    Form No. PDS 552A.18.3 DELUXE 12 SEER AIR CONDITIONER WITH PURON ® REFRIGERANT 552A (60 Hz) Sizes 018 thru 060 Br yant’ s Quantum Plus 552A with Puron® refr igerant provides f eatures which cannot be matched by any other family of equip- ment. The 552A is a Quantum Plus air conditioning system uti- lizing Br yant’ s unique Puron refr igerant. ...

  • Bryant 552A - page 2

    — 2 — DIMENSIONS AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW. 2. MINIMUM OUTDOOR OPERATING AMBIENT IN CO ...

  • Bryant 552A - page 3

    — 3 — RECOMMENDED TUBE DIAMETERS * For tube sets g reater than 50 ft and/or 20 ft vertical differential, consult Application Guideline and Service Manual — Air Conditioners and Heat Pumps Using Puron ® Refrigerant. CHECK-FLO-RA TER ® PISTON * Piston listed is for any appro ved non-capillary tube coil combina- tion. Piston is shipped with ou ...

  • Bryant 552A - page 4

    — 4 — SPECIFICA TIONS See notes on page 5. UNIT SIZE-SERIES 018-F 024-F/G 030-F 036-F/G Operating W eight (Lb) 168 209 209 212 ELECTRICAL Unit V olts — Her tz — Phase 208/230 — 60 — 1 Operating V oltage Range* 187 — 253 Compressor — Rated Load Amps 10.3 13.5/12.8 14.7 16.7/15.4 Lock ed Rotor Amps 51.0 61.0/60.0 72.5 87.5/83.0 Conden ...

  • Bryant 552A - page 5

    — 5 — SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will oper ate satisf actor ily . Operation outside these limits ma y resu lt in unit f ailure. † If wire is applied at ambient g reater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70). The ampacity of nonmetallic-sheathed ca ...

  • Bryant 552A - page 6

    — 6 — A CCESSOR Y USA GE GUIDELINE * For tubing line sets g reater than 50 ft and/or 20 ft ver tical differential, ref er to Application Guideline and Ser vice Manual — Air Conditioning and Heat Pumps Using Puron ® Refrigerant. † Only when low-pressure s witch is used. ‡ Required for lo w-ambient controller (full modulation feature) and ...

  • Bryant 552A - page 7

    — 7 — A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Contin ued 10. Low-Ambient Pressure Switc h A long life pressure s witch which is mounted to outdoor unit service valve . It is designed to cycle the outdoor f an motor in order to maintain head pressure within normal operating limits (approximately 200 psig to 365 psig). The cont ...

  • Bryant 552A - page 8

    — 8 — COMBINATION RATINGS UNIT SIZE-SERIES INDOOR UNIT TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV ‡ 018-F *CK5A/CK5BA024 17,500 NONE — 12.00 12.00 10.80 CC5A/CD5AA018 17,200 NONE — 11.50 11.50 10.45 CC5A/CD5AA024 17,500 NONE — 12.00 12.00 10.70 ...

  • Bryant 552A - page 9

    — 9 — 024-F CK5A/CK5BW030 23,200 TDR 13.00 — 13.00 11.20 CK5P A024 23,000 TDR&TXV 12.50 —— 11.10 CK5P A030 23,200 TDR&TXV 13.00 —— 11.20 CK5PW024 23,000 TDR&TXV 12.50 —— 11.10 CK5PW030 23,200 TDR&TXV 13.00 —— 11.20 COILS + 355MA V042040 V ARIABLE-SPEED FURNACE CC5A/CD5A W030 23,200 TDR 13.00 — 13.00 11.05 CK5 ...

  • Bryant 552A - page 10

    — 10 — 024-G CE3AA030 22,600 TDR 13.00 — 13.00 11.80 CK3BA024 22,200 TDR 13.00 — 13.00 11.85 CK3BA030 22,600 TDR 13.00 — 13.00 11.90 CK5A/CK5BA024 22,200 TDR 13.00 — 13.00 11.70 CK5A/CK5BA030 22,600 TDR 13.00 — 13.00 11.80 CK5A/CK5BW024 22,200 TDR 13.00 — 13.00 11.75 CK5A/CK5BW030 22,600 TDR 13.00 — 13.00 11.85 CK5P A024 22,200 TD ...

  • Bryant 552A - page 11

    — 11 — 024-G CK5A/CK5BW030 22,600 TDR 13.00 — 13.00 11.80 CK5PW024 22,200 TDR&TXV 13.00 —— 11.65 CK5PW030 22,600 TDR&TXV 13.00 —— 11.75 COILS + 315(A,J)A V060120 V ARIABLE-SPEED FURNA CE CE3AA024 22,200 TDR 13.00 — 13.00 11.45 CE3AA030 22,600 TDR 13.00 — 13.00 11.70 030-F *CK5A/CK5BA036 29,000 NONE — 12.00 12.00 10.65 CC ...

  • Bryant 552A - page 12

    — 12 — 030-F CK5PW036 29,000 TDR&TXV 13.00 —— 11.60 COILS + 355MA V042060 V ARIABLE-SPEED FURNACE CC5A/CD5AA036 29,000 TDR 13.00 — 13.00 11.25 CC5A/CD5A W030 28,000 TDR 12.50 — 12.50 10.80 CK3BA030 28,000 TDR 12.50 — 12.50 10.85 CK3BA036 29,000 TDR 13.00 — 13.00 11.30 CK5A/CK5BA036 29,000 TDR 13.00 — 13.00 11.30 CK5A/CK5BW030 ...

  • Bryant 552A - page 13

    — 13 — 036-F , G CK5A/CK5BT036 34,600 TDR 12.50 — 12.50 11.15 CK5P A036 34,600 TDR&TXV 12.50 —— 11.15 CK5PE042 34,600 TDR&TXV 12.50 —— 11.25 CK5PT036 34,600 TDR&TXV 12.50 —— 11.15 COILS + 315(A,J)A V048090 V ARIABLE-SPEED FURNA CE CC5A/CD5AA036 34,600 TDR 12.50 — 12.50 11.30 CC5A/CD5AA042 34,600 TDR 13.00 — 13.00 1 ...

  • Bryant 552A - page 14

    — 14 — 036-F , G CK3BA042 34,600 TDR 12.50 — 12.50 11.20 CK5A/CK5BA036 34,600 TDR 12.50 — 12.50 11.15 CK5P A036 34,600 TDR&TXV 12.50 —— 11.15 COILS + 355MA V042080 V ARIABLE-SPEED FURNACE CC5A/CD5AA042 34,600 TDR 12.50 — 12.50 11.25 CC5A/CD5A W036 34,600 TDR 12.50 — 12.50 11.20 CK3BA042 34,600 TDR 12.50 — 12.50 11.25 CK5A/CK5B ...

  • Bryant 552A - page 15

    — 15 — 042-F CK5P A042 39,000 TDR&TXV 12.50 —— 10.85 CK5P A048 39,500 TDR&TXV 12.50 —— 10.95 CK5PE042 39,500 TDR&TXV 12.50 —— 10.90 CK5PT042 39,000 TDR&TXV 12.50 —— 10.85 CK5PT048 39,500 TDR&TXV 12.50 —— 10.95 COILS + 315(A,J)A V066110 V ARIABLE-SPEED FURNA CE CC5A/CD5AA042 39,000 TDR 12.50 — 12.50 10.9 ...

  • Bryant 552A - page 16

    — 16 — 042-F CC5A/CD5A C048 39,000 TDR 12.50 — 12.50 10.65 CD5AA048 39,500 TDR 12.50 — 12.50 10.80 CK3BA042 39,000 TDR 12.50 — 12.50 10.75 CK3BA048 39,500 TDR 12.50 — 12.50 10.85 CK5A/CK5BA042 39,000 TDR 12.50 — 12.50 10.75 CK5A/CK5BA048 39,500 TDR 12.50 — 12.50 10.85 CK5P A042 39,000 TDR&TXV 12.50 —— 10.75 CK5P A048 39,500 ...

  • Bryant 552A - page 17

    — 17 — 048-F CK5P A048 44,500 TDR&TXV 12.00 —— 10.60 CK5PT048 44,500 TDR&TXV 12.00 —— 10.60 COILS + 315(A,J)A V066110 V ARIABLE-SPEED FURNA CE CC5A/CD5AA060 45,000 TDR 12.50 — 12.50 10.85 CC5A/CD5A C048 44,000 TDR 12.00 — 12.00 10.70 CC5A/CD5A W048 44,500 TDR 12.50 — 12.50 10.80 CD5AA048 44,500 TDR 12.00 — 12.00 10.80 CD ...

  • Bryant 552A - page 18

    — 18 — 048-F CK5PX060 46,000 TDR&TXV 12.00 —— 10.70 COILS + 355MA V060100 V ARIABLE-SPEED FURNACE CC5A/CD5AA060 44,500 TDR 12.00 — 12.00 10.55 CC5A/CD5A C048 44,000 TDR 12.00 — 12.00 10.40 CC5A/CD5A W060 45,500 TDR 12.50 — 12.50 10.85 CD5AA048 44,500 TDR 12.00 — 12.00 10.55 CK3BA048 44,500 TDR 12.00 — 12.00 10.60 CK3BA060 45,0 ...

  • Bryant 552A - page 19

    — 19 — * T ested combination. † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system may cause deg radation in perf or mance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a furnace equipped with TDR. Most Br yant furnaces are equipped with TDR. ‡ TXV must be Puron ® compa ...

  • Bryant 552A - page 20

    — 20 — DET AILED COOLING CAP A CITIES* See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys ...

  • Bryant 552A - page 21

    — 21 — DET AILED COOLING CAP A CITIES* continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 22

    — 22 — DET AILED COOLING CAP A CITIES* continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 23

    — 23 — DET AILED COOLING CAP A CITIES* continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 24

    — 24 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 25

    — 25 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 26

    — 26 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 27

    — 27 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 28

    — 28 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 29

    — 29 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 30

    — 30 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 31

    — 31 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 32

    — 32 — DET AILED COOLING CAP A CITIES* Continued NO TE: When the required data fall between the pub lished data, inter polation may be perf or med. Extrapolation is not an acceptable pr actice. * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length and/o ...

  • Bryant 552A - page 33

    — 33 — CONDENSER ONL Y RA TINGS* See notes on page 35. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 552AN018-F 30 TCG 16.0 15.1 14.3 13.4 12.4 11.5 10.5 9.50 SDT 67.7 77.4 87.0 96.7 106.4 116.1 125.8 135.2 KW 0.80 0.92 1.06 1.21 1.38 1.56 1.76 1.97 35 TCG 17.6 16.6 15.7 14.8 13.8 12.8 11.7 10.6 SDT 68.7 78.3 88. ...

  • Bryant 552A - page 34

    — 34 — CONDENSER ONL Y RA TINGS* Continued See notes on page 35. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 552AN030-F 30 TCG SDT KW 26.7 71.2 1.41 25.3 80.9 1.59 23.8 90.6 1.80 22.4 100. 2.04 21.0 110. 2.30 19.5 120. 2.59 18.0 129. 2.91 16.4 139. 3.26 35 TCG SDT KW 29.3 72.5 1.42 27.8 82.1 1.60 26.2 91.8 1.81 ...

  • Bryant 552A - page 35

    — 35 — SYSTEM DESIGN SUMMAR Y 1. Intended f or outdoor installation with free air inlet and outlet. Outdoor fan e xter nal static pressure availab le is less than 0.01-in. wc. 2. Minimum outdoor oper ating air temperature without low-ambient oper ation accessor y is 55 ° F (12.8 ° C). 3. Maximum outdoor oper ating air temperature is 125 ° F ...

  • Bryant 552A - page 36

    SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 552A.18.2 New: PDS 552A.18.3 © 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 — 36 — PRINTED IN U.S.A. Catalog No. 5255-206 10-03 GUIDE SPECIFICATIONS GENERAL System Description Outdoo ...

Manufacturer Bryant Category Air Conditioner

Documents that we receive from a manufacturer of a Bryant 552A can be divided into several groups. They are, among others:
- Bryant technical drawings
- 552A manuals
- Bryant product data sheets
- information booklets
- or energy labels Bryant 552A
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bryant 552A.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bryant 552A, service manual, brief instructions and user manuals Bryant 552A. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bryant 552A.

Similar manuals

A complete manual for the device Bryant 552A, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bryant 552A by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bryant 552A.

A complete Bryant manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bryant 552A - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bryant 552A, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bryant 552A, that we can find in the current document
3. Tips how to use the basic functions of the device Bryant 552A - which should help us in our first steps of using Bryant 552A
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bryant 552A
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bryant 552A in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bryant 552A?

Use the form below

If you did not solve your problem by using a manual Bryant 552A, ask a question using the form below. If a user had a similar problem with Bryant 552A it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)