    Form No. PDS 698B.24.1 TWO-SPEED PURON® PLUS™ ELECTRIC HEAT PUMP 698B (60 HZ) Sizes 024, 036, 048, and 060 • T W O - S P E E D • ™ Model 698B Heat Pumps incor porate innov ativ e 2-speed com- pressor technology with Puron ® , the refrigerant of the future, to provide quiet, ef fi cient cooling perf ormance. Built into these units are f e ...

  • Bryant 698B - page 2

    — 2 — DIMENSIONS A01063 DIMENSIONS (IN.) SOUND PO WER (dBA) *Sound lev els are equivalent at high and low speeds. UNIT SIZE SERIES A B C D E F G H K L M N MINIMUM MOUNTING P AD DIMENSIONS 024 A 33-13/16 22-1/2 26-3/16 4-1/8 7-1/8 21-15/16 28-3/8 5/8 12 13-3/4 12 2-3/8 20 x 27 036 A 27-13/16 30 33 5-1/16 9-11/16 15-15/16 22-3/8 3/4 16-1/4 14 13- ...

  • Bryant 698B - page 3

    — 3 — RECOMMENDED TUBE DIAMETERS NO TE: Maximum long-line tube length of 50 ft liquid and v apor line sets indicated abov e must be f ollowed on all applications . Over 50 ft or 20 ft vertical differential, refer to Application Guideline and Service Manual — Air Conditioners and Heat Pumps Using Puron ® Refrigerant. UNIT SIZE TUBE LENGTH (Ft ...

  • Bryant 698B - page 4

    — 4 — SPECIFICA TIONS * P ermissible limits of the voltage r ange at which the unit will operate satisf actorily . Oper ation outside these limits ma y result in unit failure . † If wire is applied at ambient greater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70). The ampacity of nonmetallic-sheathed cab le (NM), tra ...

  • Bryant 698B - page 5

    — 5 — OPTIONAL EQUIPMENT DESCRIPTION AND USA GE (Listed Alphabetically) 1. Coastal Filter A mesh screen inser ted under the top cov er and inside the base pan to protect the condenser coil from salt damage without restricting air fl ow . SUGGESTED USE:In geographic areas where salt damage could occur . 2. Snow Stand Coated wire rac k which sup ...

  • Bryant 698B - page 6

    — 6 — COMBINA TION RA TINGS UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Lo w High Low High Lo w High Low High Low High Low 024-A FV4ANF002* 735 440 24,000 12,000 14.0 11.0 21,000 10,600 3.38 3.40 12,400 4400 2.34 1.52 7.8 CC5A/CD5AA024 750 450 22,000 11,800 11.5 9.5 20,400 1 ...

  • Bryant 698B - page 7

    — 7 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 036-A FK4CNF001 1100 660 33,600 17,200 14.0 10.7 32,600 15,400 3.12 3.50 18,500 7300 2.32 1.78 8.1 FK4CNF002 1100 660 34,000 17,400 14.5 10.8 33,400 15,600 3.26 3.56 18,800 730 ...

  • Bryant 698B - page 8

    — 8 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 036-A CK5A/CK5BA048 1100 700 34,800 17,600 15.0 11.6 32,400 15,800 3.32 3.66 18,400 7300 2.46 1.82 8.7 CK5A/CK5BT042 1100 700 34,400 17,600 15.0 11.5 32,000 15,600 3.26 3.62 18 ...

  • Bryant 698B - page 9

    — 9 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 036-A CC5A/CD5AB042 1200 800 34,600 17,600 14.5 11.2 32,800 15,800 3.20 3.58 18,700 7500 2.38 1.80 8.3 CC5A/CD5A C048 1200 800 34,200 17,400 14.5 11.1 32,000 15,600 3.08 3.52 1 ...

  • Bryant 698B - page 10

    — 10 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 048-A CK5A/CK5BN060 1470 910 45,500 24,000 14.5 11.0 42,500 24,000 3.06 3.62 27,800 14,000 2.58 2.22 9.0 CK5A/CK5BT048 1470 910 44,000 24,000 14.0 10.6 42,000 24,000 3.02 3.52 ...

  • Bryant 698B - page 11

    — 11 — * Ratings are net values re fl ecting the eff ects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on: Cooling Standard: 80 ° F (27 ° C) db 67 ° F (19 ° C) wb indoor entering air temperature and 95 ° F (35 ° C) db air entering outdoor unit. High-T emp Heating Standard: 70 ° F (21 ° C) db in ...

  • Bryant 698B - page 12

    — 12 — 698BNX BALANCE POINT WORKSHEET BUILDING H EAT LO SS, 1000 BTU / HR UN I T I NTEGRATED HEATING C APACITY, 1000 BTU/HR P rinte d in U .S.A . OUTDOOR TEMPERATURE, ° F -10 0 10 20 30 40 50 60 70 80 2.9 5.9 8.8 11.7 14.7 17.6 20.5 70 60 50 40 30 20 10 KW BASED ON INDOOR ENT. AIR AT 70 ∞ F AND AT RATED CFM 23. 4 80 A - 698BNX024 / FV4ANF002 ...

  • Bryant 698B - page 13

    — 13 — DET AILED COOLING CAP A CITIES* See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacit ...

  • Bryant 698B - page 14

    — 14 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 15

    — 15 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 16

    — 16 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 17

    — 17 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 18

    — 18 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 19

    — 19 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 20

    — 20 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 21

    — 21 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 22

    — 22 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 23

    — 23 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 24

    — 24 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 25

    — 25 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 26

    — 26 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 27

    — 27 — DET AILED COOLING CAP A CITIES* continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length is used and/or indoor unit is located abov e outdoor unit, a slight v ariation in capacity may occur . † T otal and sensible capacities are net capa ...

  • Bryant 698B - page 28

    — 28 — HEA T PUMP HEA TING PERFORMANCE See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh ...

  • Bryant 698B - page 29

    — 29 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K ...

  • Bryant 698B - page 30

    — 30 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac ...

  • Bryant 698B - page 31

    — 31 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac ...

  • Bryant 698B - page 32

    — 32 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac ...

  • Bryant 698B - page 33

    — 33 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K ...

  • Bryant 698B - page 34

    — 34 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K ...

  • Bryant 698B - page 35

    — 35 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K ...

  • Bryant 698B - page 36

    — 36 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac ...

  • Bryant 698B - page 37

    — 37 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac ...

  • Bryant 698B - page 38

    — 38 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K ...

  • Bryant 698B - page 39

    — 39 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K ...

  • Bryant 698B - page 40

    — 40 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac ...

  • Bryant 698B - page 41

    — 41 — HEA T PUMP HEA TING PERFORMANCE continued * The Btuh heating capacity values sho wn are net “ integrated ” values from which the defrost eff ect has been subtracted. The Btuh heating from supplement heaters should be added to those v alues to obtain total system capacity . † The kW values include the compressor , outdoor f an motor ...

  • Bryant 698B - page 42

    — 42 — ...

  • Bryant 698B - page 43

    — 43 — ...

  • Bryant 698B - page 44

    — 44 — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: New © 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls., IN 46231 PRINTED IN U.S.A. Catalog No. 5269-803 4-01 ...

Manufacturer Bryant Category Heat Pump

Documents that we receive from a manufacturer of a Bryant 698B can be divided into several groups. They are, among others:
- Bryant technical drawings
- 698B manuals
- Bryant product data sheets
- information booklets
- or energy labels Bryant 698B
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bryant 698B.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bryant 698B, service manual, brief instructions and user manuals Bryant 698B. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bryant 698B.

A complete manual for the device Bryant 698B, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bryant 698B by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bryant 698B.

A complete Bryant manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bryant 698B - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bryant 698B, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bryant 698B, that we can find in the current document
3. Tips how to use the basic functions of the device Bryant 698B - which should help us in our first steps of using Bryant 698B
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bryant 698B
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bryant 698B in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bryant 698B?

Use the form below

If you did not solve your problem by using a manual Bryant 698B, ask a question using the form below. If a user had a similar problem with Bryant 698B it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)