    Form No. PDS 561C.18.6 ELECTRIC AIR CONDITIONER 561C (60 Hz) Sizes 018 thru 060 Model 561C Energy-Efficient Air Conditioners incor porate inno- vativ e technology to provide reliab le summer cooling perfor- mance. Built into these units are the f eatures most desired by homeowners toda y including SEER ratings of up to 11.5 when used with componen ...

  • Bryant 561C - page 2

    —2— DIMENSIONS—561C A97017 AIR IN NOTES: 1. Allow 30 in. clearance to service side of unit, 48 in. above unit, 6 in. on one side, 12 in.  on remaining side, and 24 in. between units for proper airflow. 2. Minimum outdoor operating ambient in cooling mode is 55 ° F, max. 125 ° F. 3. Series designation is the 14th position of t ...

  • Bryant 561C - page 3

    —3— CHECK-FLO-RA TER® PIST ON CHART * Piston listed is f or any approv ed coil non-capillar y tube combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil. RECOMMENDED TUBE DIAMETERS * For tube sets betw een 50 and 175 ft, consult Residential Split System Long-Line Application Guideline. SOUND PO WER ...

  • Bryant 561C - page 4

    —4— SPECIFICA TIONS See notes on page 7. UNIT SIZE-SERIES 561C018-A, D 561C024-A, D 561C030-A, D 561C030-A Operating W eight (Lb) 113/115 115/117 124/133 124 ELECTRICAL Unit V olts—Hertz—Phase 208-230—60—1 208/230—60—3 Operating V oltage Range* 197—253 187—253 Compressor— Rated Load Amps 9.6/9.0 10.7/11.6 14.2/14.8 9.4 Lock ed ...

  • Bryant 561C - page 5

    —5— SPECIFICA TIONS Continued See notes on page 7. UNIT SIZE-SERIES 561C036-A, B, E 561C036-B, D 561C036-B 561C042-A, B 561C042-B, C 561C042-B Operating W eight (Lb) 129/138/138 129/133 133 138/142 142 ELECTRICAL Unit V olts—Hertz—Phase 208-230—60—1 208/230—60—3 460—60—3 208-230—60—1 208/230—60—3 460—60—3 Operating V ...

  • Bryant 561C - page 6

    —6— SPECIFICA TIONS Continued See notes on page 7. UNIT SIZE-SERIES 561C048-A, B 561C048-B, C 561C060-A, B 561C060-B, E Operating W eight (Lb) 192/198 233/218 ELECTRICAL Unit V olts—Hertz—Phase 208-230—60—1 208/230—60—3 460—60—3 208-230—60—1 208/230—60—3 460—60—3 Operating V oltage Range* 197—253 187—253 414—50 ...

  • Bryant 561C - page 7

    —7— * P er missible limits of the v oltage range at which unit will operate satisf actor ily . Oper ation outside these limits may result in unit f ailure. † If wire is applied at ambient greater than 30°C (86°F), consult T able 310-16 of the NEC (ANSI/NFP A 70). The ampacity of nonmetallic-sheathed cable (NM), trade name R OMEX, shall be t ...

  • Bryant 561C - page 8

    —8— A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 9. High-Pressure Switch Auto reset SPST s witch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to 400 ± 10 psig and resets at 298 ± 20 psig. Provides protection against compressor damage due to l ...

  • Bryant 561C - page 9

    —9— COMBINA TION RA TINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 018-A, D CC5A/CD5AA018* 17,200 NONE — 10.00 10.00 9.20 CC5A/CD5AA024 17,600 NONE 10.00 10.50 10.50 9.45 CC5A/CD5A W024 17,600 N ...

  • Bryant 561C - page 10

    —10— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 030-A, D CD5A/CD5AA030* 28,000 NONE 10.00 10.10 10.10 9.10 CC5A/CD5AA036 29,000 NONE 10.00 10.10 10.10 9.30 CC5A/CD5A ...

  • Bryant 561C - page 11

    —11— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 036-A, B, D , E CK3BA036 33,800 NONE 10.00 10.20 10.20 9.20 CK3BA042 33,800 NONE 10.00 10.20 10.20 9.20 CK5A/CK5BA036 ...

  • Bryant 561C - page 12

    —12— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 036-A, B, D , E CK5A/CK5BA042 33,400 TDR 10.80 — 10.80 10.00 CK5A/CK5BT042 33,400 TDR 10.80 — 10.80 10.00 CK5A/CK5 ...

  • Bryant 561C - page 13

    —13— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 042-A, B, C COILS + 355MA V060100 V ARIABLE-SPEED FURNACE CC5A/CD5AA042 40,000 TDR 10.50 — 10.50 9.45 CC5A/CD5AC048 ...

  • Bryant 561C - page 14

    —14— COMBINA TION RA TINGS Continued * T ested Combination. † In most cases, only 1 method should be used to achie v e TDR function. Using more than 1 method in a system ma y cause degradation in performance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a furnace equipped with TDR. All Br yant furnaces are equipped with TDR exc ...

  • Bryant 561C - page 15

    —15— DET AILED COOLING CAP A CITIES* See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys K ...

  • Bryant 561C - page 16

    —16— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ...

  • Bryant 561C - page 17

    —17— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ...

  • Bryant 561C - page 18

    —18— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ...

  • Bryant 561C - page 19

    —19— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ...

  • Bryant 561C - page 20

    —20— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ...

  • Bryant 561C - page 21

    —21— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ...

  • Bryant 561C - page 22

    —22— DETAILED COOLING CAPACITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ota ...

  • Bryant 561C - page 23

    —23— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ...

  • Bryant 561C - page 24

    —24— DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity ma y occur . † T otal and sensible capacities are net capacities . B ...

  • Bryant 561C - page 25

    —25— CONDENSER ONL Y RA TINGS* See notes on page 26. SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 65 75 85 95 105 115 125 561C018-A, D 30 TCG 17.6 16.2 14.7 13.4 12.0 10.7 9.52 8.35 KW 1.37 1.49 1.58 1.66 1.73 1.77 1.80 1.82 SDT 75.6 86.1 96.4 106.0 116.0 126.0 136.0 146.0 35 TCG 19.6 18.1 16.6 15.1 13.6 12.3 10.9 9.68 KW 1.40 1.52 1.63 ...

  • Bryant 561C - page 26

    —26— CONDENSER ONL Y RA TINGS* Continued * ARI listing applies only to systems shown in Ratings and P erformance table . KW — T otal Po wer (Kw) SDT — Saturated T emperature Leaving Compressor (°F) SST — Saturated T emperature Entering Compressor (°F) TCG — Gross Cooling Capacity (1000 Btuh) SST °F CONDENSER ENTERING AIR TEMPERA TURE ...

  • Bryant 561C - page 27

    —27— SYSTEM DESIGN 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature without lo w-ambient operation accessor y is 55°F (12.8°C). 3. Maximum outdoor operating air temperature is 125°F (51.7°C). 4. For reli ...

  • Bryant 561C - page 28

    —2 8— SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels PDS 561C.18.5 © 1999 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 PRINTED IN U.S.A. Catalog No. 5256-108 11-99 GUIDE SPECIFICA TIONS GENERAL System Description Outdoor-mounted, air-coo ...

Manufacturer Bryant Category Air Conditioner

Documents that we receive from a manufacturer of a Bryant 561C can be divided into several groups. They are, among others:
- Bryant technical drawings
- 561C manuals
- Bryant product data sheets
- information booklets
- or energy labels Bryant 561C
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bryant 561C.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bryant 561C, service manual, brief instructions and user manuals Bryant 561C. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bryant 561C.

Similar manuals

A complete manual for the device Bryant 561C, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bryant 561C by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bryant 561C.

A complete Bryant manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bryant 561C - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bryant 561C, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bryant 561C, that we can find in the current document
3. Tips how to use the basic functions of the device Bryant 561C - which should help us in our first steps of using Bryant 561C
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bryant 561C
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bryant 561C in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bryant 561C?

Use the form below

If you did not solve your problem by using a manual Bryant 561C, ask a question using the form below. If a user had a similar problem with Bryant 561C it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)