • Bryant 574B - page 27

    — 27 — PACKAGED GAS HEATING/ELECTRIC COOLING UNITS CONSTANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONS SIZE RANGE: 2 TO 5 TONS, NOMINAL COOLING 40,000 TO 130,000 BTUH, NOMINAL HEATING INPUT BRYANT MODEL NUMBER: 574B PART 1 — GENERAL 1.01 SYSTEM DESCRIPTION Outdoor rooftop mounted, gas heating/electric cooling unit utilizing a scroll compres ...

  • Bryant 574B - page 28

    — 28 — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: NEW Form PDS 574B.24.1 © 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 PRINTED IN U.S.A. Catalog No. 5257-400 8-03 K. Electrical Requirements: All unit power wiring shall enter t ...

Manufacturer Bryant Category Gas Heater

Documents that we receive from a manufacturer of a Bryant 574B can be divided into several groups. They are, among others:
- Bryant technical drawings
- 574B manuals
- Bryant product data sheets
- information booklets
- or energy labels Bryant 574B
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bryant 574B.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bryant 574B, service manual, brief instructions and user manuals Bryant 574B. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bryant 574B.

Similar manuals

A complete manual for the device Bryant 574B, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bryant 574B by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bryant 574B.

A complete Bryant manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bryant 574B - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bryant 574B, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bryant 574B, that we can find in the current document
3. Tips how to use the basic functions of the device Bryant 574B - which should help us in our first steps of using Bryant 574B
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bryant 574B
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bryant 574B in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bryant 574B?

Use the form below

If you did not solve your problem by using a manual Bryant 574B, ask a question using the form below. If a user had a similar problem with Bryant 574B it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)