    Reference Manual 00809-0100-4860, Rev BC January 2013 R osemount 8600D Series V or tex Flo wmeter ...

  • Emerson 8600 - page 2

    Reference Manual 00809-0100-4860, Rev BC January 2013 www .emersonprocess.com/rosemount ...

  • Emerson 8600 - page 3

    Reference Manual 00809-0100-4860, Rev BC Title Page January 2013 i R osemount 8600D Smar t V or tex Flowmeter NO TICE R ead this manu al bef ore working with the produc t. For pe rsonal and system sa fety , and for optimum produc t per formance , mak e sure you thorou ghly underst and the conte nts before installing, using, or maintain ing this pro ...

  • Emerson 8600 - page 4

    ii Reference Manu al 00809-0100-4860, Rev BC Title Page January 2013 ...

  • Emerson 8600 - page 5

    iii Reference Manu al 00809-0100-4860, Rev BC Table of Contents January 2013 Ta b l e o f C o n t e n t s 1 Section 1: Introduction 1.1 How to use this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson 8600 - page 6

    iv Reference Manu al 00809-0100-4860, Rev BC Table of Contents January 2013 T a ble of Cont ents 2.8.1 Installing th e Transient Protector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 3 Section 3: Configur ation 3.1 Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson 8600 - page 7

    v Reference Manu al 00809-0100-4860, Rev BC Table of Contents January 2013 Ta b l e o f C o n t e n t s 5 Section 5: Tr oubleshooting 5.1 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67 5.2 Troubleshooting tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson 8600 - page 8

    vi Reference Manu al 00809-0100-4860, Rev BC Table of Contents January 2013 T a ble of Cont ents C Appendix C: Electronics verification C.1 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119 C.2 Electronics verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson 8600 - page 9

    1 Reference Manu al 00809-0100-4860, Rev BC Section 1: Introduction January 2013 Introduc tion Sec tion 1 Introduc tion How to use this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1 Safety m essages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson 8600 - page 10

    2 Reference Manu al 00809-0100-4860, Rev BC Section 1: Introduc tion January 2013 Introduction 1.2 Safet y messages Procedures and instruc tions in this manual may require special precautions to ensure the safe t y of the personnel pe r forming the operations. Re f er to the sa fety m essages, list ed at the beginning of eac h sec tion, befo re per ...

  • Emerson 8600 - page 11

    3 Reference Manu al 00809-0100-4860, Rev BC Section 2: Instal lation January 2013 Installa tion Sec tion 2 Inst alla tion Safety m essages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson 8600 - page 12

    4 Reference Manu al 00809-0100-4860, Rev BC Section 2: Installation January 2013 Installa tion Figure 2-1. Installation Flo wchart Is Configuration OK? Mount Flowmeter Wire Flowme ter Power Flowmeter DONE Mount Conduit ST ART HERE FIELD INST ALL CONFIGURE Ta g Process Config • T ransmitter Mode •P r o c e s s F l u i d •F i x e d P r o c e s ...

  • Emerson 8600 - page 13

    5 Reference Manu al 00809-0100-4860, Rev BC Section 2: Instal lation January 2013 Installa tion 2.2 Commissioning Commission the Rose mount 8 600D before puttin g it into operation. This ensures proper configuration and op eration of the meter . It also enables you to check hardware setti ngs, test the flowmet er e lec tronics, verify flowmete r co ...

  • Emerson 8600 - page 14

    6 Reference Manu al 00809-0100-4860, Rev BC Section 2: Installation January 2013 Installa tion Horiz ont al installation For hori zontal install ation, the pre fe rred orientatio n is to hav e the electronics installed to the side of the pipe . In liquid applic ations, this e nsures any e ntrapped air or solids do not strik e the shedding bar and d ...

  • Emerson 8600 - page 15

    7 Reference Manu al 00809-0100-4860, Rev BC Section 2: Instal lation January 2013 Installa tion Upstream/Do wnstream piping The vor tex meter m ay be installed with a minimum of ten diam eters (D) of s traig ht pip e lengt h upstre am and five diame ters (D) of straight pipe length downstre am. Rated accuracy is based on the number of pipe di amete ...

  • Emerson 8600 - page 16

    8 Reference Manu al 00809-0100-4860, Rev BC Section 2: Installation January 2013 Installa tion Although the signal conditioning functions reduce susce ptibility to extraneous noise, some environme nts are more suit able than o thers. Avoid pl acing the flowmeter or its wiring close t o device s that produce high inte nsit y electromagneti c and ele ...

  • Emerson 8600 - page 17

    9 Reference Manu al 00809-0100-4860, Rev BC Section 2: Instal lation January 2013 Installa tion Alarm As par t of normal opera tions, the Rose mount 8600D con tinuously runs a se lf-diagnostic routine. If the routine detec ts an intern al failure in the electro nics, flowmeter output is driven t o a low or high alarm leve l, depending on the positi ...

  • Emerson 8600 - page 18

    10 Reference Manu al 00809-0100-4860, Rev BC Section 2: Installation January 2013 Installa tion 2.4.2 L CD indicator op tion If you r electronics are equipped with the L CD indica tor (Option M5), the ALARM and SEC URIT Y jumpers are located on the fac e of the indicator as shown in Fi gur e 2-6 . Figure 2-6. L CD Indicator Alarm and Securit y Jum ...

  • Emerson 8600 - page 19

    11 Reference Manu al 00809-0100-4860, Rev BC Section 2: Instal lation January 2013 Installa tion 2.5 Meter body inst allation ta sks The installation ta sks include detailed mech anical and electrical installation procedures. 2.5.1 Handling Handle all p ar ts carefully to prev en t damage . Whene ver po ssible , transport the syste m to the install ...

  • Emerson 8600 - page 20

    12 Reference Manu al 00809-0100-4860, Rev BC Section 2: Installation January 2013 Installa tion 2.5.4 Flange bolts Install the Ro semount 8600D Flowmeter be t ween two conv ention al pipe flange s, as shown in Figure 2-7 on page 12 . Figure 2-7. Flanged-Style Flowmeter Inst allation Gask ets (Supplied by Customer) Flow Installation Bolt s and Nuts ...

  • Emerson 8600 - page 21

    13 Reference Manu al 00809-0100-4860, Rev BC Section 2: Instal lation January 2013 Installa tion 2.5.5 Flanged-st yle flowmete r mounting Physical moun ting of a flanged-st yle flowme ter is similar t o installing a t ypical section of pipe . Con ven tional to ols, equipmen t, and acces sorie s (such a s bolts and gask ets) are required. Tighten th ...

  • Emerson 8600 - page 22

    14 Reference Manu al 00809-0100-4860, Rev BC Section 2: Installation January 2013 Installa tion 2.6 Electronics consider ations Both integ ral a nd rem ote mou nted el ec tro nic s require input power at the electronic s. For remo te mount installation s, mount the e lec tronics against a fl at sur fac e or on a pipe that is up t o t wo inches (50 ...

  • Emerson 8600 - page 23

    15 Reference Manu al 00809-0100-4860, Rev BC Section 2: Instal lation January 2013 Installa tion 2.6.4 Cable gland If you are using cable glands inst ead of c onduit, follow the cable gland manuf ac turer’s instruc tions for pre paration and make the connections in a conve ntional manner in acc ordance with local or plant electrical codes. Be sur ...

  • Emerson 8600 - page 24

    16 Reference Manu al 00809-0100-4860, Rev BC Section 2: Installation January 2013 Installa tion 2.6.6 Wiring procedure The signal terminals are locat ed in a compart men t of the elec tronics housing separate from the flowme ter e lec tronics. C onnec tions f or a HART-ba sed communi cator and a curr ent t est connection are abo ve the signal te rm ...

  • Emerson 8600 - page 25

    17 Reference Manu al 00809-0100-4860, Rev BC Section 2: Instal lation January 2013 Installa tion Figure 2-10. Po wer Supply Load Limitations Note R loop(max) in t he equation abov e ref ers to the to tal loop load resistanc e. T echnica lly , the total loop load re sistance is the sum of th e loop lo ad resist or , signal wiring resistance , and if ...

  • Emerson 8600 - page 26

    18 Reference Manu al 00809-0100-4860, Rev BC Section 2: Installation January 2013 Installa tion Note If a Smart Wireless THUM™ Ad apte r is being u sed with the Ros emount 8600 flowmeter t o exc hange inf orma tion via the Wi rele ss HART prot ocol, an additional 2.5 Vdc is dropped in the conne c ted loop . This is becau se the THUM is wir ed in ...

  • Emerson 8600 - page 27

    19 Reference Manu al 00809-0100-4860, Rev BC Section 2: Instal lation January 2013 Installa tion Pulse output Note Re member when u sing the pulse outp ut, all power to the electronics is still suppl ied ove r the 4 –20 mA signal wiring. The flowmeter provides an isola ted transistor sw itch-closure frequency output signal propor tional to flow , ...

  • Emerson 8600 - page 28

    20 Reference Manu al 00809-0100-4860, Rev BC Section 2: Installation January 2013 Installa tion Note When using pulse output, be sure to follow these precautions:  Shiel ded t wisted pair is required whe n the pulse output and 4–20 mA out put are run in the same conduit or cable trays. Shielded wire will also reduce false tr iggering caused by ...

  • Emerson 8600 - page 29

    21 Reference Manu al 00809-0100-4860, Rev BC Section 2: Instal lation January 2013 Installa tion Figure 2-13. 4-20 mA Wiring Figure 2-14. 4–20 mA and Pulse Wiring with Electronic T otali zer/ Counter 2 .6 . 7 Remote el ec t r on i c s If you order one of the remot e elec tronics option s (options R10, R20, R 30, R3 3, R50, or RXX), the flowme ter ...

  • Emerson 8600 - page 30

    22 Reference Manu al 00809-0100-4860, Rev BC Section 2: Installation January 2013 Installa tion Mounting Mount the met er body in the process flow line as descr ibed earlier in this sec tion. Mount the bracke t and electronics housing in the desired lo ca tion. The housing can be repositioned on the bracket t o facilitate field wiring and conduit r ...

  • Emerson 8600 - page 31

    23 Reference Manu al 00809-0100-4860, Rev BC Section 2: Instal lation January 2013 Installa tion 1. If you pl an to run the c oaxial cable in c onduit, care fully cut the con duit to the desired length to provide f or proper as sembly at the housing. A junction box may be plac ed in the conduit run to provide a spac e for ex tra coaxial cable lengt ...

  • Emerson 8600 - page 32

    24 Reference Manu al 00809-0100-4860, Rev BC Section 2: Installation January 2013 Installa tion the indicat or . Figure 2-1 6 shows the flowmete r fitted with the LCD indicat or and ex tended cover . The indicator f ea tures an eight- character (and five alphanume ric) liquid cr ystal display that gives a direct reading o f the digital signal from ...

  • Emerson 8600 - page 33

    25 Reference Manu al 00809-0100-4860, Rev BC Section 2: Instal lation January 2013 Installa tion Figure 2-17 shows the ind icator displ ay with all segments lit. A HART-b ased comm unicator can be u sed to c hange the enginee ring units of th e paramete rs display ed on the indicator . (See Section 4: O pera tion for more inf ormation). 2.7.1 Insta ...

  • Emerson 8600 - page 34

    26 Reference Manu al 00809-0100-4860, Rev BC Section 2: Installation January 2013 Installa tion Note The circui t board is electrosta tically sensit ive. Be sure to obse r ve handlin g precautions for st ati c-s ensi ti ve com po nents . 3. Inser t the mounting screw s into the L CD indic ator . 4. Re mov e the t wo jumpers on the c ircuit boar d t ...

  • Emerson 8600 - page 35

    27 Reference Manu al 00809-0100-4860, Rev BC Section 2: Instal lation January 2013 Installa tion 2.8.1 Installing the T ransien t Protector For flowmete rs ordered with the transient prot ector option (T1), the protector is shipped installed. When purch ased se parate ly from the Ro semount 8600 D, you mu st install the prot ec tor on a R osemoun t ...

  • Emerson 8600 - page 36

    28 Reference Manu al 00809-0100-4860, Rev BC Section 2: Installation January 2013 Installa tion ...

  • Emerson 8600 - page 37

    29 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configuration January 2013 Configu ration Sec tion 3 Con figura tion Re view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 29 Process variable s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson 8600 - page 38

    30 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configu ration January 2013 Configuration 3.2.2 PV% of range Perce nt of Range — The primar y variable as a percentage of range provides a gauge as to where the curre nt mea sureme nt of th e meter is wi thin the confi gured range of the met er . For example , the range may be defined as 0 g ...

  • Emerson 8600 - page 39

    31 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configuration January 2013 Configu ration Standard/Normal f low units Std Cu f t/ m i n SCFH NCMM NmlCum/h NCMD Note When c onfiguring Stand ard or Normal Flow units to the v olumetric flow , a densit y ratio mu st be provi ded. See the Dens it y/Density Ratio on p age 39 . Special units Speci ...

  • Emerson 8600 - page 40

    32 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configu ration January 2013 Configuration R osemount 8600D to displa y flow in bar rels pe r minute instead of gallons per minute , and one barrel is equal to 31.0 g allons.  Base volume unit: gal  Bas e time uni t: min  Use r defined unit: br  Conve rsio n number: 1 / 31.0 See the ...

  • Emerson 8600 - page 41

    33 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configuration January 2013 Configu ration For example , if you are c onve r ting from gallons to barrel s and there are 31 gallons in a barrel, the conv ersion factor is 31. The conve rsion equa tion is as follows (where barrels is the new vol ume u ni t): 1 gallon = 0.032258 bbl. Mass flow Al ...

  • Emerson 8600 - page 42

    34 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configu ration January 2013 Configuration Ve l o c i t y f l o w Displays t he cu rrent velocit y fl ow value and u nits. Ve l o c i t y u n i t s Allows the user to se lec t the velocit y units from t he available list. V elocit y m easured base V elocity Measured Base will dete rmin e if the ...

  • Emerson 8600 - page 43

    35 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configuration January 2013 Configu ration To t a l i z e r c o n f i g To t a l i z e r C o n f i g — Used to configure the flow paramet er (volume, m ass, ve locit y) that will be total led . Note The to talizer va lue is saved in the non-v olat ile memor y of the e lec tronics every three ...

  • Emerson 8600 - page 44

    36 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configu ration January 2013 Configuration Calculat ed process density Allows use rs to view the calculated proce ss density value when the vor tex is configured f or tempe rature compe nsated steam applica tions. Also allows the use r to con figure the calculated densi t y units. Process densi ...

  • Emerson 8600 - page 45

    37 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configuration January 2013 Configu ration T/C failure mode Allows the us er to conf igure the temperature se nsor failure mode. In the even t that the thermocouple sensor fails, the vor tex can go eith er int o an alarm output mode, or co ntinue to opera te norm ally using the Fix ed Proc ess ...

  • Emerson 8600 - page 46

    38 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configu ration January 2013 Configuration 3.2.6 T ag T ag is the quick est way t o identify and dist inguish between flowmete rs. Flowmeters can be tagged according to the require ments of y our application. The tag may be up to eight char ac ters long. 3. 2 . 7 P r oce ss co nfi g The flowmet ...

  • Emerson 8600 - page 47

    39 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configuration January 2013 Configu ration Density/Densit y ratio When con figurin g a meter f or mass flo w un its, a densit y value needs to be entered. Whe n con figuring a meter f or Stand ard and Normal V o lumetri c flow units a density ratio will be required. Densit y ratio Configure the ...

  • Emerson 8600 - page 48

    40 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configu ration January 2013 Configuration Operating conditions T f = absolute temperature at actual (flowing ) conditions in degrees Rankine o r Ke lvin. (The transmitter will c onvert from de grees F ahrenheit or degrees Ce lsius t o degrees Rankine or Ke lvin respect ively .) P f = absolute ...

  • Emerson 8600 - page 49

    41 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configuration January 2013 Configu ration 3 .2 . 8 Reference K - fa c to r The r efe rence K-fa c tor is a fa cto r y c alibrat ion nu mber rela ting the flow through the m ete r to the shedding frequency mea sured by the el ec tronics. Ev er y 8600 meter manufactured by Emerson is run t hroug ...

  • Emerson 8600 - page 50

    42 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configu ration January 2013 Configuration Primar y V ariable (PV) Selections for this Variable are Mass Flow , Volumetric Flow , V elocit y Flow , a nd Process T emper ature. The Primar y V ariable is the variable mapped to the analog output. Secondary V ariable (SV) Selections f or this V ari ...

  • Emerson 8600 - page 51

    43 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configuration January 2013 Configu ration Primar y V ariable Lo wer R ange V alue (PV LR V) This is the 4 mA set point for the meter , and is t ypically set to 0 wh en the PV is a Flow Vari able. 3.2.14 PV da mping Damping ch anges the response time o f the flowmete r to smooth vari ations in ...

  • Emerson 8600 - page 52

    44 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configu ration January 2013 Configuration Figure 3-1. Field Communicator Me nu T ree for the Rosemount 8600D 1. Device Setup 2. PV 3. AO 4. LRV 5. URV 1. Process Variables 2. Diagnostics and Service 3. Basic Setup 4. Detailed Setup 5. Review 1. PV 2. PV % Range 3. Analog Output 4. View Other V ...

  • Emerson 8600 - page 53

    45 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configuration January 2013 Configu ration T able 3-2. Field Communicator Fast K ey Sequences f or the Rosemount 8600D Fu n c t i o n Fa s t Ke y s Alarm Jum per 1, 4, 2, 1, 3 Analog Output (Config) 1, 4, 2, 1 Analog Output (View) 1, 1, 3 Auto Ad just F ilter 1, 4, 3, 1, 4 Bas e Time Unit 1, 1, ...

  • Emerson 8600 - page 54

    46 Reference Manu al 00809-0100-4860, Rev BC Section 3: Configu ration January 2013 Configuration ...

  • Emerson 8600 - page 55

    47 Reference Manu al 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope ration Sec tion 4 O pe ration Diagnostics/service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4 7 Advanc ed func tionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson 8600 - page 56

    48 Reference Ma nual 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope rati on Densit y test calc Allows for the test of the density calculation for saturat ed steam. The vor tex meter will calculat e th e asso cia te d s tea m de ns it y a t a us er en ter ed tem p era tu re va l ue. Pr oc ess Fl u id mu st be s et t o T comp Sa t St e ...

  • Emerson 8600 - page 57

    49 Reference Manu al 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope ration 4.1.3 Pulse output test Pulse Output T est is a fixed frequency mode test that checks the integrit y of the pulse loop. It tests tha t all connections are good and that the pulse output is r unning on the loo p . 4.1.4 Flow simula tion Flow Simulation en ables ...

  • Emerson 8600 - page 58

    50 Reference Ma nual 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope rati on Simulate flow external Simula te flow external allo ws you to dis connect the sensor electronically so an external frequency sourc e can be used to te st and veri f y the electronics. Enable normal flow Enabl e nor mal fl ow a llows you to e xit the flow si m ...

  • Emerson 8600 - page 59

    51 Reference Manu al 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope ration Once your scaled trim points have been e n tered a s 2 and 10, you can now calibrate y our flow meter by enterin g vo lta ge measu rements dir ec tl y f rom th e vol tm eter . 4.1.7 Shed freq at UR V Shed Freq a t URV function gi ves the shedding freque nc y c ...

  • Emerson 8600 - page 60

    52 Reference Ma nual 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope rati on Mating pipe I.D. The inside diamet er of the pipe adjace nt to the flow meter can cau se entrance e ffects that may alte r flowmete r readi ngs. The exact inside diame ter of the pipe mu st be specified to correct for these eff ec ts. Ent er the appropriat e ...

  • Emerson 8600 - page 61

    53 Reference Manu al 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope ration 4.3.2 Configure outputs The Ro semount 8600D is digitally adju sted at the factor y using precision equipme nt to e nsure accurac y . Y ou shou ld be able to install and operate the flowmeter without a D/A T rim. Analog output For m aximum accuracy , calibrate ...

  • Emerson 8600 - page 62

    54 Reference Ma nual 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope rati on Alarm lev el selec t Select the Alarm le ve l of the transmitte r . Either R ose mount standa rd or NAMUR compli ant. Alarm / sat lev els Displ ays Alarm and Satur ation mA output leve ls. Note Alarm and Saturation levels can be found in the specifications se ...

  • Emerson 8600 - page 63

    55 Reference Manu al 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope ration Pulse output The Ro semount 8600D c omes with an option al pulse output option (P). This enables the flow meter to o utpu t th e pul se r ate to a n ex ter nal contr ol s ystem , tota lizer , or oth er dev ice. If th e flowmete r was orde red with the pulse mo ...

  • Emerson 8600 - page 64

    56 Reference Ma nual 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope rati on Scaled velocity This mode allows you to configure the pu lse output based on a ve locit y Flow Rate . Pulse scaling rate Allows the us er to se t a certain veloc it y flow rate t o a desired frequency . For e xa m pl e: 10 f t/sec = 10,000HZ 1. Ent er a Flow ...

  • Emerson 8600 - page 65

    57 Reference Manu al 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope ration Pulse output test Pulse Output T est is a fixed frequency mode test that checks the integrit y of the pulse loop. It tests that all c onne ctio ns are good and that pulse output is running o n the loop. HART output Multidrop configuration ref ers to the connec ...

  • Emerson 8600 - page 66

    58 Reference Ma nual 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope rati on Poll add ress Poll Ad dress e nables yo u to set the poll addre ss for a multi-drop ped meter . The poll address is used to ide ntif y each meter on the multi -drop line. Follow the on-screen instr uc tions to set the address at a number from 1 to 15. T o set ...

  • Emerson 8600 - page 67

    59 Reference Manu al 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope ration Burst option Burst Option e nable s you to se lect the variables t o broadcas t ove r the burst transmitte r . Choose one of the f ollowing op tions : PV –Selects the process variable f or br oadca st ove r the burst transmitte r . Perce nt Range/Current – ...

  • Emerson 8600 - page 68

    60 Reference Ma nual 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope rati on XMTR variable slo t 4 User se lec ted Burst Variable 4. Local display The Local Dis play function on the R osemoun t 8600D allows yo u to select which vari ables are shown on the optional (M5) local di spla y . Choos e from the foll owing vari able s:  Pri ...

  • Emerson 8600 - page 69

    61 Reference Manu al 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope ration If one or more of these conditions exist, a nd you h ave check ed other pote ntial sources (K-fac tor , ser vice ty pe, lo wer and upper range values, 4–20mA tr im, pulse scaling fac tor , process tempe rature , pipe ID), refe r to Sec tion 5: T roubl eshoot ...

  • Emerson 8600 - page 70

    62 Reference Ma nual 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope rati on Manual filter adjust Manual Filter Adju st a llows you to manu ally adjust the following settings : Low Flow Cutoff , Low Pass Filte r , and T rigger Lev el, while monitoring flow and or sig/tr . Primar y V ariable (PV ) PV is the actual mea sured variable . ...

  • Emerson 8600 - page 71

    63 Reference Manu al 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope ration The Low P ass Filte r corner freq uency variable off ers t wo modes for adju stmen t:  Increase filte ring  Increase se nsit ivit y T rigger lev el T rigger Level is c onfigured to rejec t noise wi thin the flow ra nge while allowing normal am plitude va ...

  • Emerson 8600 - page 72

    64 Reference Ma nual 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope rati on T emperat ure damping The default d amping value is 2.0 sec onds. T e mpera ture Damping can be reset to an y value between 0.4 and 32 sec onds. LFC response D ef i n es h o w th e o u t p ut o f t he Vor t e x m et er w i l l be ha ve en t er i n g in t o a ...

  • Emerson 8600 - page 73

    65 Reference Manu al 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope ration Date Dat e is a user-defined variable that pro vides a place to sa ve a date , t ypically used to store the last dat e that the transmitter c onfiguration was changed. Wr i t e p r ot e c t Write Pro tec t is a read-only information al variable that re fle cts ...

  • Emerson 8600 - page 74

    66 Reference Ma nual 00809-0100-4860, Rev BC Section 4: Operation January 2013 Ope rati on Hardware re v Hardware Rev – Designa tes the revision le vel f or the Ro semount 8600D har dware. Final assembly number Final Assembly Number – F actor y set number th at refe rs to the elec tronics of your flowmet er . The number is con figured int o the ...

  • Emerson 8600 - page 75

    67 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g Sec t ion 5 T roubleshoo ting Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 67 T roubleshooting tables . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson 8600 - page 76

    68 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g 5.2 T roubleshooting ta bles The most c ommon problems expe rienced by use rs of the R osemoun t 8600D are listed in “T rou- bleshooting tables ” on page 68 along with pote ntial causes o f the problem and suggested corrective ac ti ...

  • Emerson 8600 - page 77

    69 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g 5.3 Adv anced troubleshooting The Ro semount 8600D e lec tronics provides se veral adva nced troubleshoot ing fea tures. These fe atures enhance y our abilit y to lo ok inside the electronics a nd can be helpful for troubleshoot- ing in ...

  • Emerson 8600 - page 78

    70 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g T able 5-1. Diagnostic Messages Mess age Descript ion ROM C HEC K SU M E RRO R The EPROM me mor y checksum test has failed. The transmitter will re main in ALARM until the ROM checks um test passes. NV MEM CHE CK SUM ERROR The Us er Con ...

  • Emerson 8600 - page 79

    71 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g 5.3.2 Elec tronics test points As s ho wn i n Figure 5-1 , there are several test points located on the elec tronic s. LO W L OOP VOL T AG E The voltage at the transmitter terminals ha s dropped to a level that is cau sing t he intern a ...

  • Emerson 8600 - page 80

    72 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g The electronics is capable of inte rnally gene rating a flow signal tha t may be used to sim ulate a sens or signal to pe r form electronics v erification with a Handheld C ommunicator or AM S inte r face . The simulated sign al amplitu ...

  • Emerson 8600 - page 81

    73 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g 5.4 Diagnostic messages on LCD In addition to the output, the LCD indicator di splays diagnostic messag es for t roublesho oting the flowmete r . These messages are a s follows : SELF TEST The flowmete r is in the process of pe r formin ...

  • Emerson 8600 - page 82

    74 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g F A UL T_EER OM The flowmet er electronics has unde rgone a EEPR OM checksum fault. Contact your Fie ld Service Center . F A UL T_RAM The flowmete r electronic s ha s undergone a RAM test fault. Contac t you r Field Ser vice Center . F ...

  • Emerson 8600 - page 83

    75 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g F A UL T_T AC O (MT A op tion only) The ASIC responsible for the an alog to digital co nversi on of the pro cess temperat ure has faile d. Contac t you r Field Ser vice Center . F A UL T_T C (MT A option only) The tempe rature sensor th ...

  • Emerson 8600 - page 84

    76 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g Note Use only the procedures and new parts specifical ly ref ere nced in this manual. Un authoriz ed procedur es or par ts can a ffect produc t performa nce and the output signal us ed to control a process, and ma y render the instrumen ...

  • Emerson 8600 - page 85

    77 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g Install the terminal block 1. A l ig n th e s o cke te d h o le s o n t he b ac k si d e o f t h e t er mi na l bl o ck ov er t h e p i ns p ro tr u di n g from the bo ttom of the hou sing cavity in the termin al block side of the e lec ...

  • Emerson 8600 - page 86

    78 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g 3. If the meter h as the LCD indica tor option, loosen the t wo screws. Re move the L CD and the connector from the electronics board. 4. Loose n the three captive screws th at anchor the electronics. 5. Use plie r s or a flathe ad scre ...

  • Emerson 8600 - page 87

    79 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g Install the elec tronics boards 1. V erify that powe r to the R osemoun t 8600D is off. 2. Align the sockets on the bottom of the t wo elec tronics boards ove r the pi ns protruding from the bottom of the housing cavit y . 3. Carefull y ...

  • Emerson 8600 - page 88

    80 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g Re move the electronic s housing 1. T urn off the powe r to the Ro semount 8600D . 2. Re move the te rminal block side cove r . 3. Disconnect the wires and c onduit fro m the housing. 4. Use a 5 / 32 -in. (4 mm) hex wrench to loose n th ...

  • Emerson 8600 - page 89

    81 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g Note Be sure to fully c heck all other tro ubleshooti ng possibili ties bef ore removi ng the sensor . Also, plea se n ote that the sensor is a complete assembly and cannot be fur ther disassembled. T o ols needed  5 / 32 -in. (4 mm) ...

  • Emerson 8600 - page 90

    82 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g Cleaning the se aling sur face Befo re inst alling a sensor in the meter body , clean the sealing sur face by c ompleting t he following procedure . The gask ets around the sens or are used t o seal in the proc ess flui d. 1. Use a suct ...

  • Emerson 8600 - page 91

    83 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g 5.6.5 R emo te e lec tronic s proc edure If the Ro semount 8600D e lec tronics housin g is mounted re motely , some re place ment procedures are di ffer ent than f or the flowmete r with integral electronics. The following proce dures a ...

  • Emerson 8600 - page 92

    84 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g Detac h the mete r adapt er The above instruc tions will provide access to the meter body . Use the following steps if it is ne ces sa r y to rem ove t he coa xia l c ab l e: 1. Loose n and remove the t wo screws that hold the union ont ...

  • Emerson 8600 - page 93

    85 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g Attac h the me ter ad apter 1. If you are us ing a conduit adap ter or cable glan d, slide it ov er the pl ain e nd of the coaxi al cable (the end withou t a ground wire). 2. Slide the mete r adapte r ove r the coaxial cable e nd. 3. Us ...

  • Emerson 8600 - page 94

    86 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g 5. Loose n the conduit adap ter (or cable gland) from the housing adapter . Figure 5-11. Remot e Elec tronics Exploded View Grou nd Connection Hou sing Adapte r Hous ing Ada pter Sc rews Electroni cs Housing Coaxial Cable Nu t Housing B ...

  • Emerson 8600 - page 95

    87 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g Att a ch t he coa xi al c ab le 1. Rout e the co axial cable through the conduit (if you are usi ng co nd ui t) . 2. Place a conduit adapter ove r the end of the coaxial cable . 3. Re move the hou sing adapt er from the electronics hous ...

  • Emerson 8600 - page 96

    88 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g 5.6.7 Ch anging the housing orien tation The en tire electronics hou sing may be r otated in 90 de gre e i nc rement s for easy v iew ing . Use th e follo wing steps t o change the hou sing orientat ion: 1. Loos en the screw on th e acc ...

  • Emerson 8600 - page 97

    89 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g Note Use pl ant approved proc edure for re moving a te mpera ture sensor from a the rmowell. 3. R emov e tempe rature s ensor from e lectronics by usin g a 2.5 mm allen wre nch to remove cap head screw from elec tronics . 4. Gently pull ...

  • Emerson 8600 - page 98

    90 Reference Manu al 00809-0100-4860, Rev BC Section 5: Troubleshooting January 2013 Tr o u b l e s h o o t i n g ...

  • Emerson 8600 - page 99

    91 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Reference Data January 2013 Specifications and Ref erenc e Data A p p en d i x A R efer en ce dat a Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 91 F unc tional specifications . . . . . . . . . . . ...

  • Emerson 8600 - page 100

    92 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Re ference Data January 2013 Specifications and R ef erence D ata The Reynol ds number equation shown be low combines the effects of de nsit y (  ), visc osit y (  cp ), pi pe inside diamete r (D), a nd flow velocity (V). Process temperature limits Sta nda rd -58 to 482 °F (–50 to 25 ...

  • Emerson 8600 - page 101

    93 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Reference Data January 2013 Specifications and Ref erenc e Data Analog output adjustment Engineering units and lowe r and u pper range values are us er-selec ted. O utpu t is automatic all y scaled to provide 4 mA at the selected lower range value , 20 mA at the se lec ted upper range value. ...

  • Emerson 8600 - page 102

    94 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Re ference Data January 2013 Specifications and R ef erence D ata Load limitations (HART analog) Maximum loop re sistance is dete rmined by the v oltage leve l of the external pow er supply , as described by: Note HART Communication require s a mini mum loop resistance of 250 ohms. Option al ...

  • Emerson 8600 - page 103

    95 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Reference Data January 2013 Specifications and Ref erenc e Data Permanent pressure lo ss The approxim ate pe rmanent pres sure loss (PPL) from the R ose mount 8600D flo wmeter is calculated for e ach application i n the V or tex sizing sof t ware available from your loca l Ro semount represen ...

  • Emerson 8600 - page 104

    96 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Re ference Data January 2013 Specifications and R ef erence D ata F ailure mode alarm HART an alog If self-di agnostics detect a gross flowmeter failure , the analog si gnal will be drive n to the v alues below: High or low alarm signal is use r-selectable through the fail mode alarm jump er ...

  • Emerson 8600 - page 105

    97 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Reference Data January 2013 Specifications and Ref erenc e Data 3 kA crest (8  20  s) 6 kV crest (1.2  50  s) 6 kV/0.5 kA (0.5  s, 100 kHz , ring wave) Security lockout When the securit y lo ckout jumpe r is en abled, the electronics wil l not allow you to modif y parameters t ...

  • Emerson 8600 - page 106

    98 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Re ference Data January 2013 Specifications and R ef erence D ata A. 3 T y pi ca l fl o w r an ge s Ta b l e A - 5 - Ta b l e A - 9 sh ow t y pical flow ra nges for some common proc ess fluids with default filte r setting s. Consult your local sale s represe ntativ e to ob tain a comput er si ...

  • Emerson 8600 - page 107

    99 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Reference Data January 2013 Specifications and Ref erenc e Data 200 psi g (13,8 bar G) max min 79.2 2.34 134 3.98 212 5.51 360 9.36 349 9.09 593 15.4 300 psi g (20,7 bar G) max min 79.2 2.34 134 3.98 198 5.51 337 9.36 326 9.09 554 15.4 400 psi g (27,6 bar G) max min 73.0 2.34 124 3.98 172 5.5 ...

  • Emerson 8600 - page 108

    100 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Re ference Data January 2013 Specifications and R ef erence D ata Note s The Ro semount 8600D me asures the v olumetric flow under ope rating conditions (i.e . the ac tual volume at the ope rating pressure and te mperatur e–acfm or ac mh), as shown above. Howeve r , ga s volumes are strong ...

  • Emerson 8600 - page 109

    101 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Reference Data January 2013 Specifications and Ref erenc e Data T able A-11. Saturated Steam Flow Rate Limits (Assumes S team Quality is 1 00%) Process Pressure Flow Rate Limits Minimum and Maximum Saturated Ste am Flow Rates for line siz es 3-in./DN 80 through 4-in./DN 100 3-in./DN 80 4-i n ...

  • Emerson 8600 - page 110

    102 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Re ference Data January 2013 Specifications and R ef erence D ata A .4 Performance specifications The following performance specifications are for all R osemount models exc ept where no ted. Digital per formance specifications applicable to Digital HART output. A. 4 . 1 F lo w a cc u r acy I ...

  • Emerson 8600 - page 111

    103 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Reference Data January 2013 Specifications and Ref erenc e Data Nominal c onditions include tempe rature varia tio n in saturation and superhe at at 150 psig (10 bar-g) and abov e. For pre ssure below 150 p sig (10 bar-g), add 0.08% of unce r taint y for e very 15 psi (1 bar) below 150 psig ...

  • Emerson 8600 - page 112

    104 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Re ference Data January 2013 Specifications and R ef erence D ata Vibration spec ifications Integral aluminum housings and remote aluminum housings At or near the minimum liquid flow rate in a normal pipe mounted in stalla tion, the maximum vibration should be 0.0 87-in. (2,21 mm) double amp ...

  • Emerson 8600 - page 113

    105 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Reference Data January 2013 Specifications and Ref erenc e Data Po wer supply eff ec t HART an alog Les s than 0.005% of span pe r volt A .5 Ph ysical specifications NA CE compli ance Mat erials o f Construction meet NACE m ateri al recomme ndati ons per MR0175/IS O15156 for u se in H 2 S co ...

  • Emerson 8600 - page 114

    106 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Re ference Data January 2013 Specifications and R ef erence D ata Gasket Graphite wit h Stainless Stee l Inser t Proces s connections Mounts between the following flange c onfigurations: ASME B16.5 (AN SI): Cla ss 150, 300 EN 1092: PN 16, 40 , 63 Mounting Integr al (standard) Electronic s ar ...

  • Emerson 8600 - page 115

    107 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Reference Data January 2013 Specifications and Ref erenc e Data A .6 Dimensional dra wings Figure A-1. Flanged-Style Flowmeter Dimensional Dra win gs (1-through 8-in./25 through 200 mm Line Size s) Diameter 3.08 (78.2) Diameter B 3.20 (81) 2.56 (65) 2.90 (72) 1.10 (28) 1.00 (25.4) C A 2.00 ( ...

  • Emerson 8600 - page 116

    108 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Re ference Data January 2013 Specifications and R ef erence D ata T able A-14. Flanged-Style Flowmeter (1-through 2-in./25 through 50 mm Line Sizes) Nominal Size in. (mm) Flange Rating F ace-to-face A in. (mm) Diame ter B in. (mm) C in. (mm) Wei g h t (1) lb (kg) (1) Add 0.2 lb (0,1 kg) for ...

  • Emerson 8600 - page 117

    109 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Reference Data January 2013 Specifications and Ref erenc e Data Figure A-2. Dimensional Drawings for Remote Mount T ransmitters 5.77 (147) 1 / 2 -14 NPT (F or Remote Cable Conduit) 2.00 (51) 3.12 (80) 6.77 (172)  2.44 (62) 3.20 (81) 2.56 (65) 1.10 (28) 2.85 (72) 1.00 (25,4) 4.35 (110) 3.0 ...

  • Emerson 8600 - page 118

    110 Reference Manu al 00809-0100-4860, Rev BC Appendix A: Re ference Data January 2013 Specifications and R ef erence D ata Figure A-3. Dimensional Drawings for Flanged S t yle Remote Mount Flo wmeters (1-through 8-in./25 through 200 mm Line Siz es) T able A-17. Remot e Mount, Flange d St yle Sensor Flowmet er Dimensions Nominal Siz e in. (mm) E Fl ...

  • Emerson 8600 - page 119

    111 Reference Manu al 00809-0100-4860, Rev BC Appendix B: Approval information January 2013 Approval in formation Appe ndix B A pprov al inf orm ation B.1 Produc t ce r tifications B.1.1 Approv ed manufac turing locations Emerson Pro cess Man agement Flow T echnologies Co mpany , Ltd - N anjing, Jiang su Province , P . R. China B.1 .2 Intern ationa ...

  • Emerson 8600 - page 120

    112 Reference Manu al 00809-0100-4860, Rev BC Appendix B: Approval information January 2013 Approval in forma tion T ype 'n' certification IE C 60079-0: 2011 Edition : 6.0 IE C 60079-11: 2011-06 Edition : 6.0 IE C 60079-15: 2010 Edition : 4 N7 Certification No . IE CEx BA S 12.0054X Ex nA ic IIC T5 Gc (-40 °C ≤ Ta ≤ +70 °C) Maximum ...

  • Emerson 8600 - page 121

    113 Reference Manu al 00809-0100-4860, Rev BC Appendix B: Approval information January 2013 Approval in formation B.1.3 Chin ese ce r t ifications (NEP SI) Flameproof ce r tification GB3836.1– 20 10 GB3836.2– 20 10 GB3836.4– 20 10 E3 Certificat ion No. GYJ111284X Ex db ia IIC T6 (-50 °C ≤ Ta ≤ +70 °C) Proces s tempe rature range : -202 ...

  • Emerson 8600 - page 122

    114 Reference Manu al 00809-0100-4860, Rev BC Appendix B: Approval information January 2013 Approval in forma tion I.S. cert ification GB3836.1– 20 10 GB3836.4– 20 10 GB3836.20– 2010 I3 Certification No . GYJ12.1239X Ex ia IIC T4 Ga (-60 °C ≤ Ta ≤ +70 °C) Ui = 30 Vdc Ii = 185 mA Pi = 1.0 W Ci = 0uF Li= 0.97mH Special conditions f or saf ...

  • Emerson 8600 - page 123

    115 Reference Manu al 00809-0100-4860, Rev BC Appendix B: Approval information January 2013 Approval in formation 12. During installa tion, opera tion and main ten ance, users sh all comply with the re levant require ments o f the produc t instruction manual, GB3836.13-1 997 “Elec trical apparatus for e xplos ive gas atmospheres Par t 13: Repair ...

  • Emerson 8600 - page 124

    116 Reference Manu al 00809-0100-4860, Rev BC Appendix B: Approval information January 2013 Approval in forma tion B.1.4 Europe an cer tifica tions (A TE X) I.S. cert ification EN 60079-0: 2012 EN 60079-11: 2012 I1 Certification No . Basee fa12A TE X0179X A TE X Marking II 1 G Ex ia IIC T4 Ga (-60 °C ≤ Ta ≤ +70 °C) Ui = 30 VDC Ii= 185 mA Pi = ...

  • Emerson 8600 - page 125

    117 Reference Manu al 00809-0100-4860, Rev BC Appendix B: Approval information January 2013 Approval in formation E1 Certificat ion No. DEKRA12A TE X0189X Integ ral T ran smi tter ma rked: A TE X Marking II 1/2 G Ex d [ia Ga] IIC T6 Ga/Gb Remote T ran smi tter mar ked: A TE X Marking II 2 G Ex d [ia Ga] IIC T6 Gb Rem o te S en s o r ma r ke d : A T ...

  • Emerson 8600 - page 126

    118 Reference Manu al 00809-0100-4860, Rev BC Appendix B: Approval information January 2013 Approval in forma tion ND Certification No . DEKRA12A TE X0190X Integ ral T ran smi tter ma rked: A TE X Marking II 1 D Ex ta [ia] IIIC T500 90°C Da Remote T ran smi tter mar ked: A TE X Marking II 1 D Ex ta [ia] IIIC T500 90°C Da Rem o te S en s o r ma r ...

  • Emerson 8600 - page 127

    119 Reference Manu al 00809-0100-4860, Rev BC Appendix C: Electronics verification January 2013 Elec tronics verification Appe ndix C Elec tronic s v e rification Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 119 Electronics verification . . . . . . . . . . . . ...

  • Emerson 8600 - page 128

    120 Reference Manu al 00809-0100-4860, Rev BC Appendix C: Electronics verification January 2013 Electronics v erifi cation C .2 Electronics verification Elec tronics func tionalit y can be verified vi a t wo differe nt ve rification methods:  Flow Simulation Mode  Using an Extern al Freque nc y Gene rator Both me thods require the use o f a F ...

  • Emerson 8600 - page 129

    121 Reference Manu al 00809-0100-4860, Rev BC Appendix C: Electronics verification January 2013 Elec tronics verification Figure C- 1. Profile of V ar y ing Flow Simulation Signal. C.2.4 Elec tronics ve rification using an extern al frequency gene rat or If an extern al freque nc y sourc e is desira ble, the n test po ints on the electronics are av ...

  • Emerson 8600 - page 130

    122 Reference Manu al 00809-0100-4860, Rev BC Appendix C: Electronics verification January 2013 Electronics v erifi cation 1. Re move the e lec tronics compartm en t cov er . 2. Re move the t wo screws and the L CD indic ator if applicable. 3. Connec t a Field Communicator or AMS to the loop . 4. Access the flow simula tion menu on the c ommuni cat ...

  • Emerson 8600 - page 131

    123 Reference Manu al 00809-0100-4860, Rev BC Appendix C: Electronics verification January 2013 Elec tronics verification Figure C-2. T est F requenc y Output and Chassis Ground Points. C.2.5 Calcula ting output variable s with known input freque nc y Use the f ollowing equations with a known input freque nc y for ve rification of a flow rate or 4? ...

  • Emerson 8600 - page 132

    124 Reference Manu al 00809-0100-4860, Rev BC Appendix C: Electronics verification January 2013 Electronics v erifi cation T o verif y a 4–20 mA output For a giv en input frequency F (Hz), and K-fac t or (compe nsated), find output current I: where C x is the unit con ve r sion ( T able C-1 on page C-125 ), URV is the uppe r range value (user uni ...

  • Emerson 8600 - page 133

    125 Reference Manu al 00809-0100-4860, Rev BC Appendix C: Electronics verification January 2013 Elec tronics verification T able C-1. Unit Con versions r =operating de nsit y * Spec ial Units Conv ersion Factor C. 3 E x a mp l e s The following examples illustrate the flowrate calculations tha t may be necessar y for your application. There are wa ...

  • Emerson 8600 - page 134

    126 Reference Manu al 00809-0100-4860, Rev BC Appendix C: Electronics verification January 2013 Electronics v erifi cation K-factor (compe nsated) = 10.79 (via Field C ommunicator or AMS) = 75.00/(10.79  0.016 6667) = 417.1 gpm There fore , an input frequenc y of 75.00 Hz re presents a flow ra te of 417.1 gpm in this applica tion. For a giv en i ...

  • Emerson 8600 - page 135

    127 Reference Manu al 00809-0100-4860, Rev BC Appendix C: Electronics verification January 2013 Elec tronics verification For a giv en input frequency , you m ay also dete rmine the curren t output. Use the Example 2 on page 126 with an input freque nc y of 300 Hz: URV= 40000 lb/hr LR V= 0 lb/hr F in (Hz) = 300.00 = 9.83 mA There fore , an input fr ...

  • Emerson 8600 - page 136

    128 Reference Manu al 00809-0100-4860, Rev BC Appendix C: Electronics verification January 2013 Electronics v erifi cation C.3.2 SI units Example 1 (SI units) There fore , an input frequency of 80.00 Hz re presen ts a flow rate of 1694.6 lpm i n this application. For a giv en input frequency , you may also dete rmine the current output. U se the ab ...

  • Emerson 8600 - page 137

    129 Reference Manu al 00809-0100-4860, Rev BC Appendix C: Electronics verification January 2013 Elec tronics verification Example 2 (SI units) There fore , an input frequency of 650.00 Hz re presen ts a flow rate of 3446.4 k g/hr in this application. For a giv en input freque ncy , you ma y also dete rmine the current output . Us e the prior e xamp ...

  • Emerson 8600 - page 138

    130 Reference Manu al 00809-0100-4860, Rev BC Appendix C: Electronics verification January 2013 Electronics v erifi cation Example 3 (SI units) There fore , an input frequency of 700.00 Hz re presen ts a flow rate of 9259.2 NCMH in this application. For a giv en input freque ncy , you ma y also dete rmine the current output . Us e the prior e xampl ...

  • Emerson 8600 - page 139

    131 Reference Manu al 00809-0100-4860, Rev BC January 2013 Figure 1-1. R osemount 8600D HART ™ Menu T ree 1. Device Setup 2. PV 3. AO 4. LRV 5. URV 1. Process Variables 2. Diagnostics and Service 3. Basic Setup 4. Detailed Setup 5. Review 1. PV 2. PV % Range 3. Analog Output 4. View Other Variables 1. Volumetric Flow 2. Mass Flow 3. Velocity Flow ...

  • Emerson 8600 - page 140

    132 Reference Manu al 00809-0100-4860, Rev BC January 2013 ...

  • Emerson 8600 - page 141

    Index-1 Reference Manu al 00809-0100-4860, Rev BC Index January 2013 Index A Air Flow Rate Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 Ambient Temperature Limi ts . . . . . . . . . . . . . . . . . . . . . 93 Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18, 93 B Back Pressure . . . . . . . . . . . . . ...

  • Emerson 8600 - page 142

    Index-2 Reference Manu al 00809-0100-4860, Rev BC Index January 2013 Index O Output Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Output Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 Overrange Capabi lity . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 P Paint . . . . . . . . . . . ...

  • Emerson 8600 - page 143

    ...

  • Emerson 8600 - page 144

    Reference Manual 00809-0100-4860, Rev BC January 2013 St andard T erms and C onditions of Sale can be found at ww w .rosemount .com/terms_of_sale The Emer son log o i s a tra demar k a nd ser vi ce ma rk of E mer son E le ct ric Co. Ro semount. the R ose mount logotype, and SMAR T F AMIL Y are registered trade marks of Ro semount Inc. Co planar is ...

Manufacturer Emerson Category Gas Heater

Documents that we receive from a manufacturer of a Emerson 8600 can be divided into several groups. They are, among others:
- Emerson technical drawings
- 8600 manuals
- Emerson product data sheets
- information booklets
- or energy labels Emerson 8600
All of them are important, but the most important information from the point of view of use of the device are in the user manual Emerson 8600.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Emerson 8600, service manual, brief instructions and user manuals Emerson 8600. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Emerson 8600.

A complete manual for the device Emerson 8600, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Emerson 8600 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Emerson 8600.

A complete Emerson manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Emerson 8600 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Emerson 8600, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Emerson 8600, that we can find in the current document
3. Tips how to use the basic functions of the device Emerson 8600 - which should help us in our first steps of using Emerson 8600
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Emerson 8600