Manual Bryant 594D

24 pages 0.18 mb
Download

Go to site of 24

Summary
  • Bryant 594D - page 1

    Form No. PDS 594D.18.7 ELECTRIC AIR CONDITIONER Model 594D (60 Hz) Sizes 018 thru 060 WIDE RANGE OF SIZES —A vailab le in 7 nominal sizes from 018 through 060 to meet the needs f or residential and light commercial applications. WEA THER-PRO TECTIVE CABINET —Steel is galvaniz ed, then coated with a la yer of zinc phosphate to which a coat of mo ...

  • Bryant 594D - page 2

    —2— ACCESS PANEL 1 1 / 4 "  1. Allow 30 in. clearance to service end of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side, and 24 in. between units for proper airflow. Minimum outdoor operating ambient in cooling mode is 55 ° F (unless low-ambient control is used) max 125 ° F. 2. Series designation is the 1 ...

  • Bryant 594D - page 3

    —3— RECOMMENDED TUBE DIAMETERS * For tube sets between 50 and 175 ft, consult Residential Split System Long-Line Application Guideline . CHECK-FLO-RA TER® * Piston listed is for any appro ved non-capillary tube coil combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil. SOUND PO WER (dBA) LIQUID TUB ...

  • Bryant 594D - page 4

    —4— SPECIFICA TIONS See notes on page 5. UNIT SIZE - SERIES 018-E 024-E 030-E 036-E OPERA TING WT (Lb) 138 143 146 200 ELECTRICAL Unit V olts—Hertz—Phase 208/230—60—1 208/230—60—1 208/230—60—1 208/230—60—1 Operating V oltage Range* 187—253 187—253 187—253 187—253 Compressor— Rated Load Amps 8.9 11.4 13.7 16.0 Lock ...

  • Bryant 594D - page 5

    —5— SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will operate satisf actor ily . Operation outside these limits ma y result in unit failure. Copper wire must be used from service disconnect to unit. † If wire is applied at ambient greater than 30°C (86°F), consult T able 310-16 of the NEC (ANSI/NF ...

  • Bryant 594D - page 6

    —6— ACCESSORY USAGE GUIDELINE * For tubing line sets betw een 50 and 175 ft, refer to Residential Split System Long-Line Application Guideline. † Only when low-pressure s witch is used. A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) 1. Ball Bearing Fan Motor A fan motor with ball bearings which permits speed reduction while mainta ...

  • Bryant 594D - page 7

    —7— A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 11. Low-Ambient Contr oller Head pressure controller is a cycle control de vice activ ated by a temperature sensor mounted on a header tube of the outdoor coil. It is designed to cycle the outdoor f an motor in order to maintain condensing temperature within normal operati ...

  • Bryant 594D - page 8

    —8— COMBINA TION RA TINGS See notes on page 11. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY SUPPLIED ENHANCE- MENT SEER EERA ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR† A CCESSORY TXV‡ 018-E CK5A/CK5BA024* 17,600 NONE 10.50 11.00 11.00 10.60 CC5A/CD5AA018 17,200 NONE 10.50 11.00 11.00 10.45 CC5A/CD5AA024 17,600 ...

  • Bryant 594D - page 9

    —9— COMBINA TION RA TINGS Continued See notes on page 11. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY SUPPLIED ENHANCE- MENT SEER EERA ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR† A CCESSORY TXV‡ 030-E FC4BNF030 28,200 TDR & TXV 11.00 — — 9.45 FC4BNF036 28,600 TDR & TXV 10.80 — — 9.35 FF1(B,C ,D)N ...

  • Bryant 594D - page 10

    —10— COMBINA TION RA TINGS Continued UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY SUPPLIED ENHANCE- MENT SEER EERA ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR† A CCESSORY TXV‡ 042-E CD5AA048* 41,000 NONE 11.00 11.50 11.50 10.25 CC5A/CD5AA042 41,000 NONE 11.00 11.50 11.50 10.25 CC5A/CD5AC048 40,500 NONE 11.00 11.50 ...

  • Bryant 594D - page 11

    —11— COMBINA TION RA TINGS Continued * T ested Combination † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system may cause deg r adation in perf ormance. Use either the accessory Time-Dela y Rela y KAA TD0101TDR or a furnace equipped with TDR. All Bryant furnaces are equipped with TDR exc ...

  • Bryant 594D - page 12

    —12— DET AILED COOLING CAP A CITIES* See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens? ...

  • Bryant 594D - page 13

    —13— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ To ...

  • Bryant 594D - page 14

    —14— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ To ...

  • Bryant 594D - page 15

    —15— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ To ...

  • Bryant 594D - page 16

    —16— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ To ...

  • Bryant 594D - page 17

    —17— DET AILED COOLING CAP A CITIES* Continued See notes on page 18. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F 85 95 105 115 125 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ To ...

  • Bryant 594D - page 18

    —18— DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI Standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity may occur . † T otal and sensib le capacities are net capacities. Bl ...

  • Bryant 594D - page 19

    —19— CONDENSER ONLY RATINGS* See notes on page 20. SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 65 75 85 95 105 115 594D018-E 30 TCG 16.9 16.2 15.4 14.6 13.8 12.9 12.0 SDT 77.1 86.9 96.8 107.0 116.00 126.0 136.0 KW 0.809 0.930 1.07 1.22 1.38 1.55 1.74 35 TCG 18.6 17.8 16.9 16.1 15.2 14.3 13.4 SDT 78.3 88.0 97.8 108.0 117. 127.0 137.0 KW ...

  • Bryant 594D - page 20

    —20— CONDENSER ONLY RATINGS* Continued * ARI listing applies only to systems shown in P erformance Data table . KW — T otal P ower (Kw) SDT — Saturated T emperature Lea ving Compressor (°F) SST — Saturated T emperature Entering Compressor (°F) TCG — Gross Cooling Capacity (1000 Btuh) SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 ...

  • Bryant 594D - page 21

    —21— SYSTEM DESIGN SUMMAR Y 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan e xter nal static pressure av ailable is less than 0.01 in. wc. 2. Minimum outdoor operating air temperature without lo w-ambient operation accessor y is 55°F (12.8°C). 3. Maximum outdoor operating air temperature is 125°F (51.7°C). ...

  • Bryant 594D - page 22

    —22— MA TCHED SYSTEM A98599 ...

  • Bryant 594D - page 23

    —23— ...

  • Bryant 594D - page 24

    —2 4— SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 594D.18.6 © 1999 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 PRINTED IN U.S.A. Catalog No. 5259-405 11-99 GUIDE SPECIFICATIONS GENERAL System Description Outdoor-mounted, air-coole ...

Manufacturer Bryant Category Air Conditioner

Documents that we receive from a manufacturer of a Bryant 594D can be divided into several groups. They are, among others:
- Bryant technical drawings
- 594D manuals
- Bryant product data sheets
- information booklets
- or energy labels Bryant 594D
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bryant 594D.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bryant 594D, service manual, brief instructions and user manuals Bryant 594D. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bryant 594D.

Similar manuals

A complete manual for the device Bryant 594D, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bryant 594D by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bryant 594D.

A complete Bryant manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bryant 594D - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bryant 594D, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bryant 594D, that we can find in the current document
3. Tips how to use the basic functions of the device Bryant 594D - which should help us in our first steps of using Bryant 594D
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bryant 594D
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bryant 594D in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bryant 594D?

Use the form below

If you did not solve your problem by using a manual Bryant 594D, ask a question using the form below. If a user had a similar problem with Bryant 594D it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)