Manual Bryant 569J

56 pages 3.99 mb
Download

Go to site of 56

Summary
  • Bryant 569J - page 1

    1 569J AIR - - COOLED CONDENSING UNITS 60 Hz, with PURON R (R - - 410A) REFRIGERANT SIZE S 07 - - 14 Installation, Start - - Up and Ser vice I nstruc tions CONTENTS SAFET Y CONSIDER A TIONS 2 .................... INST ALLA TION GUI DELI NES 2 .................. Replacemen t/Retrof it — R - - 22 to Pur on 2 ........... INS T ALLA TIO N 10 - - 23 . ...

  • Bryant 569J - page 2

    2 SAF ETY CONSIDERA TIONS Impro per in stallation , adjus tment, alteration, ser vice, maintenance, o r us e can cau se exp los ion, fir e, electrical shock or other c onditions which ma y cause personal injury or property dam age. Consult a quali fied instal ler , service agenc y , or your di stributor or branch for infor mation or as sis tance. T ...

  • Bryant 569J - page 3

    3 Same tub e sizes are capab le of hand ling hig her flow rates (expressed as tons of cooli ng capaci ty) wit h Puron refrigera nt compare d to R- - 22 at constant pressure drops. For examp le, a 1 / 2 - - inch OD liquid lin e is rated at 33 % higher tons with Puron R than with R- - 22 (at 5 _ F pressure drop). A 1 1 / 8 - - inch O D su ction line ...

  • Bryant 569J - page 4

    4 C11097 UNI T STD. UNIT WT . CORN ER A CORN ER B CORN ER C CORN ER D CEN TER OF GRA VITY UNIT HEIGHT lbs. kg . lbs. kg. lb s. kg. lbs. kg . lbs. kg. X Y Z H 569J*07A/ B (MC HX) 328 149 128 58 68 31 62 28 70 32 21 [533.2] 19 [482.6] 13 [330.2] 42 3 / 8 [1076.0] 569J*08A/ B (MC HX) 353 160 138 63 72 33 65 29 78 35 19 [482.6] 23 [584.2] 13 [330.2] 42 ...

  • Bryant 569J - page 5

    5 Tab le 1A — Ph ysical Dat a —569J*07-14A/B Un its — 60 Hz E ngl ish UNI T SIZE 569J *07A/B *08A/B *12A/ B *14A/B NOM INAL C APACI TY ( tons) 6 7.5 10 12.5 OPERA TING WEI GHTS (lb ) NOVAT ION ™ Coil (Al T ube) 328 353 418 431 Round T ube/P late Fin Coil ( Cu/Al ) 389 389 490 598 REFRIGERAN T TYPE ‡ R-410A NOVA TION Opera ting Char ge, T ...

  • Bryant 569J - page 6

    6 Tab le 1B — Ph ysical Dat a — 569J*07-14A/B Un its — 60 Hz S I UNI T SIZE 569J *07A/B *08A/B *12A/ B *14A/B NOM INAL C AP A CIT Y (kW ) 21.1 26.4 35.1 44 OPERA TING WEI GHTS (lb ) NOVAT ION ™ Coil (Al T ube) 149 160 190 196 Round T ube/P late Fin Coil ( Cu/Al ) 176 177 222 271 REFRIGERAN T TYPE ‡ R-410A NOVA TION Opera ting Char ge, T y ...

  • Bryant 569J - page 7

    7 Tab le 2A — Ph ysical Dat a — 569J*12-14D/E Un its — 60 Hz En gl ish UNI T SIZE 569J *12D/E *14D/ E NOM INAL C APACI TY ( tons) 10 12.5 OPERA TING WEI GHTS (lb ) NOVAT ION ™ Coil (Al T ube) 499 505 Round T ube/P late Fin Coil ( Cu/Al ) 516 654 REFRIGERAN T TYPE ‡ R-410A NOVA T ION Operating C harge A /B , T ypical (lb) † 7.4 / 7.3 10. ...

  • Bryant 569J - page 8

    8 Tab le 2B — Ph ysical Dat a — 569J*16-25D/E Un its — 60 Hz SI UNI T SIZE 569J *12D/E *14D/ E NOM INAL C AP A CIT Y (kW ) 35.1 44 OPERA TING WEI GHTS (k g) NOVAT ION ™ Coil (Al T ube) 226 229 Round T ube/Pl ate Fin Coil (Cu/ Al T ube) 234 297 REFRIGERAN T TYPE ‡ R-410A NOVA TION Opera t ing C harge A/B, T ypical (kg) † 3.4 / 3.3 4.8 / ...

  • Bryant 569J - page 9

    9 Puron r 1= 123456789 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 56 9J E 1 4A 000 G 0 0 A 0A _____________ Model T ype Pa ck ag in g 569J = Bryant C on de n s in g U ni t R - - - 410A Refrigerant A=S t a n d a r d Ty p e o f C o i l Electrical Options B = Single Circuit with Low Ambient Controller A = Single Circuit E = Dual Circuit with Low Ambient Controll ...

  • Bryant 569J - page 10

    10 . INST ALLA TION Jobsite Survey Complete th e follow ing checks befo re ins tallation. 1. Consult local buildi ng codes a nd the NEC (Nati onal Electrical Code) AN SI /NF P A 70 for special ins talla- tion requ irements . 2. Det ermine unit l ocation (from proje ct plans) or sele ct unit loca tion. 3. Chec k for poss ible overhe ad obstructions ...

  • Bryant 569J - page 11

    11 If it is nec essary to roll the unit into position, mount the unit on lon gitudin al rails, us ing a minimum of 3 roller s. App ly for ce to the rails , not the un it. If the u nit is to be skidded into posit ion, pla ce it on a la r ge pa d and drag it by the pad. Do not a pply any force t o the unit. Raise from above t o lift the unit from the ...

  • Bryant 569J - page 12

    12 T able 5 – 569J* 07-14A/B Pi ping R ecomme nd ations (Single-Circuit Un it) R - - - 410A Equivalent Le ngth Ft 0 --- 3 8 38 - - - 75 75 - - - 113 113 - - - 150 150 - - - 188 m 0 --- 1 2 12 - - - 23 23 - - - 34 34 - - - 46 46 - - - 57 Model Linea r Length Ft 0 --- 2 5 25 - - - 50 50 - - - 75 75 - - - 100 100 - - - 125 m 0 --- 8 8 --- 1 5 15 - - ...

  • Bryant 569J - page 13

    13 T able 6 – 569J*12-14D/E Pi ping R ecomme nd ations (T wo-Circuit Unit) NOT E: 569J* **D/E requires TW O sets of refrig eration piping R - - - 410A Equivalent Le ngth Ft 0 --- 3 8 38 - - - 75 75 - - - 113 113 - - - 150 150 - - - 188 m 0 --- 1 2 12 - - - 23 23 - - - 34 34 - - - 46 46 - - - 57 Model Linea r Length Ft 0 --- 2 5 25 - - - 50 50 - - ...

  • Bryant 569J - page 14

    14 Refer to Hot Gas Bypass line sizing t ables for appropriat e size. Cont act your Bryant represent ative for a copy of these t ables. 569J***D/E: General ly onl y one hot gas bypass system will be appl ied on a two-circuit uni t. Connect the hot ga s bypass system t o Circuit 1 (first-on/l ast-of f, c onnected t o the evaporato r coil’ s bottom ...

  • Bryant 569J - page 15

    15 Installa tion of liqui d line moi sture indica ting sightglass in each circuit is recommend ed. Locate the sigh tglass (es ) between th e outlet of the filter d rier and the TX V inlet. Refer t o T a ble 9 for recommenda tions on refrigera tion specialties . INDOOR COIL CKT 2 AIRFLOW INDOOR COIL CKT 1 AIRFLOW 15 DIAMS MIN 10 DIAMS 8 DIAMS MIN TX ...

  • Bryant 569J - page 16

    16 Sol enoi d drop c ontrol wi ri ng: control t he power t o the liquid l ine solenoid t hrough a Solenoid V al ve Relay (SVR) in all unit s. Use part number HN61P C005 (fiel d- - supplied, install ed). 569J ***A/B unit requi res one SVR; 569J***D/E unit re quires two rel ays. 569J***D/E u ni t als o req uir es a s epa r at e co nt r ol p ow er tra ...

  • Bryant 569J - page 17

    17 Prelim inary C harge — Before starti ng the unit, c har ge R-410A li quid refrigerant into the high side of each 569J circuit through the liquid service valve(s). The am ount of refrige rant added m ust be at least 80% o f the operating ch ar ge listed in T ables 5 or 6 for LI NEA R line leng th LES S the f actory ch ar ge quan tity (if fac to ...

  • Bryant 569J - page 18

    18 Disconnect sizing data is provided on t he uni t informat ive plate . Loca te on unit cabi net or wit hin sight of the unit per nationa l or loc al c odes. Do not cover unit inform ative plate i f mounting the disconnec t on the unit cabine t. Un its wit h Factory -In stalled D iscon nect — The f actory- installed option d iscon nect switch is ...

  • Bryant 569J - page 19

    19 unit disconnec t switch or HA CR switch is open. O ther connec tion methods will result in the conveni ence outl et circui t being de-e nergized when t he unit disconnec t or HACR switch is open. See F ig. 13 . C10206 UNIT VOL T AGE CON NE CT AS PRI MARY CO NNEC TIONS TRANSFO RMER TERMI NALS 208, 230 240 L1: RED + YEL L2: BL U + GRA H1 + H3 H2 + ...

  • Bryant 569J - page 20

    20 All Units — V oltage to comp ress or termin als dur ing oper ation must be within volt age range i ndicate d on unit name plate. See T able s 10 and 1 1. On 3-phase unit s, volt ages between phas es mus t be balanced w ithin 2% and th e current w ithin 10%. Use the formula shown in the legend for T a bles 10 and 1 1, Note 4 (see page 23) to de ...

  • Bryant 569J - page 21

    21 If the unit will be ope rating at 208-3-60 power , remove the black wire (B LK) f rom the tr ansf ormer primary connec tion labe lled “230” and move it to the conne ction labe lled “208”. See Fig. 18. C10079 Fig. 18 - - Con trol T rans former W iring Ext ernal Dev ices — The 569J c ontrol tra nsformers provide 24 - - v NEC Cla ss 2 pow ...

  • Bryant 569J - page 22

    22 T able 10 – Elec trical Data — 569J*07 - - 14A/B 60 Hz Units WTIHO UT POWERED CO NVEN IENCE OUTL ET UNI T V --- P h --- H z VOL TAGE RANGE } CO MPRESSO R 1 OFM (ea) POWER SUPPL Y MIN MAX RLA LRA WAT T S FLA MCA MOCP 569J*07A/ B 208/230 - - - 3 - - - 60 187 253 19 123 325 1.5 26.7 40 4 6 0 --- 3 --- 6 0 414 506 9.7 62 325 0.8 13.7 20 5 7 5 -- ...

  • Bryant 569J - page 23

    23 T able 1 1 – El ectric al Data — 569J*12- - 14D/E 60 Hz Units WTIHO UT POWERED CO NVEN IENCE OUTL ET UNI T V --- P h --- H z VOL TAGE RANGE } CO MPRESSO R 1 COMP RESSOR 2 OFM (ea) POWER SUPPL Y MIN MAX RLA LRA RLA LRA WAT T S FLA MC A MOCP 569J*12D/ E 208/230 - - - 3 - - - 60 187 253 16 110 16 110 325 1.5 40.6 60 4 6 0 --- 3 --- 6 0 414 506 ...

  • Bryant 569J - page 24

    24 PRE- ST AR T -UP IMP ORT ANT : Before be ginning Pre-Start-Up or Star t-Up , review Star t-Up C hecklis t at the back of th is book. The Che cklist assures proper start-up of a unit and provides a record of unit condi tion, applica tion requirem ents, system informat ion, and operation at initial star t-up. UNIT DAMAG E HAZARD Failur e to follow ...

  • Bryant 569J - page 25

    25 Compr essor Ove rload — This overl oad inte rrupts power to the c ompressor when either the curren t or internal moto r winding temperatur e becomes ex cess ive, and automatically r esets when th e interna l tempera ture drops to a s afe le vel. This overload may requi re up to 60 minut es (or longe r) to re set. If the interna l overload i s ...

  • Bryant 569J - page 26

    26 C10913 Fig. 21 - - 569J*07A/B Charging Chart (Novation) C10914 Fig. 22 - - 569J*08A/B Charging Chart (Novation) 569J ...

  • Bryant 569J - page 27

    27 C10915 Fig. 23 - - 569J*12A/B Charging Chart (Novation) C10916 Fig. 24 - - 569J*14A/B Charging Chart (Novation) 569J ...

  • Bryant 569J - page 28

    28 C10917 Fig. 25 - - 569J*12D/E Charging Chart (Novation) 569J ...

  • Bryant 569J - page 29

    29 C10918 Fig. 26 - - 569J*14D/E Charging Chart (Novation) 569J ...

  • Bryant 569J - page 30

    30 C10919 Fig. 27 - - 569J*07A/B Charging Chart (R TP F) C10920 Fig. 28 - - 569J*08A/B Charging Chart (R TP F) 569J ...

  • Bryant 569J - page 31

    31 C10921 Fig. 29 - - 569J*12A/B Charging Chart (R TP F) C11093 Fig. 30 - - 569J*14A/B Charging Chart (R TP F) 569J ...

  • Bryant 569J - page 32

    32 C10923 Fig. 31 - - 569J*12D/E Charging Chart (R TP F) 569J ...

  • Bryant 569J - page 33

    33 C11094 Fig. 32 - - 569J*14D/E Charging Chart (R TP F) 569J ...

  • Bryant 569J - page 34

    34 C10925 Fig. 33 - - T ypical 569J***A/B Wiring Diagram 569J ...

  • Bryant 569J - page 35

    35 C10926 Fig. 34 - - T ypical 569J***D/E Wiring Diagram 569J ...

  • Bryant 569J - page 36

    36 OPERA T ING SEQUENCE Base Unit Controls Indoor (Supply ) Fan — The indoor fa n contact or (IFC) is remotely l ocated at the fan coil or fan s ection. If the ther mostat fan o peration is selected as Continuous, the IFC is e ner gize d and the indoor (supply) fan motor runs continuously . If t he thermosta t fa n operation is selected as Au tom ...

  • Bryant 569J - page 37

    37 ROUTINE SYSTEM MAINTENANCE These ite ms s hould be part of a routine m aintena nce prog ram, to be checked ever y month or tw o, until a specif ic sched ule for each can be iden tified for th is ins tallation: Quarterl y Ins pection (and 30 days after initial start) — Ind oor section S Condenser c oil cl eanline ss checked. S Return air f ilte ...

  • Bryant 569J - page 38

    38 Liq uid Line Filt er Drier — The factory -pro vided filter d rier is s pecifically desig ned to operate w ith Puro n ® . Replace the filter dr ier with factory-authori zed components onl y with a filter drier with desiccant made from 100% molecular sieve grade XH -1 1. Filter dr ier must be replaced whenev er the refrigera nt sys tem i s open ...

  • Bryant 569J - page 39

    39 Comfort Alert Diagnostic Module The Comfort Alert Diagnostic Module (CAD M) monitors and anal yzes data from the Copela nd Scroll ® three- phas e compressor and the the rmostat dema nd. The CADM also prov ides a 3 -minute an ti-recycle time d elay to compres sor cycli ng. Ea ch compre ss or has a separate CAD M module . The CAD M detects caus e ...

  • Bryant 569J - page 40

    40 T abl e 12 – LE D Status Codes Status LED Status LED Descr iption Stat us LED T roub lesh oot ing In format ion Green “PO WER” Mod ule h as pow er Supp l y v ol tage is p resent at module terminals Red “TRIP” LED On Sol id The rmostat de mand sign al Y is prese nt, but the com - pres sor i s not runni ng. 1. Compressor protect or is op ...

  • Bryant 569J - page 41

    41 T abl e 13 – CADM T roubl eshoo ting Miswi red Module Indic ation Reco mmended T roubles hooti ng Action Green L ED is not on, mo dule does no t power up Determi ne if both R and C module terminals are co nnected. Verify voltage in present at module’s R and C termi nals. NOT E: The CADM re quires a c ons tant no minal 2 4V AC power s upply . ...

  • Bryant 569J - page 42

    42 Condenser Fans Service V alves C10927 Fig. 38 - - T ypical Exter ior , Single - - Circuit Unit (569J*08A/B shown ) 32L T Sensor T ypical Location (NOV A TION coil model) Outdoor Coil HPS LPS High Flow Access Port C10928A Fig. 39 - - T ypical Interior , Single - - Circuit Unit (569J*08A/B show n) 569J ...

  • Bryant 569J - page 43

    43 Condenser Fans Service V alves C10929 Fig. 40 - - T ypical Exter ior , T wo - - Circuit Un it (569J*14D/E shown) HPS LPS Motormaster Sensor Location (NOV A TION coil model) Outdoor Coil CKT 2 CKT 1 1 1 2 2 High Flow Access Ports C10930A Fig. 41 - - T ypical Interior , T wo- - Circuit Unit (569J*14D/E sh own) 569J ...

  • Bryant 569J - page 44

    44 Coil T ype Identifica tion 569J units are avail able wit h different coi l t ypes. Cle aning methods dif fer for each type so identifying the coil type is importa nt. Unit model numbe r and a ppearance can i dentify the coi l type. NOV A TION t Ty p e — The new NOV A T ION H eat Excha nger T echnol ogy i s an all - - alumi num construc tion wi ...

  • Bryant 569J - page 45

    45 The rep air pro cedure r equires the use of M AP P gas and torch (must be suppli ed by servicer) i nstead of conventional oxyacety lene fu el and tor ch. While the flame temperatur e for M AP P is lo wer than th at of o xyacetylen e (and thus prov ides mor e flexibility w hen wo rking on aluminu m), the flame temperatu re is s till higher than t ...

  • Bryant 569J - page 46

    46 7. Hold ga rden sprayer nozzl e close to fi nned a reas and apply c leaner wit h a ve rtical , up-and-down motion. A void sp raying in h orizon tal pattern to minimize po- tential for fin d amage. 8. E nsure cleane r thoroughly penet rates deep i nto finned areas . 9. Int erior and exteri or finned a reas must be t horoughly cleaned. 10. Finned ...

  • Bryant 569J - page 47

    47 TROUBLESHOOTING (cont ) PROBLEM SOLUTION COMP RESSOR CYCLES ON L OW- PRESSURE SWITCH Indoor-Air Fan Running 1. Li q ui d lin e so le n oid v a lv e( s) f a ils to o pe n . 1. Ch eck liquid line solenoid val ve(s) for proper operation. Replace if neces sary . 2. Fil ter dri er pl ugged. 2. Repl ac e fil te r drie r . 3. Expan si on valve power he ...

  • Bryant 569J - page 48

    48 APP ENDIX A Air Conditioner & Hea t P ump with PURON ® — Quick Reference Guid e S Puro n ® (R-410A) refrigerant opera tes at 50 percent to 70 perce nt higher pressures than R-22. Be sure that servicing equipment and replacement c omponents are designed to ope rate with Puron ® . S Puro n ® refrigera nt cylinders are rose colore d. S Re ...

  • Bryant 569J - page 49

    49 APP ENDIX C Low Ambie nt Option — Factory Installed Units with th e factory ins talled low ambient option are equippe d with a Motormaster R so lid - - st ate h ead p ressur e contr ol which r egulates f an speed . A temperatur e sens or , mounted on c ircuit 1 of t he outdoor coil (see Figs. 44 through 47) control s the speed of approved outd ...

  • Bryant 569J - page 50

    50 20 in (508 mm) Sensor C10931 Fig. 44 - - 569J***A/B Motormaster Sensor Location (All Sizes - - Novation) 10 in (254 mm) Sensor C10932 Fig. 45 - - 569J*12 - - 14D/E Motormaster Sensor Location (Novation) 569J ...

  • Bryant 569J - page 51

    51 569J*07-08A/B 569J*12A/B 569J*14A/B C11098 Fig. 46 - - 569J*07 - - 14A/B Motormaster Sens or Loc ation (R TPF) 569J ...

  • Bryant 569J - page 52

    52 569J*12D/E 569J*14D/E C11099 Fig. 47 - - 569J*12 - - 14D/E Motormaster Sens or Loc ation (R TPF) 569J ...

  • Bryant 569J - page 53

    53 D K J H G F E C B A C10800 Fig. 48 - - W ind Baff le s 569J ...

  • Bryant 569J - page 54

    54 T a b l e1 5–W i n dB a f f l eD i m e n s i o n DIM ENS IONS - - - INC H ES UNI T BAFFLE A B C D E F G H J K 569J*07A/ B (MCHX) LEFT SI DE 32 1 / 2 33 1 / 4 34 35 1 / 4 6 18 34 1 / 8 --- --- --- BACK 40 1 / 2 41 1 / 4 42 35 1 / 4 4 1 / 2 18 32 5 / 8 --- --- --- 569J*08A/ B (MCHX) LEFT SI DE 44 1 / 2 45 1 / 4 46 35 1 / 4 6 18 34 1 / 8 --- --- ...

  • Bryant 569J - page 55

    55 ST AR T -UP CHECKLIST I. P RELIMINAR Y INFORMA TION OUTDOOR: MODE L NO. SERI AL NO. INDOOR: AIRHANDL ER MANUF ACT URER MODEL NO. SERI AL NO. ADDITI ONAL ACCESSOR IES II. PRE-ST AR T -UP OUTDOOR UNIT IS THE RE ANY SHI PPING DAMAGE? (Y/N) IF SO, WHERE: WI LL THI S DAMAGE PRE VENT UNIT ST AR T -UP? (Y/ N) CHEC K POWER SUPPL Y . DOE S IT AGRE E W IT ...

  • Bryant 569J - page 56

    56 CHECK VOL T AGE IMBALANCE LINE -TO-LI NE VOL T S: AB V AC V BC V (AB + AC + BC)/ 3 = A VERAGE VOL T AGE = V MAXIMUM DEVI A TI ON FROM A VER AGE VOL T AGE = V VOL T AGE IMBAL ANCE = 100 X (MAX DEVIA T ION)/( A VERAGE VOL T AGE ) = IF O VER 2% V OL T AG E IMB ALA NCE, D O N OT A TTEMPT T O ST AR T SYS TEM! CALL L OCAL POW ER COMP ANY FOR ASSIST AN ...

Manufacturer Bryant Category Fan

Documents that we receive from a manufacturer of a Bryant 569J can be divided into several groups. They are, among others:
- Bryant technical drawings
- 569J manuals
- Bryant product data sheets
- information booklets
- or energy labels Bryant 569J
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bryant 569J.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bryant 569J, service manual, brief instructions and user manuals Bryant 569J. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bryant 569J.

Similar manuals

A complete manual for the device Bryant 569J, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bryant 569J by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bryant 569J.

A complete Bryant manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bryant 569J - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bryant 569J, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bryant 569J, that we can find in the current document
3. Tips how to use the basic functions of the device Bryant 569J - which should help us in our first steps of using Bryant 569J
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bryant 569J
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bryant 569J in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bryant 569J?

Use the form below

If you did not solve your problem by using a manual Bryant 569J, ask a question using the form below. If a user had a similar problem with Bryant 569J it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)