  • Carrier 012 - page 1

    Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS .................. 1 INST ALLA TION ............................ 1-16 Step 1 — Provide Unit Support .............. 1 • ROOF CURB • SLAB MOUNT Step 2 — Field Fabricate Ductwork ........... 1 Step 3 — Make Field Connection for Condensate Disposal .......... ...

  • Carrier 012 - page 2

    ROOF CURB ACCESSOR Y ‘ ‘A ’ ’ UNIT SIZE 50DJ901371 1 8 -2 9 50LJQ008,012 [356] 50DJ901381 2 8 -0 9 [610] UNIT SIZE ‘ ‘F’ ’ POWER ‘ ‘G’ ’ CONTROL CONNECTOR PKG. ACC. 50LJQ008,012 1 9 [25] NPT or 2 9 [51] NPT 3 ⁄ 4 9 [19] NPT 50DJ90131 1 NOTES: 1. Roof curb accessory is shipped unassembled. 2. Insulated panels: 25 mm (one in ...

  • Carrier 012 - page 3

    Step 3 — Make Field Connection for Conden- sate Disposal — Units must have an external trap added. See Fig. 3. A 3 ⁄ 4 -in. FPT connection is located on the side of the unit. Use a trap at least 100 mm (4 in.) deep, and protect against freeze-up. If drain line is run to a drain, pitch line away from unit at 25 mm (one in.) per 3 m (10 ft) of ...

  • Carrier 012 - page 4

    T able 1A — Physical Data (SI) BASE UNIT 50LJQ 008 012 NOMINAL CAP ACITY (kW) 23.2 28.8 OPERA TING WEIGHT (kg) Unit 381 426 With Economizer 401 446 Roof Curb 101 101 COMPRESSOR Hermetic Quantity 22 Oil (ml) (each compressor) 1627 2071 REFRIGERANT TYPE R-22 Operating Charge (kg) Circuit 1 3.7 4.0 Circuit 2 3.2 3.9 OUTDOOR F AN Propeller Quantity . ...

  • Carrier 012 - page 5

    T able 1B — Physical Data (English) BASE UNIT 50QJ 008 012 NOMINAL CAP ACITY (tons) 6.6 8.2 OPERA TING WEIGHT (lb) Unit 840 940 With Economizer 884 984 Roof Curb 223 223 COMPRESSOR Hermetic Quantity 22 Oil (fluid oz) (each compressor) 55 70 REFRIGERANT TYPE R-22 Operating Charge (lb-oz) Circuit 1 8-2 8-14 Circuit 2 7-0 8-10 OUTDOOR F AN Propelle ...

  • Carrier 012 - page 6

    UNIT 50LJQ STD. UNIT WEIGHT ECONOMIZER WEIGHT CORNER WEIGHT ‘ ‘A ’ ’ CORNER WEIGHT ‘ ‘B’ ’ CORNER WEIGHT ‘ ‘C’ ’ CORNER WEIGHT ‘ ‘D’ ’ ‘ ‘H’ ’ ‘‘J’ ’ ‘ ‘K’ ’ Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Ft-in. mm Ft-in. mm Ft-in. mm 008 840 381 44 20 182 83 156 71 231 105 271 123 2-0 7 ⁄ 8 632 3-5 5 ...

  • Carrier 012 - page 7

    Step 5 — Make Electrical Connections Unit cabinet must have uninterrupted, unbroken elec- trical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for elec- trical ground when installed in ac ...

  • Carrier 012 - page 8

    Fig. 8 — Electric Heater Power Wiring Connections — 50LJQ, 400-3-50; Single Point Kit 50DJ902041 and 50DJ902101 Fig. 9 — Electric Heater Power Wiring Connections — 50LJQ, 400-3-50; Single Point Kit 50DJ902061 and 50DJ902121 8 ...

  • Carrier 012 - page 9

    Fig. 10 — Electric Heater Power Wiring Connections — 50LJQ, 220-3-50; Single Point Kit 50DJ902031 and 50DJ902081 Fig. 1 1 — Electric Heater Wiring Connections — 50LJQ, 220-3-50; Single Point Kit 50DJ902051 and 50DJ9021 1 1 LEGEND FOR FIG. 7-13 EQUIP — Equipment FU — Fuse GND — Ground HTR — Heater TB — T erminal Block 9 ...

  • Carrier 012 - page 10

    Fig. 12 — Electric Heater Power Wiring Connections — 50LJQ, 220-3-50; Single Point Kit 50DJ902091 Fig. 13 — Electric Heater Power Wiring Connections — 50LJQ, 220-3-50; Single Point Kit 50DJ902131 LEGEND FOR FIG. 7-13 EQUIP — Equipment FU — Fuse GND — Ground HTR — Heater TB — T erminal Block 10 ...

  • Carrier 012 - page 11

    T able 2 — Electrical Data UNIT 50LJQ NOMINAL V -PH-HZ VOL T AGE RANGE COMPR (each) OFM IFM ELECTRIC HEA T POWER SUPPL Y ELECTRIC HEA T POWER WIRING FIG. NO. ELECTRIC HEA T P ART NO. 50DJ901— Min Max RLA LRA FLA Hp FLA Nominal kW* FLA MCA MOCP† 008 220-3-50 198 242 15.3 82.0 1.5 1.5 5.8 — — 41.7 50 — — 9.5 24.7 70.3 80 10 71 1 14.6 38 ...

  • Carrier 012 - page 12

    FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation in- structions included with the accessory . Locate thermostat as- sembly on a solid wall in the conditioned space to sense av- erage temperature in accordance with thermostat installation instructions. Route thermostat cable or equivalent si ...

  • Carrier 012 - page 13

    Step 6 — Adjust Indoor-Fan Speed — Adjust in- door fan speed to meet jobsite conditions. For units with electric resistance heating, required mini- mum L/s (cfm) is 1062 (2250) for 50LJQ008 and 1416 (3000) or 50LJQ012, with the following exceptions. UNIT 50LJQ UNIT VOL T AGE HEA TER kW UNIT CONFIG- URA TION REQUIRED MINIMUM L/s Cfm 012 220 50.0 ...

  • Carrier 012 - page 14

    MOTOR MOUNTING NUTS AND BOLTS Fig. 18 — Belt-Drive Motor Mounting T able 5A — Fan R/s at Motor Pulley Settings (SI) 50LJQ MOTOR PULLEY TURNS OPEN 0 1 ⁄ 2 11 1 ⁄ 2 22 1 ⁄ 2 33 1 ⁄ 2 44 1 ⁄ 2 5 008 14.70 14.26 13.82 13.38 12.94 12.50 12.06 1 1.62 1 1.18 10.74 10.30 012 15.00 14.65 14.30 13.95 13.60 13.25 12.90 12.55 12.20 1 1.85 1 1.50 ...

  • Carrier 012 - page 15

    T able 6 — Fan Performance (SI), 50LJQ008 (50 Hz) — Horizontal Discharge Units AIRFLOW (L/s) EXTERNAL ST A TIC PRESSURE (Pa) 50 100 150 200 250 300 350 400 450 500 r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW 1 100 7.9 0.35 9.4 0.50 10.6 0.68 1 1.7 0.85 12.7 1.03 13.6 1.25 14.4 1.46 14.9 1.69 15.1 1.92 15.0 2. ...

  • Carrier 012 - page 16

    T able 10 — Fan Performance (English), 50LJQ008 (50 Hz) — Horizontal Discharge Units AIRFLOW (Cfm) EXTERNAL ST A TIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2200 459 0.42 549 0.62 625 0.83 691 1.06 753 1.31 805 1.58 842 1.87 857 2.16 851 2.45 823 2 ...

  • Carrier 012 - page 17

    ST ART -UP IMPOR T ANT : Ener gize crankcase heaters 24 hours prior to base unit start-up to remove entrapped refrigerant from the oil. Heaters are energized as long as there is power to the unit. Unit Preparation — Make sure that unit has been in- stalled in accordance with these installation instructions and applicable codes. Return-Air Filters ...

  • Carrier 012 - page 18

    NOTES: 1. In heating mode, economizer damper blade will move to the mini- mum position, and unit will operate as described for units without economizer , regardless of outdoor air temperature. 2. The temperatures given in the graph are for demonstration pur- poses only and may vary depending on which thermostat is used. LEGEND C— Contactor HC — ...

  • Carrier 012 - page 19

    position of the reversing valves and shuts of f the outdoor fan. The electric heaters (if installed) will be ener gized. On units with economizer , the economizer damper blade will move to the fully closed position. The unit continues to defrost until the coil temperature as measured by DFT2 reaches 65 F or the duration of defrost cycle completes a ...

  • Carrier 012 - page 20

    CONDENSA TE DRAIN — Check and clean each year at start of cooling season. In winter , keep drain dry or protect against freeze-up. FIL TERS — Clean or replace at start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be same dimensions as original filters. OUTDOOR-AIR INLET SCREENS ...

  • Carrier 012 - page 21

    Fig. 25 — Cooling Charging Charts, 50LJQ008 Fig. 26 — Cooling Charging Charts, 50LJQ012 21 ...

  • Carrier 012 - page 22

    ...

  • Carrier 012 - page 23

    ...

  • Carrier 012 - page 24

    Copyright 1992 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 015-015 Printed in U.S.A. Form 50LJQ-C1SI Pg 24 1-92 Replaces: New ...

Manufacturer Carrier Category Heat Pump

Documents that we receive from a manufacturer of a Carrier 012 can be divided into several groups. They are, among others:
- Carrier technical drawings
- 012 manuals
- Carrier product data sheets
- information booklets
- or energy labels Carrier 012
All of them are important, but the most important information from the point of view of use of the device are in the user manual Carrier 012.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Carrier 012, service manual, brief instructions and user manuals Carrier 012. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Carrier 012.

Similar manuals

A complete manual for the device Carrier 012, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Carrier 012 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Carrier 012.

A complete Carrier manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Carrier 012 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Carrier 012, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Carrier 012, that we can find in the current document
3. Tips how to use the basic functions of the device Carrier 012 - which should help us in our first steps of using Carrier 012
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Carrier 012
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Carrier 012 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Carrier 012?

Use the form below

If you did not solve your problem by using a manual Carrier 012, ask a question using the form below. If a user had a similar problem with Carrier 012 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)