Manual Liebert 130 kVA

102 pages 0.59 mb
Download

Go to site of 102

Summary
  • Liebert 130 kVA - page 1

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V User Manual – Hipulse Installation & Maintenance of Hipulse 130 kVA Single phase 110V , Single & 1 + N System ...

  • Liebert 130 kVA - page 2

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V ...

  • Liebert 130 kVA - page 3

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V Dear Customer, Please accept our thanks for giving us the privilege to serve you by choosing a Liebert make ‘UPS’. If this is your f irst Liebert UPS, we hope it is the beginning of a long relationship which delivers value to your organisation. If you already own and use a L ...

  • Liebert 130 kVA - page 4

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V ...

  • Liebert 130 kVA - page 5

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V Rev. No. Revision details Date IMPORTANT This manual contains information concerning the installation, operation and maintenance of the Hipulse Uninterruptible Pow er System (UPS) for the single module and one plus one Systems. All relevant parts of the manual should be read pri ...

  • Liebert 130 kVA - page 6

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V ...

  • Liebert 130 kVA - page 7

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V REGISTERED HEAD OFFICE Emerson Network Power (India) Private Limited PLOT NO. C - 20, ROAD NO. 19 WAGLE INDUSTRIAL ESTATE THANE – 400 604 MAHARASHTRA, INDIA TELEPHONE: (00 91 2 2) 25807000/ 25828405 / 25802388 FAX: (00 91 22) 25800829 / 25828358 *** WEST ZONE *** Mumbai Addres ...

  • Liebert 130 kVA - page 8

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V ...

  • Liebert 130 kVA - page 9

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V *** EAST ZONE *** Kolkatta Address: Jindal Towers, 21/1A/3, Darga Road, Kolkata - 700 017 Tel: 91 - 33 - 2289 0493 / 033 2289 0490 Fax: 91 - 33 - 2289 0492 Bhubaneshwar Addre ss: 69, Satya Nagar, Bhubaneshwar 751 007 Tel: 91 - 674 - 2520 778 Fax: 91 - 674 - 2520 778 Jamshedpur A ...

  • Liebert 130 kVA - page 10

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V ...

  • Liebert 130 kVA - page 11

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V Safety Procedure WARNING In a domestic environment, this product may cause radio interface in which cas e the user may be required to take additional measures. WARNING HIGH EARTH LEAKAGE CURRENT: EARTH CONNECTIONS IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY. This equipment m ...

  • Liebert 130 kVA - page 12

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V ...

  • Liebert 130 kVA - page 13

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V GENERAL As with other types o f high power equipment, dangerous voltages are present within the UPS and battery enclosure. The risk of contact with these is minimised as the live component parts are housed behind a hinged, lockable door. Further internal safety screens make the ...

  • Liebert 130 kVA - page 14

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V ...

  • Liebert 130 kVA - page 15

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 1 General Introduction 1 1.1 Introduction 1 1.2 Design Concept 1 1.2.1 Hipulse Module Design 1 1.2.2 Bypass Supplies 2 1.2.3 System control Philosophy 3 1.2.4 ECOMODE (for single UPS) 4 1.2.5 UPS Power Switch Configuration 5 1.2.6 Battery circuit breaker 5 1.2.7 Battery temperat ...

  • Liebert 130 kVA - page 16

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V ...

  • Liebert 130 kVA - page 17

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 5 Operating Instructions 31 5.1 Introduction 31 5.1.1 General Notes 31 5.1.2 Power switches 31 5.2 Procedure for UPS Startup: without interrupting 32 power to the load 5.3 Procedure for UPS Startup: without powe r initially 34 supplied to the load 5.4 Procedure for Switching the ...

  • Liebert 130 kVA - page 18

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V ...

  • Liebert 130 kVA - page 19

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 7 Display Panel Interpretation 55 7.1 LED Interpretation 55 7.2 Display Panel Messages 57 8 1 + N System 6 3 8.1 Ge neral 63 8.2 Installation Procedure 65 8.2.1 Preliminary Checks 65 8.2.2 Protective Devices 65 8.2.3 Power Cables 65 8.2.4 Control Cables 65 8.2.5 Battery Control ...

  • Liebert 130 kVA - page 20

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V ...

  • Liebert 130 kVA - page 21

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 1 CHAPTER 1 General Description 1.1 Introduction The Hipulse Uninterruptible Power Supply (UPS) System is connected between a critical load, such as a computer, and its t hree phase mains power supply. Being designed to furnish a well regulated 1 phase output power supply under ...

  • Liebert 130 kVA - page 22

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 2 During normal operation both the rectifier and inverter sections are active and provide regulated loa d power whilst simultaneously float charging the battery. In the event of a mains power failure, the rectifier becomes inoperative and the inverter is powered solely from the ...

  • Liebert 130 kVA - page 23

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 3 1.2.3 System Control Philosophy Normal Operation During normal operation, i.e. when the UPS input supply is presen t and within specification, both the rectifier and inverter sections are active and the static switch is turned on to connect the inverter output to the critical ...

  • Liebert 130 kVA - page 24

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 4 Overload In the event of an overload at the Inverter output which lasts longer than the typical time/ current (refer to Chapter 9 - Specifications), the Inverter will shut down and the Static Transfer Switch will automatically transfer the load onto the MSS Bypass Mains with n ...

  • Liebert 130 kVA - page 25

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 5 WARNING In ECOMODE the load is not protected against mains distortion. 1.2.5 UPS Power Switch Configurat ion Figure 1 - 2 illustrates the Hipulse UPS module in what is known as the "Split Bypass" configuration. In the Split Bypass configuration, the static bypass lin ...

  • Liebert 130 kVA - page 26

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 6 ...

  • Liebert 130 kVA - page 27

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 7 CHAPTER 2 Installa tion Procedure 2.1 Introduction WARNING Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer. WARNING The UPS equipment should be installed by a qualified engineer in accordance with the information contained in ...

  • Liebert 130 kVA - page 28

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 8 2.2 Environmental considerations 2.2.1 UPS location The UPS module should be located in a cool, dry, clean - air environment with adequate vent ilation to keep the ambient temperature within the specified operating range (see Chapter 9 - Specifications). All models in the ‘H ...

  • Liebert 130 kVA - page 29

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 9 2.3 Mechanical Considerations 2.3.1 System composition A UPS system can comprise a number of equipment cabinets, depending on the individual system design requirements - e.g. UPS cabinet, Battery cabinet. In general, all the cabinets used in a particular installation are of th ...

  • Liebert 130 kVA - page 30

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 10 2.4 Preliminary Checks Before you install the UPS hardware you should carry out the following preliminary checks: 1. Verify that the UPS room satisfies the environmental conditions stipulated in the equipment specification, paying particular attention to the ambient temperatu ...

  • Liebert 130 kVA - page 31

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 11 1903 1600 1750 4 5 1 LEFT SIDE VIEW FRONT VIEW REA R VIEW TOP VIEW Note - All dimensions are in mm 1. Rem ovable g r i l l fo r l ifti ng w ith fork - li f t truck 2. Air i nle t g ri ll 3. Rem ovable g r i l l – i f u si ng s ide cable ent ry 4. Coo l ing fan ass embly for ...

  • Liebert 130 kVA - page 32

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 12 A. CABLE ENTRY DETAILS FOUNDATION DETAILS Note: All dimensions are in mm Fig 2 - 2 : Cable entry and Foundation details for 130 kVA Single Phase UPS 125 570 90 800 1400 65 570 90 40 1220 660 1315 755 Dia 14.0 Holes 42.5 90 37.5 85 800 1400 ...

  • Liebert 130 kVA - page 33

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 13 CHAPTER 3 Inst allation (Electrical) The UPS requires both “Power” and “Control” cabling once it has been mechanically installed. All Control cables, whether screened or not, should be run separate from the Power cables in metal conduits or metal ducts which are elect ...

  • Liebert 130 kVA - page 34

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 14 3.1.2 Cable rating NOMINAL CURRENT (Amps) 3 Phase Input Mains with full battery re - charge (less 5% for 12 pulse) 1 Phase Output at full load Battery at minimum Battery Voltage UPS Rating (kVA) 380V 400V 415V 110V 115V 120V 380V 400V 415V 30 63 60 58 272 260 250 83 80 77.5 4 ...

  • Liebert 130 kVA - page 35

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 15 WARNING Failure to follow adequate earthing procedures can result in electric shock hazard to personnel, or the risk of f ire, should an earth fault occur. 3.1.6 Protective devices For safety reasons, it is necessary to install, external to the UPS, circuit breaking protectiv ...

  • Liebert 130 kVA - page 36

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 16 Parallel 1+N: Use of differential circuit breakers on UPS unit inputs in a configuration with separate inputs and one battery for each unit requires installation of a common device only on the System Bypass Mains. Use of differential circuit breakers on UPS unit inputs sharin ...

  • Liebert 130 kVA - page 37

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 17 WARNING If the load equipment will not be ready to accept power on the arrival of the commissioning engineer then en sure that the system output cables are safely isolated at their ends. 6. Connect the Battery cables between the UPS terminals (+/ - ) and its associated batter ...

  • Liebert 130 kVA - page 38

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 18 Fig 3 - 1 : Cable connections for 130 kVA 1Ph UPS U1 V1 W1 +VE - VE U3 N3 U2 N2 Q1 Q2 Q4 Q3 X4 X3 Q1 - INPUT SUPPLY Q2 - BY PASS ISOLATOR Q3 - MAINTENANCE BY PASS Q4 - OUTPUT ISOLATOR BATTERY INPUT BYP ASS OUTPUT Q3 Q1 Q2 Q4 ...

  • Liebert 130 kVA - page 39

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 19 3.2 Cont rol cables 3.2.1 Battery Control The battery circuit breaker is controlled by the Battery Circuit Breaker Controller Board which is located within the Input Transformer Cubicle - or adjacent to the Battery Circuit Breaker when the batteries are rack - mount ed. This ...

  • Liebert 130 kVA - page 40

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 20 3.2.2 Auxiliary Terminal Block X3 and X4 at UPS X3 terminal reference Reference label Description 2 Common Temperature sensor common (0V) 3 T Batt. Temperature sensor s ignal 4 Common Common (0V) 5 Batt. Sw. Battery circuit breaker trip control 6 Bat Trp Battery circuit break ...

  • Liebert 130 kVA - page 41

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 21 3.2.3 Emergency Stop If an external Emergency Stop facility is required it is connected to terminals 5 & 6 of the Auxiliary Terminal Block (X4) and connect the ‘normally closed’ remote stop switch between these two terminals using shielded cable. If this facility is n ...

  • Liebert 130 kVA - page 42

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 22 ...

  • Liebert 130 kVA - page 43

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 23 CHAPTER 4 Operator Control and Display Panel 4.1 Introduction On the front of the UPS there is a display and control panel, from which it is possible to easily verify the status of the UPS included all the meas ured parameters and alarms of the UPS and Battery. The operator c ...

  • Liebert 130 kVA - page 44

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 24 4.1.1 Operator control panel The control and display panel LEd indications are illustrated in figure 4 - 2 and described in th e following text: Mimic indications Six LED’s mounted on a single line diagram represents the various UPS power paths and show the current UPS oper ...

  • Liebert 130 kVA - page 45

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 25 Menu Control switches Four push button switches ESCape[9], DOWN [10], UP [11], ENTER [12], are located below the LCD display and are used to navigate a menu - driven UPS operating and control system. Note : In addition to entering the day - to - day operating functions, the m ...

  • Liebert 130 kVA - page 46

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 26 Pressing the ENTER button [12] from the Default Screen gives the operator access to t he ‘Measurements’ menu which facilitates access to the following measurements: Output Parameters - Output Voltage (L - N) - Output Current (L - N current displayed in Amperes or as a % L ...

  • Liebert 130 kVA - page 47

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 27 20. Emergency Stop - housed beneath a safety cover to prevent inadvertent operation. When the emergency stop switch is pressed it di sables the static switch block entirely (so removing load power). It also disables the rectifier and inverter, and trips the battery circuit br ...

  • Liebert 130 kVA - page 48

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 28 Fig 4 - 4: Map of screen display available to operator NORMAL O PERATI ON 11:15.50 01 . 02.98 NORMAL O PERATI ON 11:15.50 01 . 02.98 >MEASURE MENT < FUNCTION MAINTEN ANCE SETUP >MEASURE MENT < FUNCTION MAINTEN ANCE SETUP RECTIF. S WITCH OPEN OUTPUT S WITCH OPEN IN ...

  • Liebert 130 kVA - page 49

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 29 LCD Display Panel Messages Initializing Window After first connecting power to the UPS and closing the bypass A.C. input power switch, the INITIALIZATION message will appear on the LCD screen. It persists for about five seconds while the contro l firmware is loaded and the un ...

  • Liebert 130 kVA - page 50

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 30 The FUNCTION, MAINTENANCE and SETUP options all require a password w hich is set by the commissioning engineer. This manual does not provide servicing instructions and the options accessed from theses windows are therefore not shown on the menu map in figure 4 - 4. Only train ...

  • Liebert 130 kVA - page 51

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 31 CHAPTER 5 Operating Instructions 5.1 Introduction The UPS can be considered to be in one of three operating conditions: Normal operation All relevant power switches and circuit breakers closed, the load i s powered by the UPS. Shutdown All power switches and circuit breakers ...

  • Liebert 130 kVA - page 52

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 32 5.2 Procedure for UPS Star t - up: without interrupting power to the load This procedure will describe how to start the UPS and the how to transfer the load from the external maintenance bypass to the UPS inverter. It is assumed that the installation is complete, the system h ...

  • Liebert 130 kVA - page 53

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 33 The Display window will show the present status of the UPS 3. Close the Rectifier input power switch Q1. Note: In ECOMODE the messa ge 'LOAD ON BYPASS' will not appear. 4. Wait for 20 seconds then close the battery circuit breaker. This is located inside the battery ...

  • Liebert 130 kVA - page 54

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 34 5.3 Procedure for UPS Startup without power initially supplied to the load This procedure should be followed when turning on the UPS from fully powered down condition i.e. where the load is not being initially supplied at all. It i s assumed that the installation is complete, ...

  • Liebert 130 kVA - page 55

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 35 Select MEASUREMENT and press ENTER key. Select BATTERY and d.c. busbar voltage will be displayed: If the voltage indicated is satisfactory (432V d.c. for 380V a.c. system, 446VV d.c. for 400V a.c. system and 459V d.c. for a 41 5V a.c. system) press the Escape key repeatedly u ...

  • Liebert 130 kVA - page 56

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 36 5.4 Procedure for Switching the UPS into a Maintenance Bypass condition from normal operation The first part of this procedure details how to select the Inverter OFF and power the load from the bypass mains via the Static Switch. This procedure should be followed to transfer ...

  • Liebert 130 kVA - page 57

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 37 At this point the UPS inverter stops but the load continues to be supplied by the bypass mains. The Load on Mains indicator light (6) on the unit's synoptic panel flashes yellow, and the Load on Inverter indicator light (5) goes off. Your load is now powered via the Stat ...

  • Liebert 130 kVA - page 58

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 38 5.5 Procedure for Switching the UPS ON from a Maintenance Power condition. Follow the procedure for 'UPS startup: without interrupting power to the load' referring to the paragraph 5 .2, start from point number 2. 5.6 Procedure for completely powering down the UPS T ...

  • Liebert 130 kVA - page 59

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 39 WARNING Wait 5 minutes for the internal D.C. busbar capacitors to discharge. The UPS is now completely p owered down. IMPORTANT The Maintenance Bypass Power switch may be operated at any time when the UPS is powered down to connect the load to the maintenance bypass supply if ...

  • Liebert 130 kVA - page 60

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 40 Select NEXT PAGE and press ENTER key. Press the ENTER key. Select RESET ALARMS and press ENTER key. Return the Display window to normal by repea tedly pressing the ESCAPE key back through the various windows until the default screen is displayed. These operations resets the l ...

  • Liebert 130 kVA - page 61

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 41 5.9 Procedure to completely switch ON/ OFF the UPS at the UPS Display Control Panel: 1. From the Default window, press the ENTER key: the Main Menu window will display: 2. Select FUNCTION and press ENTER key: Before being allowed into the FUNCTION windows you are requested to ...

  • Liebert 130 kVA - page 62

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 42 The OFF selection will be highlighted, using the UP arrow key, rotate between the selecti ons offered (in this case it will be ON or OFF) select ON. Press the ENTER key to execute your order. After approximately 20 seconds, the Module Mimic will change so that the Load on Inv ...

  • Liebert 130 kVA - page 63

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 43 5.10 Procedure to switch ON/OFF the inverter at UPS display control panel CAUTION This operation gives the operator access to modify UPS’’s operating mode, it is advised that only traine d qualified personnel should attempt to do that. The display window will show the pre ...

  • Liebert 130 kVA - page 64

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 44 5.11 Setting the Battery Test A software - controlled battery facility c an be initiated from the Operator control Panel on an ‘immediate’ or ‘periodic’ basis. This test turns off the rectifier and runs the inverter (and load) from the battery from the predetermined p ...

  • Liebert 130 kVA - page 65

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 45 5.12 Language Selection : If required, select the appropriate language using the following procedure. From ‘Default’ window, press ENTER key. Se lect the FUNCTION and press the enter key. A password must be entered to gain a further access to next menu. The initial defaul ...

  • Liebert 130 kVA - page 66

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 46 ...

  • Liebert 130 kVA - page 67

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 47 CHAPTER 6 Battery Installation 6.1 Introduction The UPS battery consists of battery blocks connected in series to provide a nominal d.c. input voltage for the UPS inverter. The required ‘ Autonomy time’ (the time that battery can maintain supply to the load in the event o ...

  • Liebert 130 kVA - page 68

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 48 The following general battery safety precautions and WARINGS should be observed all the time. CAUTION • A battery can present risk of electric shock or burn from high short circuit currents. • When connected in a st ring the voltage could be 460 V d.c. this voltage is pot ...

  • Liebert 130 kVA - page 69

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 49 6.4 Installation design considerations Note: F ull safety instructions concerning the use and maintenance of UPS batteries are provided in the appropriate battery manufacturers’ manuals. The battery safety information contained in this section relates to the key considerati ...

  • Liebert 130 kVA - page 70

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 50 6.6 Battery protectio n The battery is connected to the UPS through a circuit breaker which is manually closed and electronically tripped via the UPS control circuitry. If the cells are cabinet mounted this circuit breaker is fitted within the cabinet, however, if they are r ...

  • Liebert 130 kVA - page 71

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 51 The battery cabinet also indicates the power and auxiliary connection cables (3 meters in length) between the cabinet and the UPS. Refer to section 3.3.1 to identify connections. Figure 6 - 1: A typical arrangement of Batteri es in a Battery Rack BATTERY SUPP LY TO UPS CAB IN ...

  • Liebert 130 kVA - page 72

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 52 6.8 Battery Installation Whatever the type of mounting system selected, following conditions should be noted: Layout of the cells: Whatever battery mounting system is used, the batteries should be laid out in such a manner as to make simultaneous contact with two exposed live ...

  • Liebert 130 kVA - page 73

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 53 Figure 6 - 3: Battery Control and Power Connections A – Half potential switching method B – Double positive pole method 3 2 1 V< + 1 2 3 4 5 6 7 8 9 10 11 12 X4 UPS CABIN ET BA TTERY CIRCU IT BREAKER X3 X4 X5 X6 X7 X8 X9 X2 X10 1 2 3 4 5 X1 Se n sor T emperature (Optio ...

  • Liebert 130 kVA - page 74

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 54 6.10 Battery temperature Board A battery / sensor card supplied separately from the battery circui t breaker is connected with the UPS logic through the battery circuit breaker card. With this feature fitted, the nominal float voltage supplied to the battery is adjusted so as ...

  • Liebert 130 kVA - page 75

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 55 CHAPTER 7 Display Panel Interpretation 7.1 LED Interpretation: The LED item number refers to details shown in the figure 7.1 below. LED N0. NORMAL STATE INTERPRETATIO N – ACTION 1. ON If this green led is OFF, it signifies a problem with the Bypass input a.c. Check the foll ...

  • Liebert 130 kVA - page 76

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 56 1. If [OVERTEM PERATURE] or [OVERLOAD] alarm messages are active then (after allowing the UPS to cool / checking that the load current on the Bypass line is not excessive) use the procedure to carry out the reset (see Chapter 5 – Operating Instructions). 2. Check that the c ...

  • Liebert 130 kVA - page 77

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 57 7.2 Display Panel Messages The message displayed on Hipulse can be categorized into types: - (a) ALARM messages - these are messages which needed urgent attention and warn of a UPS shutdown or imminent shutdown the load would normally transfer to the bypass supply if it is av ...

  • Liebert 130 kVA - page 78

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 58 overload present. 7. OVERLOAD SHUTDOWN This message informs the operator that the load has been transferred to bypass due to an inverter overload. 8. OUTPUT SWITCH OPEN This is a statu s alarm. The output switch must be selected ‘CLOSED’ at all times except when operating ...

  • Liebert 130 kVA - page 79

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 59 14. BATTERY: E.O.D. Battery discharge has continued beyond a preset value. The inverter will shut down, the system will attem pt a transfer to bypass. If Bypass is not available, any load connected to the UPS will be without power. 15. RECT. OFF The RECT. OFF alarm is active ...

  • Liebert 130 kVA - page 80

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 60 22. BATT ERY ON LOAD This is a status warning that the battery is discharging. It normally accompanies a [BYP: ABSENT] or [RECT: OFF] message. 23. AUTONOMY XXXX min The micro monitors the battery percentage capacity while on charge and the battery time remaining while on disc ...

  • Liebert 130 kVA - page 81

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 61 30. BYP: XFER COUNT BLOCK This message informs the operator that the load has been transferred to the bypass more than eight times in one minute. After eight transfers the load will remain on bypass. This message could be initiated by a load causing the UPS to overload, it re ...

  • Liebert 130 kVA - page 82

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 62 ...

  • Liebert 130 kVA - page 83

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 63 Chapter 8 1 + N System 8.1 General The system can comprise of up to 6 UPS mo dules of the same power rating and connected in parallel without the need for a centralized mains static bypass. Instead the bypass static switches of each UPS share the load when the system transfer ...

  • Liebert 130 kVA - page 84

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 64 Fig 8 - 1: '1+N' System block diagram with Separate Batteries RECTI FIER STATIC SWITCH INVER TER UPS 1 Output Supply Battery C .B. 1 Output I solator Q4 Input I solator Q1 Maintenance Bypass I solator Q3 Maintena n ce Bypass L ine Static Bypass Line Bypass I solator ...

  • Liebert 130 kVA - page 85

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 65 8.2 Installation procedure 8.2.1 Preliminary Checks Be sure that a parallel kit is present and fitted in each of the modules, and that the modules are of the same rating and with the same software and hardware release (see section 4.1.2 – Info window) WARNING Fitting of the ...

  • Liebert 130 kVA - page 86

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 66 8.2.5 Battery Control The system is designed to operate with separate battery configuration. Installation procedure is same as for single module. 8.2.6 Emergenc y Stop The external emergency stop facility is identical to that described for the single modules installation – ...

  • Liebert 130 kVA - page 87

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 67 8.3 Operating Instruction Starting and stopping the ‘1+N’ system is the same as a single module, however the module’s response depends on whether it is configured on the menu of the Operator Control Panel. 8.3.1 System Start - up and shutdown procedures (Separate Batter ...

  • Liebert 130 kVA - page 88

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 68 3. Close the Rectifier input power switch Q1 and UPS output power switch Q4. After approximately 20 seconds the Module Mimic led’s will change so that the Load on inverter will light (5 - steady green) and the Load on bypass (6) will extinguish. The display window will show ...

  • Liebert 130 kVA - page 89

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 69 8.3.1.2 Switching the sy stem to maintenance bypass from normal operation WARNING The internal maintenance bypass must not be used when the UPS system is comprised of more than two UPS modules in parallel. Follow the procedure for the single UPS by referring to Chapter 5 – ...

  • Liebert 130 kVA - page 90

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 70 8.3.1.5 Switching ON a UPS that was previously switched OFF and isolated from the system. 1. Close the circuit - breakers relative to the shutdown UPS that were previously opened on the power distribution switchboard. 2. Close the switches Q1 (rectifier input) and Q2 (bypass ...

  • Liebert 130 kVA - page 91

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 71 Chapter 9 Specification This specification describe requirements for an Uninterruptible Power System (UPS). 9.1 Conformity and Standard The UPS has been designed to conform the following standards: IEC, EN 9.2 UPS Environmental The UPS shall be able to operate under the follo ...

  • Liebert 130 kVA - page 92

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 72 9.4 UPS Electrical Characteristics R E C T I F I E R I N P U T M A I N S I/P Ratings Units 130 kVA 6 pulse Rated power kVA 130 Rated Mains Voltage j Vac 380 – 400 – 415 V Supply Three phase without neutral Input voltage tolerance k % ±10 Frequency Hz 50 or 60 Input frequ ...

  • Liebert 130 kVA - page 93

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 73 9.5 UPS Electrical Characteristics (DC Intermediate Circuit) D. C. I N T E R M E D I A T E C I R C U I T Rated Power kVA 130 Voltage range for Inver ter operation Vdc 340 – 480 Recommended number of - Lead - acid cells j - k - Ni - Cd cells j - k Nos. 190 (380 Vac) 198 (400 ...

  • Liebert 130 kVA - page 94

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 74 9.6 UPS Electrical Characteristics (Inverter Output) I N V E R T E R O U T P U T Rated Power kVA 130 Rated mains voltage j Vac 380 - 400 - 415 Three phase with neutral Frequency k Hz 50 to 60 Rated Power at cos φ = 0.8 KVA 130 Rated Power at cos φ = 1 KW 104 Overload % 150% ...

  • Liebert 130 kVA - page 95

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 75 9.7 UPS Electrical Characteristics (Bypass Input Mains) B Y P A S S I N P U T M A I N S Rated Power kVA 130 Rated mains voltage j Vac 38 0 - 400 - 415 Supply Three phase with neutral Rated Current: 110 Vac A 1182 Bypass voltage tolerance k % ± 10 Delay time to recognize bypa ...

  • Liebert 130 kVA - page 96

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 76 ...

  • Liebert 130 kVA - page 97

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 77 ...

  • Liebert 130 kVA - page 98

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 78 ...

  • Liebert 130 kVA - page 99

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 79 10.1 Remote Alarm Monitor The Remote Alarm Monitor (RAM) Board can be used in conjunction with the AS400 Alarms Interface Board to disp lay the UPS alarm and status information at a remote station to 100 meters from the UPS. The RAM, which can be mounted either horizontally o ...

  • Liebert 130 kVA - page 100

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 80 Figure 10.1: Remote Alarm Monitor connection details # 100201120003 Bypass Failure Low Battery Load on Mai ns Load on Maintenance Bypass Load on Inverter X4 RL – K1 RL – K2 RL – K3 RL – K4 RL – K5 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 5 4 3 2 1 9 8 7 6 UPS Monitor Lie ...

  • Liebert 130 kVA - page 101

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 81 10.2 INPUT TRANSFORMER CUBIC LE 10.2.1 Introduction The Input Transformer Cubicle is placed in the Input supply path of the UPS . It consist of Star - Star OR Delta - Star transformer of rated capacity to provide Isolation from the Input Distribution supply to the UPS input.. ...

  • Liebert 130 kVA - page 102

    User Manual Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V 82 10.3 BYPASS ISOLATION CUBICLE 10.3.1 Intr oduction Bypass Isolation Cubicle is placed in the Bypass input path of the UPS. It consist of VEE Connected – Transformer of rated capacity to provide 3 phase to 1 phase transformation . 10.3.2 Termination The Incoming Supply from ...

Manufacturer Liebert Category Power Supply

Documents that we receive from a manufacturer of a Liebert 130 kVA can be divided into several groups. They are, among others:
- Liebert technical drawings
- 130 kVA manuals
- Liebert product data sheets
- information booklets
- or energy labels Liebert 130 kVA
All of them are important, but the most important information from the point of view of use of the device are in the user manual Liebert 130 kVA.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Liebert 130 kVA, service manual, brief instructions and user manuals Liebert 130 kVA. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Liebert 130 kVA.

Similar manuals

A complete manual for the device Liebert 130 kVA, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Liebert 130 kVA by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Liebert 130 kVA.

A complete Liebert manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Liebert 130 kVA - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Liebert 130 kVA, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Liebert 130 kVA, that we can find in the current document
3. Tips how to use the basic functions of the device Liebert 130 kVA - which should help us in our first steps of using Liebert 130 kVA
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Liebert 130 kVA
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Liebert 130 kVA in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Liebert 130 kVA?

Use the form below

If you did not solve your problem by using a manual Liebert 130 kVA, ask a question using the form below. If a user had a similar problem with Liebert 130 kVA it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)