    SINGLE-PACKAGE GAS HEATING/ELECTRIC COOLING UNITS Model 583B Sizes 024-060 2 to 5 Nominal Tons Low NOx Models Available Form No. PDS 583B.24.3 Single-Package Rooftop Products with Energy-Saving Features and Puron® refrigerant. • Direct Spark Ignition • Low Sound Levels • Up to 81% AFUE • 12 SEER • Variable Speed Blower Option FEATURES/BE ...

  • Bryant PURON 583B - page 2

    — 2 — Corporate thermostats include the Time Guard ® II anti-short cycle protection circuitry. If a non-corporate thermostat without anti-short cycle protection is used the Time Guard II field in- stalled anti-short cycle kit is recommended. Refrigerant system is designed to provide dependability. Liquid filter dryers are used to promote clean ...

  • Bryant PURON 583B - page 3

    — 3 — ARI* CAPACITIES COOLING CAPACITIES AND EFFICIENCIES UNIT 583B NOMINAL T ONS ST ANDARD CFM NET COOLING CAP A CITIES (Btuh) SEER† SOUND RA TINGS** (dB) 024040 024060 2 800 24,000 12.0 72 030040 036060 2-1/2 1000 29,000 12.0 72 036060 036090 3 1200 35,000 12.0 72 042060 042090 3-1/2 1400 41,000 12.0 73 048090 048115 048130 4 1600 48,000 12 ...

  • Bryant PURON 583B - page 4

    — 4 — ARI* CAPACITIES (cont) HEATING CAPACITIES AND EFFICIENCIES LEGEND AFUE — Annual Fuel Utilization Efficiency NOTE: Before purchasing this appliance, read important energy cost and efficiency information available from your retailer. OUTDOOR SOUND: OCTAVE BAND DATA — DECIBELS (Lw(A)) UNIT 583B HEA TING INPUT (Btuh) OUTPUT CAP A CITY (Bt ...

  • Bryant PURON 583B - page 5

    — 5 — PHYSICAL DATA UNIT SIZE 583B 024040 024060 030040 030060 036060 036090 042060 042090 NOMINAL CAP A CITY (ton) 2 2 2-1/2 2-1/2 3 3 3-1/2 3-1/2 OPERA TING WEIGHT (lb) 290 290 313 313 321 321 382 382 COMPRESSORS Scroll Quantity 1 REFRIGERANT (R-410A) Quantity (lb) 5.0 5.0 5.5 5.5 6.9 6.9 9.0 9.0 REFRIGERANT METERING DEVICE Ori fi ce ID (in. ...

  • Bryant PURON 583B - page 6

    — 6 — PHYSICAL DATA (cont) UNIT SIZE 583B 048090 048115 048130 060090 060115 060130 NOMINAL CAP A CITY (ton) 444555 OPERA TING WEIGHT (lb) 421 421 421 468 468 468 COMPRESSORS Scroll Quantity 1 REFRIGERANT (R-410A) Quantity (lb) 9.5 9.5 9.5 10.0 10.0 10.0 REFRIGERANT METERING DEVICE Ori fi ce ID (in.) AccuRater ® Piston .073 .073 .073 .086 .08 ...

  • Bryant PURON 583B - page 7

    — 7 — OPTIONS AND ACCESSORIES Factory-installed options Coil options include copper/copper and vinyl-coated construc- tion for refrigerant coils. Units are shipped standard with copper tube/aluminum fin construction. See model number nomencla- ture for coil options. Electronic Variable-Speed Motor — ICM Motors (Integrated Control Motor) provi ...

  • Bryant PURON 583B - page 8

    — 8 — A99315 Filter Rack A99316 DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT P ANEL Manual Outside Air Damper A99317 Economizer A99314 ...

  • Bryant PURON 583B - page 9

    — 9 — BASE UNIT DIMENSIONS — 583B024-036 REQ ’ D CLEARANCES FOR OPERA TION AND SERVICING. in. (mm) Evaporator coil access side .................. 3 6 (914) P ower entry side (except for NEC requirements) ......... 3 6 (914) Unit top .......................... 4 8 (1219) Side opposite ducts ..................... 3 6 (914) Duct panel ........ ...

  • Bryant PURON 583B - page 10

    — 10 — REQUIRED CLEARANCE FOR OPERA TION AND SERVICING in. [mm] EV AP . COIL ACCESS SIDE..............................................................36.00 [914.0] POWER ENTR Y SIDE ......................................................................36.00 [914.0] (EXCEPT FOR NEC REQUIREMENTS) UNIT T OP ........................................ ...

  • Bryant PURON 583B - page 11

    — 11 — ACCESSORY DIMENSIONS Gasket around outer edge Insulated deck pan Gasket around duct S/A R/A HV AC unit base *Gasketing outer flange Flashing field supplied Roofing material field supplied Cant strip field supplied *Provided with roofcurb Roof Duct work field supplied Insulation (field supplied) Roofcurb* Wood nailer* Gasketing inner flan ...

  • Bryant PURON 583B - page 12

    — 12 — SELECTION PROCEDURE (WITH E XAMPLE) I DETERMINE COOLING AND HEATING REQUIREMENTS AT DESIGN CONDITIONS: Given: Required Cooling Capacity (TC).....................35,000 Btuh Sensible Heat Capacity (SHC).........................25,000 Btuh Required Heating Capacity..............................60,000 Btuh Condenser Entering Air Temperature ...

  • Bryant PURON 583B - page 13

    — 13 — PERFORMANCE DATA STANDARD INDOOR PSC MOTOR COOLING CAPACITIES 583B024 COOLING PERFORMANCE T ABLE T emp (F) Outdoor Air Entering Condenser Evaporator Air — CFM / BF 600 / 0.08 800 / 0.10 1000 / 0.12 Evaporator Air — Ewb (F) 62 67 72 62 67 72 62 67 72 75 TC SHC kW 23.7 19.6 1.74 26.0 16.8 1.76 28.1 13.9 1.78 24.7 22.3 1.88 26.9 18.6 1. ...

  • Bryant PURON 583B - page 14

    — 14 — PERFORMANCE DATA (cont) STANDARD INDOOR PSC MOTOR COOLING CAPACITIES (cont) See Legend and Notes on page 15. 583B036 COOLING PERFORMANCE T ABLE T emp (F) Outdoor Air Entering Condenser Evaporator Air — CFM/BF 900/0.09 1200/0.13 1500/0.18 Evaporator Air — Ewb (F) 62 67 72 62 67 72 62 67 72 75 TC SHC kW 35.2 30.3 2.58 38.7 25.5 2.61 41 ...

  • Bryant PURON 583B - page 15

    — 15 — PERFORMANCE DATA (cont) STANDARD INDOOR PSC MOTOR COOLING CAPACITIES (cont) 583B048 COOLING PERFORMANCE T ABLE T emp (F) Outdoor Air Entering Condenser Evaporator Air — CFM/BF 1200 / 0.06 1600 / 0.08 2000 / 0.11 Evaporator Air — Ewb (F) 62 67 72 62 67 72 62 67 72 75 TC SHC kW 47.9 41.5 3.38 52.3 34.8 3.43 56.8 28.2 3.48 49.6 47.4 3.6 ...

  • Bryant PURON 583B - page 16

    — 16 — 583B STANDARD UNIT — WET COIL AIR FLOW DELIVERY NOTE: *Air delivery values are without air filter. Deduct field-supplied air filter pressure drop to obtain external static pressure available for ducting. Deduct 10% for 208 volts. Dashes indicate portions of table that are not recommended. 230 AND 460 VOL T Unit 583B Motor Speed Externa ...

  • Bryant PURON 583B - page 17

    — 17 — 583B COOLING DRY COIL ICM AIRFLOW — SMALL CABINET 583B COOLING DRY COIL ICM AIRFLOW — LARGE CABINET 583B HEATING ICM AIRFLOW — SMALL CABINET 583B HEATING ICM AIRFLOW — LARGE CABINET UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC PRESSURE RANGE 0.0 – 0.4 0.4 – 0.7 0.7 – 1.0 0.0 – 0.4 0.4 – 0.7 0.7 ...

  • Bryant PURON 583B - page 18

    — 18 — 583B ICM AIR FLOW VS. TEMPERATURE RISE CHART PERFORMANCE DATA (CONT) ECONOMIZER/1-IN. FIL TER PRESSURE DROP (in. wg) UNIT COOLING SIZE RA TED GAS INPUT RA TE (X 1000) AIRFLO W SETTING EAST SELECT ™ (SCFM) CALCULA TED TEMPERA TURE RISE MIN. TEMP RISE MAX TEMP RISE MAX DISCH. TEMP 583B 024 40 800 36.5 20 50 175 583B 024 60 1100 40 35 65 ...

  • Bryant PURON 583B - page 19

    — 19 — TYPICAL PIPING AND WIRING INDOOR THERMOST A T DISCONNECT PER NEC* FROM POWER SOURCE RETURN AIR T OP CO VER FROM GAS LINE *NEC - NA TIONAL ELECTRICAL CODE ROOF RETURN-AIR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BO X (FIELD-SUPPLIED) SUPPL Y -AIR FLEXIBLE DUCT ROOF-MOUNTING CURB C00022 C00023 ...

  • Bryant PURON 583B - page 20

    — 20 — APPLICATION DATA Condensate trap — A 2-in. condensate tr ap must be fi eld supplied. Ductwork — Secure down fl ow discharge ductwork to roof curb . For horizontal discharge applications, attach ductwork to unit with fl anges. T o con vert a unit to down fl ow dischar ge — Units are equipped with f actor y-installed inser ts in ...

  • Bryant PURON 583B - page 21

    — 21 — 4 5 2=5v 4 5 7=7v 4 5 5=2v LEGEND FLA — Full Load Amps LRA — Lock ed Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Ov ercurrent Protection RLA — Rated Load Amps NO TES: 1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Ar ticles 430 and 440), the ...

  • Bryant PURON 583B - page 22

    — 22 — TYPICAL WIRING SCHEMATIC — 208/230-1-60 SHOWN C99076 ...

  • Bryant PURON 583B - page 23

    — 23 — TYPICAL WIRING SCHEMATIC — 208/230-3-60 SHOWN C99077 ...

  • Bryant PURON 583B - page 24

    — 24 — TYPICAL WIRING SCHEMATIC — 460-3-60 SHOWN C99078 ...

  • Bryant PURON 583B - page 25

    — 25 — ICM FIOP WIRING SCHEMATIC — 208/230-1-60 YEL BLK YEL BLU YEL YEL BLK BRN I BLK ...

  • Bryant PURON 583B - page 26

    — 26 — OPERATING SEQUENCE Heating — On a call for heating, terminal “ W ” of the thermostat is energized, starting the induced-draft motor. When the hall- effect sensor on the induced-draft motor senses that it has reached the required speed, the burner sequence begins. This function is performed by the integrated gas control (IGC). The e ...

  • Bryant PURON 583B - page 27

    — 27 — PACKAGED GAS HEATING/ELECTRIC COOLING UNITS CONSTANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONS SIZE RANGE: 2 TO 5 TONS, NOMINAL COOLING 40,000 TO 130,000 BTUH, NOMINAL HEATING INPUT BRYANT MODEL NUMBER: 583B PART 1 — GENERAL 1.01 SYSTEM DESCRIPTION Outdoor rooftop mounted, gas heating/electric cooling unit utilizing a scroll compres ...

  • Bryant PURON 583B - page 28

    — 28 — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 583B.24.2 Form PDS 583B.24.3 © 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 PRINTED IN U.S.A. Catalog No. 5258-305 5-01 K. Electrical Requirements: All unit power wiring sha ...

Manufacturer Bryant Category Fan

Documents that we receive from a manufacturer of a Bryant PURON 583B can be divided into several groups. They are, among others:
- Bryant technical drawings
- PURON 583B manuals
- Bryant product data sheets
- information booklets
- or energy labels Bryant PURON 583B
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bryant PURON 583B.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bryant PURON 583B, service manual, brief instructions and user manuals Bryant PURON 583B. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bryant PURON 583B.

Similar manuals

A complete manual for the device Bryant PURON 583B, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bryant PURON 583B by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bryant PURON 583B.

A complete Bryant manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bryant PURON 583B - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bryant PURON 583B, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bryant PURON 583B, that we can find in the current document
3. Tips how to use the basic functions of the device Bryant PURON 583B - which should help us in our first steps of using Bryant PURON 583B
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bryant PURON 583B
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bryant PURON 583B in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bryant PURON 583B?

Use the form below

If you did not solve your problem by using a manual Bryant PURON 583B, ask a question using the form below. If a user had a similar problem with Bryant PURON 583B it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)