Manual Bryant GAMA 331JAV

24 pages 3.38 mb
Download

Go to site of 24

Summary
  • Bryant GAMA 331JAV - page 1

    NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. Index Page SAFETY CONSIDERATIONS .....................................................1 ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE ........................................................................1-2 IN ...

  • Bryant GAMA 331JAV - page 2

    2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged. 3. After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricit ...

  • Bryant GAMA 331JAV - page 3

    CAUTION: Application of this furnace should be in- doors with special attention given to vent sizing and material, gas input rate, air temperature rise, and unit sizing. Improper installation or misapplication of the furnace can require excessive servicing or cause prema- ture component failure. Installation must conform to regulations of serving g ...

  • Bryant GAMA 331JAV - page 4

    I. LOCATION A. General CAUTION: DO NOT install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are followed. DO NOT use this furnace during construction when adhesives, sealers, and/or new carpets are being installed and curing. If the furnace is required during construction, use clean ou ...

  • Bryant GAMA 331JAV - page 5

    c. If furnace is installed to obtain return air is taken directly from hallway or space adjacent to furnace, all air for combustion must come from outdoors. 2. Air from outside the structure requires 1 of the following methods: a. If combustion air is taken from outdoors through 2 vertical ducts, the openings and ducts MUST have at least 1 sq in. o ...

  • Bryant GAMA 331JAV - page 6

    IV. FILTER ARRANGEMENT WARNING: Never operate unit without a filter or with filter access door removed. A failure to follow this warning could result in fire, personal injury, or death. The 2 factory-supplied filters are shipped in the blower compart- ment. After return-air duct has been connected to furnace, install filters in a V-formation inside ...

  • Bryant GAMA 331JAV - page 7

    WARNING: Use the proper length of pipes to avoid stress on gas control manifold. A failure to follow this warning could result in a gas leak causing fire, explosion, personal injury, or death. CAUTION: Use a backup wrench at furnace gas control when connecting gas pipe to furnace to avoid damaging gas controls or manifold. WARNING: Never purge a li ...

  • Bryant GAMA 331JAV - page 8

    Install accessible manual shutoff valve upstream of furnace gas controls and within 72 in. of furnace. A 1/8-in. NPT plugged tapping is provided on gas value for test gage connection. Installation of additional 1/8-in. NPT plugged tapping, accessible for test gage connection, installed immediately upstream of gas supply connection to furnace and do ...

  • Bryant GAMA 331JAV - page 9

    A terminal block (EAC-1 [hot] and EAC-2 [neutral]) is provided for EAC connection. (See Fig. 10.) The terminals are energized with 115v, 1-amp maximum during blower motor operation. 2. Humidifier (HUM) Screw terminals (HUM-1 and C OM ) are provided for 24-v humidifier connection. The terminals are energized with 24v, 0.5-amp maximum when the gas va ...

  • Bryant GAMA 331JAV - page 10

    The gas service pressure must not exceed 0.5 psig (14-in. wc), and be no less than 0.16 psig (4.5-in. wc). Thermostat wire connections at R and W/W1 are the minimum required for gas heating operation. W2 must be connected for 2-stage heating thermostats. C OM , Y/Y2, and G are required for cooling, heat pumps, and some clock thermostats. These must ...

  • Bryant GAMA 331JAV - page 11

    → Fig. 14—Unit Wiring Diagram A97508 LEGEND ALS1 AUXILIARY LI MIT SWITCH , OVERTEMP. MANUAL R ESET, SPST (N.C.) ALS2 AUXILIARY LI MIT SWITCH , OVERTEMP. AUTO RES ET, SPST ( N.C.) BHI / LOR BLOWER MOTOR SPEED CHANGE RELAY , SPDT BHT / CLR BLOWER MOTOR SPEED CHANGE RELAY , SPDT BLWM BLOWER MOTOR, 4 or 5 -S PEED, PERMANEN T-SPLIT-CA PACITOR BLWR B ...

  • Bryant GAMA 331JAV - page 12

    a. Inducer prepurge period—As inducer motor IDM comes up to low speed or high speed, the low-heat pressure switch contacts LPS (or LPS and HPS) close to begin a 15-sec prepurge period. b. Ignitor warm-up—At the end of prepurge period, hot surface ignitor HSI is energized for a 17-sec ignitor warm-up period. c. Trial-for-ignition sequence—When ...

  • Bryant GAMA 331JAV - page 13

    (3.) When thermostat is satisfied, R to G-and-Y cir- cuits are opened. The outdoor unit stops, and furnace blower motor BLWM continues operating on high-cool speed for an additional 90 sec. b. Two-Speed Cooling Outdoor Unit (See Fig. 12 for thermostat connections.) (1.) The thermostat closes R to G-and-Y1 circuits for low cooling or closes R to G-a ...

  • Bryant GAMA 331JAV - page 14

    b. When installed with a heat pump, furnace control CPU automatically holds blower off time to 22 sec during HSI ignitor on period. After 17 sec of HSI ignitor on period, a trial-for-ignition sequence occurs as described above for gas heating. After flame is proved and without blower on delay, blower motor BLWM then operates on high-gas-heat speed ...

  • Bryant GAMA 331JAV - page 15

    g. Turn high-heat adjusting screw (5/64 hex Allen wrench) counterclockwise (out) to decrease input rate or clock- wise (in) to increase rate. NOTE: DO NOT set high-heat manifold pressure less than 3.2-in. wc or more than 3.8-in. wc for natural gas. If manifold pressure is outside this range, change main burner orifices. h. When correct input is obt ...

  • Bryant GAMA 331JAV - page 16

    TABLE 9—MODEL 331JAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT (TABULATED DATA BASED ON 21,000 BTUH HIGH HEAT/13,500 BTUH LOW HEAT PER BURNER, DERATED 4% FOR EACH 1000 FT ABOVE SEA LEVEL) ALTITUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0.64 0.66 Orifice No. Manifold Pressure ...

  • Bryant GAMA 331JAV - page 17

    TABLE 9—MODEL 331JAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT Continued (TABULATED DATA BASED ON 21,000 BTUH HIGH HEAT/13,500 BTUH LOW HEAT PER BURNER, DERATED 4% FOR EACH 1000 FT ABOVE SEA LEVEL) ALTITUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0.64 0.66 Orifice No. Manifol ...

  • Bryant GAMA 331JAV - page 18

    TABLE 9—MODEL 331JAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT Continued (TABULATED DATA BASED ON 21,000 BTUH HIGH HEAT/13,500 BTUH LOW HEAT PER BURNER, DERATED 4% FOR EACH 1000 FT ABOVE SEA LEVEL) ALTITUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0.64 0.66 Orifice No. Manifol ...

  • Bryant GAMA 331JAV - page 19

    a. Place duct thermometers in return and supply ducts as near furnace as possible. Be sure thermometers do not see heat exchangers so that radiant heat will not affect thermometer readings. This is particularly important with straight-run ducts. b. When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to d ...

  • Bryant GAMA 331JAV - page 20

    17. The thermostat anticipator should NOT be in this circuit while measuring current. If thermostat has no subbase, thermostat MUST be disconnected from R and W/W1 wires during current measurement. Return SW-2 to final desired location after completing reading. See thermostat manufacturer’s instructions for adjusting heat anticipator and for vary ...

  • Bryant GAMA 331JAV - page 21

    —21— ...

  • Bryant GAMA 331JAV - page 22

    —22— ...

  • Bryant GAMA 331JAV - page 23

    A94328 SER VICE TRAINING P ackaged Service T raining prog rams are an e xcellent wa y to increase your knowledge of the equipment discussed in this man ual, including: • Unit F amiliarization • Maintenance • Installation Ov er view • Oper ating Sequence A large selection of product, theor y , and skills prog rams is av ailable , using popul ...

  • Bryant GAMA 331JAV - page 24

    © 2008 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 —24— Printed in U.S.A. 331j602 Catalog No. 5333-100 ...

Manufacturer Bryant Category Furnace

Documents that we receive from a manufacturer of a Bryant GAMA 331JAV can be divided into several groups. They are, among others:
- Bryant technical drawings
- GAMA 331JAV manuals
- Bryant product data sheets
- information booklets
- or energy labels Bryant GAMA 331JAV
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bryant GAMA 331JAV.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bryant GAMA 331JAV, service manual, brief instructions and user manuals Bryant GAMA 331JAV. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bryant GAMA 331JAV.

Similar manuals

A complete manual for the device Bryant GAMA 331JAV, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bryant GAMA 331JAV by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bryant GAMA 331JAV.

A complete Bryant manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bryant GAMA 331JAV - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bryant GAMA 331JAV, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bryant GAMA 331JAV, that we can find in the current document
3. Tips how to use the basic functions of the device Bryant GAMA 331JAV - which should help us in our first steps of using Bryant GAMA 331JAV
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bryant GAMA 331JAV
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bryant GAMA 331JAV in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bryant GAMA 331JAV?

Use the form below

If you did not solve your problem by using a manual Bryant GAMA 331JAV, ask a question using the form below. If a user had a similar problem with Bryant GAMA 331JAV it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)