    Johnson Controls Unitary Produ cts 1031452-UIM-B-0513 R-22 OUTDOOR SPLIT -SYSTEM AIR CONDITIONING SHIPPED WITH NITROGEN CHARGE ONL Y MODELS: 13 SEER - GC GD 1.5 TO 5 T ONS INSTALLATION MANUAL ® LIST OF SECTIONS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SAFETY . . . . . . . . . . . . . . . ...

  • Johnson Controls 13 SEER - GCGD - page 2

    1031452-UIM-B-0513 2 Johnson Controls Unitary Products LIMIT A TIONS The unit should be installed in accordance with all National, S tate and Local Safety Codes and the limitations listed below: 1. Limitations for the indoor unit, coil, and appropriate accessories must also be observed. 2. The outdoor unit must not be installed with any duct work i ...

  • Johnson Controls 13 SEER - GCGD - page 3

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 3 LIQUID LINE FIL TER-DRIER The air conditioning unit’s copper spun filter/dryer is located on the liq - uid line. PIPING CONNECTIONS The outdoor condensing unit must be connected to the indoor evapora - tor coil using field supplied r efrigerant grade (ACR) co pper tubing that is internally c ...

  • Johnson Controls 13 SEER - GCGD - page 4

    1031452-UIM-B-0513 4 Johnson Controls Unitary Products Connect the refrigerant lines u sing the following proced ure: 1. Remove the cap and Schrader core from both the liquid and vapor service valve service ports at the outdoor unit. Connect low pres- sure nitrogen to the liquid line service port. 2. Braze the liquid line to the liqui d valve at th ...

  • Johnson Controls 13 SEER - GCGD - page 5

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 5 SECTION V : TXV INST ALLA TIONS The following are the basic steps fo r inst allation. For detailed instruc- tions, refer to the Installation Instructions accompanying the TXV kit. Install TXV kit as follows: 1. Relieve the holding charge by pulling off the rubber cap plug on the suction manifo ...

  • Johnson Controls 13 SEER - GCGD - page 6

    1031452-UIM-B-0513 6 Johnson Controls Unitary Products SUPERHEA T CHARGING METHOD - PIST ON INDOOR 1. Operate system until temperatures and pressures stabilize (mini- mum of 10 minutes). 2. Measure and record indoor wet bulb (WB) temperature using a sling psychrometer and the outdoor dry bulb (DB) temperature using a thermometer . 3. Measure and re ...

  • Johnson Controls 13 SEER - GCGD - page 7

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 7 FIELD CONNECTIONS CONTR OL WIRING 1. Route low voltage wiring into bottom of control box as shown in Figure 6. Make low voltage wiring conne ctions inside the low volt- age box per Figures 7 - 1 1. 2. The complete connection diagram and schematic wiring label is located on the inside surface o ...

  • Johnson Controls 13 SEER - GCGD - page 8

    1031452-UIM-B-0513 8 Johnson Controls Unitary Products For additional connection diagrams for a ll UPG equipment refer to “Low V oltage System Wiring” document available online at www . upgnet.com in the Product Catalog Section. FIGURE 8: Thermostat Chart - Single S tage AC with PSC Air Handler AC 1A Single Stage Air Conditioner – PSC Air Han ...

  • Johnson Controls 13 SEER - GCGD - page 9

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 9 FIGURE 9: Thermostat Chart - Single S tage AC with PSC Air Handler AC 1B Single Stage Air Conditioner – PSC Air Handler C 24 – Volt Comm on Y Compressor Contactor SINGLE STAGE AIR CONDIT IONER MA SHP AHP ID MODELS SINGLE STAGE AIR CONDIT I O N ER Other Part Nu mbers: SAP = Legacy 265902 = ...

  • Johnson Controls 13 SEER - GCGD - page 10

    1031452-UIM-B-0513 10 Johnson Controls Unitary Products FIGURE 10: Thermostat Chart - Single S tage AC with PSC Furnace AC 5A Single Stage Air Conditioner – Single Stage PSC Furnace G*9F G*(8/9)S F*(8/9) S PS(8/9) GF(8/9) G8C L*8S C 24 – Volt Comm on R 24 – Volt Hot W Full Stage Heat Y / Y2 Second or Full Stage Compressor SINGLE STAGE PSC FUR ...

  • Johnson Controls 13 SEER - GCGD - page 11

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 11 FIGURE 1 1: Thermostat Chart - Single S tage AC with PSC Furnace AC 5B Single Stage Air Conditioner – Single Stage PSC Furnace C 24 – Volt Comm on Y Compressor Contactor SINGLE STAGE AIR CONDIT IONER SINGLE STAGE AIR CONDIT I O N ER Y Full Stage Compressor G Fan *BP11C50124 *BN11C01124 *D ...

  • Johnson Controls 13 SEER - GCGD - page 12

    1031452-UIM-B-0513 12 Johnson Controls Unitary Products SECTION IX: INSTRUCTING THE O WNER Assist owner with processing warr anty cards and/or online registration. Review Owners Guide and provide a copy to the owner and guidance on proper operation and maintenance. I nstruct the owner or the opera- tor how to start, stop and adjust temperature sett ...

  • Johnson Controls 13 SEER - GCGD - page 13

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 13 SECTION X: WIRING DIAGRAM FIGURE 12: Wiring Diagram ...

  • Johnson Controls 13 SEER - GCGD - page 14

    1031452-UIM-B-0513 14 Johnson Controls Unitary Products NOTES ...

  • Johnson Controls 13 SEER - GCGD - page 15

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 15 SECTION XI: ST ART UP SHEET Air Conditioning and Heating Start-Up Sheet Proper start-up is critical to customer comfort and equipment longevity Name Address City State or Province Zip or Postal Code Indoor Unit Model # Indoor Unit Serial # Indoor Coil Model # Indoor Coil Serial # Upflow Downf ...

  • Johnson Controls 13 SEER - GCGD - page 16

    Subject to change without not ice. Published in U.S.A. 1031452-UIM-B-0513 Copyright © 2013 by Johnson Controls, Inc. All rights reserved. Supersedes: 1031452-UIM-A-0413 Y ork Internat ional Corp. 5005 Y ork Driv e Norman, OK 73069 Supply static after indoor coil (in w.c.") Return Static (in w.c.") before filter Total External Static Pres ...

Manufacturer Johnson Controls Category Air Conditioner

Documents that we receive from a manufacturer of a Johnson Controls 13 SEER - GCGD can be divided into several groups. They are, among others:
- Johnson Controls technical drawings
- 13 SEER - GCGD manuals
- Johnson Controls product data sheets
- information booklets
- or energy labels Johnson Controls 13 SEER - GCGD
All of them are important, but the most important information from the point of view of use of the device are in the user manual Johnson Controls 13 SEER - GCGD.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Johnson Controls 13 SEER - GCGD, service manual, brief instructions and user manuals Johnson Controls 13 SEER - GCGD. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Johnson Controls 13 SEER - GCGD.

A complete manual for the device Johnson Controls 13 SEER - GCGD, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Johnson Controls 13 SEER - GCGD by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Johnson Controls 13 SEER - GCGD.

A complete Johnson Controls manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Johnson Controls 13 SEER - GCGD - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Johnson Controls 13 SEER - GCGD, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Johnson Controls 13 SEER - GCGD, that we can find in the current document
3. Tips how to use the basic functions of the device Johnson Controls 13 SEER - GCGD - which should help us in our first steps of using Johnson Controls 13 SEER - GCGD
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Johnson Controls 13 SEER - GCGD
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Johnson Controls 13 SEER - GCGD in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Johnson Controls 13 SEER - GCGD?

Use the form below

If you did not solve your problem by using a manual Johnson Controls 13 SEER - GCGD, ask a question using the form below. If a user had a similar problem with Johnson Controls 13 SEER - GCGD it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)