    05/05 505,050M *2P0505* *P505050M* Page 1 E 2005 Lennox Industries Inc. Dallas, T exas, USA RET AIN THESE INSTRUCTIONS FOR FUTURE REFERENCE 51M37 Merit ® Series Thermost at The Lennox Merit ® Series 5/2 day programmable electronic thermostat 51M37 provides excellent temperature control and a large, easy-to-read display . It includes a programmabl ...

  • Lennox International Inc. 51M37 - page 2

    Page 2 505050M 5/1/05 Within a few seconds, the Home Screen appears (see fig- ure 2) with default settings as shown. After about 1 minute of initialization time, the actual room temperature will be displayed. NOTE − T ables 2 and 3 on page 8 show all system and programming default s. I2:00 PROG A B C D HOLD FA N ON AUTO SYSTEM COOL OFF HEA T 70 H ...

  • Lennox International Inc. 51M37 - page 3

    Page 3 51M37 SERIES 5/2 HEA T − Using the Heat Mode Normal Heat Mode In normal heat mode, both the heat pump and the backup heat source are used to provide heat. If the thermost at d e- tects that the heat pump is not able to provide enough heat (as may be the case in very cold weather), then the backup heat source is activated. Emergency Heat Mo ...

  • Lennox International Inc. 51M37 - page 4

    Page 4 505050M 5/1/05 COOL − Using the Cool Mode Enabling and Disabling Cool Mode Use the COOL button to enable or disable cool mode as desired. If the thermostat is in HEA T or OFF mode, cool mo d e is enabled when the COOL button is pressed. This is indicated by COOL in the SYSTEM box (s ee f i gu r e 9). T urn Cool ON/OFF Figure 9 I0:30 75 70 ...

  • Lennox International Inc. 51M37 - page 5

    Page 5 51M37 SERIES 5/2 HOLD − Using T emperature Hold Modes When HOLD is displayed at the HOME screen, the ther- mos tat is in a temperature hold condition. This means that the temperature program data is ignored and the thermo- stat functions much like a non−programmable thermost at. Adjusting T emperature Setpoint in Hold Mode The temperatur ...

  • Lennox International Inc. 51M37 - page 6

    Page 6 505050M 5/1/05 5. Repeat step s 2 through 4 for periods B, C, and D. 6. Repeat step s 1 through 5 for the 2−day program. NOTE − This thermost at will NOT automatically switch from heating to cooling, or vice versa; operator involve- men t is required. At the change of seasons, or to accomo- date abnormal seasonal temperature swings, you ...

  • Lennox International Inc. 51M37 - page 7

    Page 7 51M37 SERIES 5/2 SETTINGS − Balance Point NOTE − The balance point is only available with the out- door sensor . If the optional outdoor sensor (X2658) is connected to the thermostat, balance point adjustment is available. The bal- ance point feature allows the measured outdoor tempera- ture to govern operation of the heat pump and backu ...

  • Lennox International Inc. 51M37 - page 8

    Page 8 505050M 5/1/05 Default Thermostat Settings Default thermostat settings are shown in table 2 and the default program is shown in table 3. T able 2 Default Thermostat Settings Mode Heat (Permanent Hold Mode) Setpoint 70°F (or 21°C) Fan Auto Filter Reminder OFF Maintenance Reminder OFF Equipment Protection T imers Reset Back to Zero T able 3 ...

  • Lennox International Inc. 51M37 - page 9

    Page 9 51M37 SERIES 5/2 Smart Setback Recovery (via DIP switch #6) Smart Setback Recovery (SSR) affects the way the ther- mo st at responds to program events. If SSR is disabled, th e thermostat will react to a program event at the time the event occurs. However , if SSR is enabled, the thermostat will react to a program event before the event occu ...

  • Lennox International Inc. 51M37 - page 10

    Page 10 505050M 5/1/05 Thermostat Output T able T able 5 depicts the 51M37 thermostat output st ates for var- ious input conditions. The following notes described terms used in the t able. NOTES: S X = output is activated with 24V AC. S BBP: outdoor temperature is below balance point S ABP: outdoor temperature is above balance point S In all cases, ...

  • Lennox International Inc. 51M37 - page 11

    05/05 505,049M *2P0505* *P505049M* Page 1 E 2005 Lennox Industries Inc. Dallas, T exas, USA RET AIN THESE INSTRUCTIONS FOR FUTURE REFERENCE 51M35 Merit ® Series Thermost at The Lennox Merit ® Series 5/2 day programmable electronic thermostat 51M35 provides excellent temperature control and a large, easy-to-read display . This product includes a p ...

  • Lennox International Inc. 51M37 - page 12

    Page 2 505049M 5/1/05 Within a few seconds, the Home Screen appears (see fig- ure 2) with default settings as shown. After about 1 minute of initialization time, the actual room temperature will be displayed. NOTE − T ables 2 and 3 on page 6 show all system and programming default s. I2:00 PROG A B C D HOLD FA N ON AUTO SYSTEM COOL OFF HEA T 70 H ...

  • Lennox International Inc. 51M37 - page 13

    Page 3 51M35 SERIES 5/2 HEA T − Using the Heat Mode Enabling and Disabling Heat Mode The thermostat must be in the HEA T mode to control the heating equipment. Press the Heat button to enable or dis- able HEA T mode. If the thermostat is in COOL or OFF mode, pressing the Heat button enables the HEA T mode (indicated by HEA T in the S YS TE M b o ...

  • Lennox International Inc. 51M37 - page 14

    Page 4 505049M 5/1/05 HOLD − Using T emperature Hold Modes When HOLD is displayed at the HOME screen, the ther- mos tat is in a temperature hold condition. This means that the temperature program data is ignored and the thermo- stat functions much like a non−programmable thermost at. Adjusting T emperature Setpoint in Hold Mode The temperature ...

  • Lennox International Inc. 51M37 - page 15

    Page 5 51M35 SERIES 5/2 NOTE − This thermost at will NOT automatically switch from heating to cooling, or vice versa; operator involve- men t is required. At the change of seasons, or to accomo- date abnormal seasonal temperature swings, you must manually select to the opposite conditioning (Heat or Cool) program. F AN − Controlling the Fan Ope ...

  • Lennox International Inc. 51M37 - page 16

    Page 6 505049M 5/1/05 Service Indicator When abnormal equipment operation is detected, the SERVICE in d icator will flash on the screen (see figure 17). This indicates that the equipment requires service from a qualified service technician. I0:i4 PROG A B C D HOLD 79 Service Indicator Flashing Figure 17 ROOM SER VICE ° FIL TER AM PM FA N ON AUTO S ...

  • Lennox International Inc. 51M37 - page 17

    Page 7 51M35 SERIES 5/2 T echnical S pecifications Thermostat T ype Electronic programmable thermostat for 2−S tage (gas or electric) Heat/2-S tage Cool, non−heat pump, non−power robbing applications. Power Supply Range 18V AC − 30V AC (24V AC nominal), 60Hz CAUTION 24V AC is present on the terminals of the thermost at bracket. If removing ...

  • Lennox International Inc. 51M37 - page 18

    Page 8 505049M 5/1/05 Maintenance Reminder Settings of Of f, 6 or 12 (months of chronological time) are available. W hen programmed time has elap sed, a mainte- nance indicator MAINT" is displayed. Service Reminder The SER VICE indicator is displayed only under the follow- ing conditions: S if the thermostat Y1 terminal has been activated w ...

  • Lennox International Inc. 51M37 - page 19

    05/05 505,048M *2P0505* *P505048M* Page 1 E 2005 Lennox Industries Inc. Dallas, T exas, USA RET AIN THESE INSTRUCTIONS FOR FUTURE REFERENCE 51M34 Merit ® Series Thermost at The Lennox Merit ® Series 5/2 day programmable electronic thermostat 51M34 provides excellent temperature control and a large, easy-to-read display . This product includes a p ...

  • Lennox International Inc. 51M37 - page 20

    Page 2 505048M 5/1/05 Within a few seconds, the Home Screen appears (see fig- ure 2) with default settings as shown. After about 1 minute of initialization time, the actual room temperature will be displayed. I2:00 PROG A B C D HOLD FA N ON AUTO SYSTEM COOL OFF HEA T 70 Home Screen Figure 2 ROOM SER VICE ° FIL TER MAINT MO TU WE TH FR SA SU AM PM ...

  • Lennox International Inc. 51M37 - page 21

    Page 3 51M34 SERIES 5/2 HEA T − Using the Heat Mode Enabling and Disabling Heat Mode The thermostat must be in the HEA T mode to control the heating equipment. Press the Heat button to enable or dis- able HEA T mode. If the thermostat is in COOL or OFF mode, pressing the Heat button enables the HEA T mode (indicated by HEA T in the S YS TE M b o ...

  • Lennox International Inc. 51M37 - page 22

    Page 4 505048M 5/1/05 HOLD − Using T emperature Hold Modes When HOLD is displayed at the HOME screen, the ther- mos tat is in a temperature hold condition. This means that the temperature program data is ignored and the thermo- stat functions much like a non−programmable thermost at. Adjusting T emperature Setpoint in Hold Mode The temperature ...

  • Lennox International Inc. 51M37 - page 23

    Page 5 51M34 SERIES 5/2 NOTE − This thermost at will NOT automatically switch from heating to cooling, or vice versa; operator involve- men t is required. At the change of seasons, or to accomo- date abnormal seasonal temperature swings, you must manually select to the opposite conditioning (Heat or Cool) program. F AN − Controlling the Fan Ope ...

  • Lennox International Inc. 51M37 - page 24

    Page 6 505048M 5/1/05 Service Indicator When abnormal equipment operation is detected, the SERVICE in d icator will flash on the screen (see figure 17). This indicates that the equipment requires service from a qualified service technician. I0:i4 PROG A B C D HOLD 79 Service Indicator Flashing Figure 17 ROOM SER VICE ° FIL TER AM PM FA N ON AUTO S ...

  • Lennox International Inc. 51M37 - page 25

    Page 7 51M34 SERIES 5/2 T echnical S pecifications Thermostat T ype Electronic programmable thermostat for 1-S tage- Heat/1-S tage Cool, gas or electric heat, non−heat pump, non−power robbing applications. Power Supply Range 18V AC − 30V AC (24V AC nominal), 60Hz CAUTION 24V AC is present on the terminals of the thermost at bracket. If removi ...

  • Lennox International Inc. 51M37 - page 26

    Page 8 505048M 5/1/05 Maintenance Reminder Settings of Of f, 6 or 12 (months of chronological time) are available. W hen programmed time has elap sed, a mainte- nance indicator MAINT" is displayed. Service Reminder The SER VICE indicator is displayed only under the follow- ing conditions: S if the thermostat Y1 terminal has been activated w ...

  • Lennox International Inc. 51M37 - page 27

    07/05 505,068M *2P0705* *P505068M* Page 1 E 2005 Lennox Industries Inc. Dallas, T exas, USA RET AIN THESE INSTRUCTIONS FOR FUTURE REFERENCE 51M39 Merit ® Series Thermost at The Lennox Merit ® Series 7 day programmable electronic thermostat 51M39 provides excellent temperature control and a large, easy-to-read display . This product includes a pro ...

  • Lennox International Inc. 51M37 - page 28

    Page 2 505068M 07/05 Within a few seconds, the HOME screen appears (see fig- ure 2) with default settings as shown. After about 1 minute of initialization time, the actual room temperature will be displayed. NOTE − T ables 2 and 3 on page 7 show all system and programming default s. COOL OFF AUTO EMG. HEAT I0:26 PROG A B C D HOLD F AN ON AUT O 70 ...

  • Lennox International Inc. 51M37 - page 29

    Page 3 51M39 SERIES 5/2 HEA T − Using the Heat Mode Enabling and Disabling Heat Mode The thermostat must be in the heat mode to control the heating equipment. Press the HEA T button to enable or disable HEA T mode. If the thermost at is in cool or of f mode, pressing the HEA T button enables the heat mode (indicated by HEA T in the lower right co ...

  • Lennox International Inc. 51M37 - page 30

    Page 4 505068M 07/05 NOTE − If no buttons are pressed during a demand for cooling, t he equipment must operate for at least 4 minutes. Afte r a demand has been satisfied, cooling equipment op- eration is locked out for 5 minutes. If another cooling de- ma nd occurs during this 5−minute interval, COOL" and the snowflakes will flash; howe ...

  • Lennox International Inc. 51M37 - page 31

    Page 5 51M39 SERIES 5/2 Figure 1 1 Program Example 6AM NOON 6PM MID 6AM NIGHT A B D A B D A B D A B D A B C D A B C D A B C D C C C C SA TURDA Y PROGRAM: 72° 68° 64° SUNDA Y PROGRAM: 72° 68° 64° FRIDA Y PROGRAM: 72° 68° 64° THURSDA Y PROGRAM: 72° 68° 64° WEDNESDAY PROGRAM: 72° 68° 64° TUESDA Y PROGRAM: 72° 68° 64° MONDA Y PROGRAM: ...

  • Lennox International Inc. 51M37 - page 32

    Page 6 505068M 07/05 Displaying Outside T emperature Pressing the ENTER (Outside) button at the HOME screen di sp l ays the out side temperature (see figure 15) for several seconds, then returns to room temperature. Check Outside T emperature Figure 15 88 Fan Settings Hold Enter (Outside) SETTINGS − Filter/Maintenance Reminders Th e 51M39 thermos ...

  • Lennox International Inc. 51M37 - page 33

    Page 7 51M39 SERIES 5/2 Removing and Installing Thermostat The thermostat hinges on tabs on the top of the subbase; no tool is needed to remove the thermostat from the sub- base. Pivot the bottom of the thermostat outward (releas- ing the snap s), then lif t up to remove. T o install it, first position the top tilted toward the wall brack- et and a ...

  • Lennox International Inc. 51M37 - page 34

    Page 8 505068M 07/05 T echnical S pecifications Thermostat T ype Electronic programmable thermostat for 2−S tage (gas or electric) Heat/2-S tage Cool, non−heat pump, non−power robbing applications. T able 5 51M39 T erminal Designations T erminal Description R 24V AC Y1 First-stage cooling W1 First-stage heating Y2 Second-stage cooling W2 Seco ...

  • Lennox International Inc. 51M37 - page 35

    Page 9 51M39 SERIES 5/2 NOTE − All protection timers (except the compressor OFF timer) can be over−ridden if a heating or cooling demand is initiated or terminated using the UP , DOWN, HEA T , or COOL buttons. Equipment Protection Override Both the minimum compressor OFF timer and the mini- mum equipment cycle timer can be over−ridden by pres ...

  • Lennox International Inc. 51M37 - page 36

    ...

  • Lennox International Inc. 51M37 - page 37

    07/05 505,069M *2P0705* *P505069M* Page 1 E 2005 Lennox Industries Inc. Dallas, T exas, USA RET AIN THESE INSTRUCTIONS FOR FUTURE REFERENCE 51M42 Merit ® Series Thermost at The Lennox Merit ® Series 7−day programmable electronic thermostat 51M42 provides excellent temperature control and a large, easy-to-read display . It includes a programmabl ...

  • Lennox International Inc. 51M37 - page 38

    Page 2 505069M 07/05 Within a few seconds, the HOME screen appears (see fig- ure 2) with default settings as shown. After about 1 minute of initialization time, the actual room temperature will be displayed. NOTE − T ables 2 and 3 on page 8 show all system and programming default s. COOL OFF AUTO EMG. HEAT I0:26 PROG A B C D HOLD F AN ON AUT O 70 ...

  • Lennox International Inc. 51M37 - page 39

    Page 3 51M42 SERIES 5/2 HEA T − Using the Heat Mode Normal Heat Mode In normal heat mode, both the heat pump and the backup heat source are used to provide heat. If the thermost at d e- tects that the heat pump is not able to provide enough heat (as may be the case in very cold weather), then the backup heat source is activated. Emergency Heat Mo ...

  • Lennox International Inc. 51M37 - page 40

    Page 4 505069M 07/05 COOL − Using the Cool Mode Enabling and Disabling Cool Mode Use the COOL button to enable or disable cool mode as desired. If the thermosta t i s in heat or of f mode, cool mode is enabled when the COOL button is pressed. This is indi- cated by COOL on the r igh t si de of the disp lay (s e e fig u r e 9). Heat Prog Fan Setti ...

  • Lennox International Inc. 51M37 - page 41

    Page 5 51M42 SERIES 5/2 T emporary (2-Hour) Hold At any time the program is running, from the HOME screen, set a temporary 2-hour hold by pressing the Up/ Down arrow buttons until the desired setpoint is displayed; HOLD" flashes (see figure 12). This overrides the pro- gram for 2 hours from the last button press, then returns to the program ...

  • Lennox International Inc. 51M37 - page 42

    Page 6 505069M 07/05 F AN − Controlling the Fan Operation U s e the F AN button to select either continuous fan mode or auto fan mode. T o change from continuous to auto fan mode (or vice ver - sa), press the F AN button. Note whether a fan icon in the F AN b ox is present (indicating that the fan is running) or not (fan not running) . If continu ...

  • Lennox International Inc. 51M37 - page 43

    Page 7 51M42 SERIES 5/2 COOL OFF AUTO EMG. HEAT I0:26 PROG A B C D HOLD F AN ON AUT O FIL TER S ER VICE MAINTENANCE 76 Reminders Figure 19 ROOM ° MO AM PM COOL OFF AUTO EMG. HEAT FA N ON AUT O FIL TER S ER VICE MAINTENANCE 76 Service Indicator Flashing ROOM ° Filter & Maintenance Indicators After the filter has been changed or maintenance per ...

  • Lennox International Inc. 51M37 - page 44

    Page 8 505069M 07/05 Default Thermostat Settings Default thermostat settings are shown in table 2 and the default program is shown in table 3. T able 2 Default Thermostat Settings Mode Heat (Perm. Hold) Heat Setpoint (Perm Hold) 70°F (or 21°C) Cool Setpoint (Perm Hold) 78°F (or 26°C) Fan Auto Filter Reminder OFF Maintenance Reminder OFF Equipme ...

  • Lennox International Inc. 51M37 - page 45

    Page 9 51M42 SERIES 5/2 T echnical S pecifications Thermostat T ype Electronic programmable thermostat for heat pump, 3-stage heat/2-st age cool. NOTE − 2 s t ages of heat pump heat and one st age of auxil- iary (gas or electric) backup heat are supported. Power Supply Range 18V AC − 30V AC (24V AC nominal), 60Hz CAUTION 24V AC is present on th ...

  • Lennox International Inc. 51M37 - page 46

    Page 10 505069M 07/05 T able 5 51M42 T erminal Designations T erm. Description B Reversing valve, heat active O Reversing valve, cool active R 24V AC Y1 First-stage cooling/heating, compressor energized W1* Auxiliary heating, furnace energized Y2 Second-stage cooling/heating, compressor energized E* Emergency heat G Fan control L Service Indicator ...

  • Lennox International Inc. 51M37 - page 47

    07/05 505,067M *2P0705* *P505067M* Page 1 E 2005 Lennox Industries Inc. Dallas, T exas, USA RET AIN THESE INSTRUCTIONS FOR FUTURE REFERENCE 51M38 Merit ® Series Thermost at The Lennox Merit ® Series 7 day programmable electronic thermostat 51M38 provides excellent temperature control and a large, easy-to-read display . This product includes a pro ...

  • Lennox International Inc. 51M37 - page 48

    Page 2 505067M 7/13/05 Within a few seconds, the HOME screen appears (see fig- ure 2) with default settings as shown. After about 1 minute of initialization time, the actual room temperature will be displayed. COOL OFF AUTO EMG. HEAT I0:26 PROG A B C D HOLD F AN ON AUT O 70 HOME Screen Figure 2 ROOM ° MO AM PM At this point, the thermostat will be ...

  • Lennox International Inc. 51M37 - page 49

    Page 3 51M38 SERIES 5/2 HEA T − Using the Heat Mode Enabling and Disabling Heat Mode The thermostat must be in the heat mode to control the heating equipment. Press the HEA T button to enable or disable heat mode. If the thermost at is in cool or of f mode, pressing the HEA T button enables the heat mode ( i n d i- cated by HEA T in the lower rig ...

  • Lennox International Inc. 51M37 - page 50

    Page 4 505067M 7/13/05 HOLD − Using T emperature Hold Modes When HOLD is displayed at the HOME screen, the ther- mos tat is in a temperature hold condition. This means that the temperature program data is ignored and the thermo- stat functions much like a non−programmable thermost at. Adjusting T emperature Setpoint in Hold Mode The temperature ...

  • Lennox International Inc. 51M37 - page 51

    Page 5 51M38 SERIES 5/2 1. Press and re lease the PROG button. "MO" (Monday), "AM 6:00", period "A", "COOL SETPOINT 78", and "HEA T SETPOINT 70" are displayed. "AM 6" flashes. 2. Use the Up/Down arrow buttons to select the desired hour; press the PROG button when the desired hour is reache ...

  • Lennox International Inc. 51M37 - page 52

    Page 6 505067M 7/13/05 The default setting for the reminders is OFF (disabled). Press Up/Down arrow buttons to select the desired re- minder intervals. T able 1 Filter and Maintenance Reminders Buttons to Use Reminder A vailable Settings and How to Use SETTINGS (1st press) FIL TER T otal fan run time expressed in months (Of f136 12); for (1 s t pre ...

  • Lennox International Inc. 51M37 - page 53

    Page 7 51M38 SERIES 5/2 T able 3 Default Program Settings (Time & T emp.) Programs Time T emp. − Heat T emp. Cool All days − A 6:00am 70 _ F / 21 ° C 78 _ F / 26 ° C All days − B 8:00am 62 _ F / 17 ° C 85 _ F / 29 ° C All days − C 6:00pm 70 _ F / 21 ° C 78 _ F / 26 ° C All days − D 10:00pm 62 _ F / 17 ° C 82 _ F / 28 ° C Therm ...

  • Lennox International Inc. 51M37 - page 54

    Page 8 505067M 7/13/05 Smart Setback Recovery (via DIP switch #6) Smart Setback Recovery (SSR) affects the way the ther- mo st at responds to program events. If SSR is disabled, th e thermostat will react to a program event at the time the event occurs. However , if SSR is enabled, the thermostat will react to a program event before the event occur ...

Manufacturer Lennox International Inc. Category Thermostat

Documents that we receive from a manufacturer of a Lennox International Inc. 51M37 can be divided into several groups. They are, among others:
- Lennox International Inc. technical drawings
- 51M37 manuals
- Lennox International Inc. product data sheets
- information booklets
- or energy labels Lennox International Inc. 51M37
All of them are important, but the most important information from the point of view of use of the device are in the user manual Lennox International Inc. 51M37.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Lennox International Inc. 51M37, service manual, brief instructions and user manuals Lennox International Inc. 51M37. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Lennox International Inc. 51M37.

A complete manual for the device Lennox International Inc. 51M37, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Lennox International Inc. 51M37 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Lennox International Inc. 51M37.

A complete Lennox International Inc. manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Lennox International Inc. 51M37 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Lennox International Inc. 51M37, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Lennox International Inc. 51M37, that we can find in the current document
3. Tips how to use the basic functions of the device Lennox International Inc. 51M37 - which should help us in our first steps of using Lennox International Inc. 51M37
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Lennox International Inc. 51M37
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Lennox International Inc. 51M37 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Lennox International Inc. 51M37?

Use the form below

If you did not solve your problem by using a manual Lennox International Inc. 51M37, ask a question using the form below. If a user had a similar problem with Lennox International Inc. 51M37 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)