    Form No. PDS 550A.24.10 DELUXE 13 SEER AIR CONDITIONER WITH PURON ® REFRIGERANT 550A Sizes 024 thru 060 Br yant’ s Air Conditioners with Puron® refr igerant provide a col- lection of features unmatched by an y other family of equipment. The 550A family has been designed utilizing Br yant’ s Puron refrigerant. The environmentally sound refrige ...

  • Bryant 550A - page 2

    —2— DIMENSIONS A99067 AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW. 2. MINIMUM OUTDOOR OPERATING AMBIENT ...

  • Bryant 550A - page 3

    —3— RECOMMENDED TUBE DIAMETERS *F or tube sets greater than 50 ft horizontal and/or 20 ft v er tical differential, consult Residential Split System Application Guideline and Service Manual. CHECK-FLO-RA TER® PIST ON *Piston listed is f or any appro ved non-capillary tube coil com- bination. Piston is shipped with outdoor unit and must be insta ...

  • Bryant 550A - page 4

    —4— SPECIFICA TIONS See notes on page 5. . UNIT SIZE-SERIES 024-G 030-F 036-F/G Operating Weight (Lb) 214 202 237 ELECTRICAL Unit V olts—Her tz—Phase 208/230—60—1 Operating V oltage Range* 187—253 Compressor— Rated Load Amps 12.8 14.7 15.4/16.7 Locked Rotor Amps 60.0 72.5 83.0/79.0 Condenser F an Motor—Full Load Amps 0.80 0.80 1.1 ...

  • Bryant 550A - page 5

    —5— SPECIFICA TIONS Continued *P ermissible limits of the voltage r ange at which the unit will operate satisf actorily . Operation outside these limits ma y result in unit f ailure. † If wire is applied at ambient greater than 30°C (86°F), consult T able 310-16 of the NEC (ANSI/NFP A 70). The ampacity of nonmetallic-sheathed cab le (NM), t ...

  • Bryant 550A - page 6

    —6— EV OLUTION™* CONTROLS * When applied with Bryant’ s Perf ect Humidity™ ser ies 355, 315 and FE Indoor Models. † Must be installed in Dual-Fuel Evolution system applications . A CCESSOR Y USA GE GUIDELINE *F or tubing line sets greater than 50 ft horizontal and/or 20 ft vertical differential, ref er to Residential Split-System Long-L ...

  • Bryant 550A - page 7

    —7— A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) 5. Crankcase Heater An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes the chance of liquid slugging. Usage Guideline: Required in low ambient applications. R ...

  • Bryant 550A - page 8

    —8— COMBINA TION RA TINGS UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH FA C T OR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory Puron TXV‡ 024-G *CC5A/CD5AA030 23,000 NONE — 13.00 13.00 11.25 CC5A/CD5AA024 22,800 NONE — 12.50 12.50 11.15 CC5A/CD5A W024 22,800 NONE — 12.50 12.50 11.1 ...

  • Bryant 550A - page 9

    —9— 024-G COILS + 315(A,J)A V066155 V ARIABLE-SPEED FURNA CE CE3AA024 22,400 TDR 14.00 — 14.00 12.30 CE3AA030 22,800 TDR 14.00 — 14.00 12.55 COILS + 355MA V042040 V ARIABLE-SPEED FURNACE CE3AA024 22,400 TDR 14.00 — 14.00 12.20 CE3AA030 22,800 TDR 14.00 — 14.00 12.45 COILS + 355MA V042060 V ARIABLE-SPEED FURNACE CC5A/CD5AA024 22,400 TDR ...

  • Bryant 550A - page 10

    —10— 030-F FF1DNA030 28,600 TDR 12.50 — 12.50 11.05 FG3AAA036 28,400 NONE — 12.50 12.50 11.00 FK4(C,D)NF001 29,000 TDR&TXV 13.00 — — 11.95 FK4(C,D)NF002 29,000 TDR&TXV 13.50 — — 12.05 FK4(C,D)NF003 29,600 TDR&TXV 14.00 — — 12.40 FV4(A,B)NF002 29,000 TDR&TXV 13.50 — — 12.05 FV4(A,B)NF003 29,600 TDR&TXV 14. ...

  • Bryant 550A - page 11

    —11— 030-F COILS + 355MA V042060 V ARIABLE-SPEED FURNACE CC5A/CD5AA036 29,600 TDR 13.50 — 13.50 11.90 CC5A/CD5A W030 28,400 TDR 13.20 — 13.20 11.50 CE3AA030 29,000 TDR 13.20 — 13.20 11.65 CE3AA036 29,200 TDR 13.50 — 13.50 11.75 CK3BA030 28,400 TDR 13.20 — 13.20 11.45 CK3BA036 29,600 TDR 13.50 — 13.50 11.95 CK5A/CK5BA036 29,600 TDR 1 ...

  • Bryant 550A - page 12

    —12— 036-F CK5PE042 35,000 TDR&TXV 14.00 — — 12.20 CK5PT036 35,000 TDR&TXV 13.50 — — 12.05 CK5PT042 35,000 TDR&TXV 14.00 — — 12.15 CK5PW036 35,000 TDR&TXV 13.50 — — 12.05 COILS + 315(A,J)A V060110 V ARIABLE-SPEED FURNA CE CC5A/CD5AA036 35,000 TDR 14.00 — 14.00 12.00 CC5A/CD5AA042 35,000 TDR 14.00 — 14.00 12.0 ...

  • Bryant 550A - page 13

    —13— 036-F CK3BA042 35,000 TDR 13.50 — 13.50 11.75 CK5A/CK5BA042 35,000 TDR 13.50 — 13.50 11.75 CK5A/CK5BT042 35,000 TDR 13.50 — 13.50 11.75 CK5A/CK5BW036 35,000 TDR 13.20 — 13.20 11.60 CK5P A042 35,000 TDR&TXV 13.50 — — 11.75 CK5PT042 35,000 TDR&TXV 13.50 — — 11.75 CK5PW036 35,000 TDR&TXV 13.20 — — 11.60 COILS + ...

  • Bryant 550A - page 14

    —14— 036-G FV4BNF003 35,000 TDR&TXV 14.00 — — 12.40 FV4BNF005 36,000 TDR&TXV 14.50 — — 12.85 FX4BNF036 35,000 TDR&TXV 12.50 — — 11.20 FX4BNF042 35,600 TDR&TXV 13.00 — — 11.40 COILS + 315(A,J)A V036070 V ARIABLE-SPEED FURNA CE CC5A/CD5AA036 34,400 TDR 13.50 — 13.50 11.85 CE3AA036 34,000 TDR 13.50 — 13.50 11.70 ...

  • Bryant 550A - page 15

    —15— 036-G COILS + 355MA V042040 V ARIABLE-SPEED FURNACE CC5A/CD5AA042 34,400 TDR 13.50 — 13.50 11.85 CC5A/CD5A W036 34,400 TDR 13.50 — 13.50 11.85 CC5A/CD5A W042 33,800 TDR 13.50 — 13.50 11.75 CE3AA036 34,000 TDR 13.50 — 13.50 11.65 CE3AA042 34,600 TDR 13.50 — 13.50 11.90 CK3BA042 34,600 TDR 13.50 — 13.50 11.90 CK5A/CK5BA042 34,600 ...

  • Bryant 550A - page 16

    —16— 036-G CK3BA036 34,600 TDR 13.50 — 13.50 12.00 CK3BA042 34,600 TDR 13.50 — 13.50 12.05 CK5A/CK5BA036 34,600 TDR 13.50 — 13.50 12.00 CK5A/CK5BA042 34,600 TDR 13.50 — 13.50 12.05 CK5A/CK5BE042 34,600 TDR 13.50 — 13.50 12.15 CK5A/CK5BT036 34,600 TDR 13.50 — 13.50 12.00 CK5A/CK5BT042 34,600 TDR 13.50 — 13.50 12.05 CK5A/CK5BW036 34 ...

  • Bryant 550A - page 17

    —17— 042-F CC5A/CD5A W048 40,500 TDR 14.00 — 14.00 11.95 CD5AA048 40,500 TDR 14.00 — 14.00 11.90 CE3AA042 40,500 TDR 13.50 — 13.50 11.85 CE3AA048 41,000 TDR 13.50 — 13.50 11.90 CK3BA042 40,500 TDR 13.50 — 13.50 11.80 CK3BA048 40,500 TDR 14.00 — 14.00 12.00 CK5A/CK5BA042 40,500 TDR 13.50 — 13.50 11.80 CK5A/CK5BA048 40,500 TDR 14.00 ...

  • Bryant 550A - page 18

    —18— 042-F CK5PT042 40,500 TDR&TXV 13.00 — — 11.30 CK5PT048 40,500 TDR&TXV 13.20 — — 11.55 COILS + 355MA V060080 V ARIABLE-SPEED FURNACE CC5A/CD5AA042 40,500 TDR 13.20 — 13.20 11.50 CC5A/CD5A C048 40,000 TDR 13.20 — 13.20 11.55 CD5AA048 40,500 TDR 13.50 — 13.50 11.75 CE3AA042 41,000 TDR 13.20 — 13.20 11.60 CE3AA048 41,00 ...

  • Bryant 550A - page 19

    —19— 048-F COILS + 315(A,J)A V060110 V ARIABLE-SPEED FURNA CE CC5A/CD5AA060 46,000 TDR 13.00 — 13.00 12.00 CC5A/CD5A C048 45,000 TDR 13.00 — 13.00 11.70 CC5A/CD5A W048 45,500 TDR 13.50 — 13.50 11.95 CD5AA048 45,500 TDR 13.50 — 13.50 11.95 CE3AA048 46,000 TDR 13.00 — 13.00 11.95 CE3AA060 47,000 TDR 14.00 — 14.00 12.35 CK3BA048 46,000 ...

  • Bryant 550A - page 20

    —20— 048-F CK5P A060 46,500 TDR&TXV 13.00 — — 11.70 CK5PT060 46,500 TDR&TXV 13.00 — — 11.70 CK5PX060 47,500 TDR&TXV 13.50 — — 12.05 COILS + 355MA V060120 V ARIABLE-SPEED FURNACE CC5A/CD5AA060 46,500 TDR 13.00 — 13.00 11.55 CC5A/CD5A W048 46,000 TDR 13.00 — 13.00 11.50 CC5A/CD5A W060 47,000 TDR 13.50 — 13.50 12.00 C ...

  • Bryant 550A - page 21

    —21— COMBINA TION RA TINGS Continued UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH FA C T OR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Bryant Gas Furnace or Accessory TDR + TXV‡ Accessory Puron TXV‡ 060-H *CD5PX060 59,000 TXV — 13.00 — — 11.05 CC5A/CD5AA060 56,000 NONE — — 12.50 — ...

  • Bryant 550A - page 22

    —22— *T ested combination. † In most cases, only one method should be used to achie ve TDR function. Using more than one method in a system may cause deg radation in perf or mance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a furnace equipped with TDR. Most Br yant furnaces are equipped with TDR. ‡ TXV must be Puron compati ...

  • Bryant 550A - page 23

    —23— DET AILED COOLING CAP A CITIES* See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** T o ...

  • Bryant 550A - page 24

    —24— DET AILED COOLING CAP A CITIES* continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sy ...

  • Bryant 550A - page 25

    —25— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sy ...

  • Bryant 550A - page 26

    —26— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sy ...

  • Bryant 550A - page 27

    —27— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sy ...

  • Bryant 550A - page 28

    —28— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sy ...

  • Bryant 550A - page 29

    —29— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sy ...

  • Bryant 550A - page 30

    —30— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sy ...

  • Bryant 550A - page 31

    —31— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sy ...

  • Bryant 550A - page 32

    —32— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sy ...

  • Bryant 550A - page 33

    —33— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sy ...

  • Bryant 550A - page 34

    —34— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sy ...

  • Bryant 550A - page 35

    —35— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sy ...

  • Bryant 550A - page 36

    —36— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sy ...

  • Bryant 550A - page 37

    —37— DET AILED COOLING CAP A CITIES* Continued See notes on page 38. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sys kW** Capacity MBtuh† T otal Sy ...

  • Bryant 550A - page 38

    —38— DET AILED COOLING CAP A CITIES* Continued NO TE: When the required data f alls between the published data, interpolation may be perf or med. Extrapolation is not an acceptable pr actice. * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length and/or ...

  • Bryant 550A - page 39

    —39— CONDENSER ONL Y RA TINGS* See notes on page 40. SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 65 75 85 95 105 115 125 550A024-G 30 TCG 20.9 19.4 17.9 16.2 14.4 12.4 10.2 7.8 SDT 69.8 79.1 88.3 97.6 106.7 115.7 124.7 133.6 KW 0.92 1.07 1.24 1.41 1.60 1.78 1.97 2.16 35 TCG 24.2 21.7 20.1 18.4 16.6 14.6 12.4 10.0 SDT 71.3 80.6 89.8 99.1 ...

  • Bryant 550A - page 40

    —40— CONDENSER ONL Y RA TINGS* Continued * ARI listing applies only to systems shown in Combination Ratings tab le. KW — Outdoor Unit Kilow atts Only SDT — Saturated T emperature Leaving Compressor (°F) SST — Saturated T emperature Entering Compressor (°F) TCG — Gross Cooling Capacity (1000 Btuh). SST °F CONDENSER ENTERING AIR TEMPER ...

  • Bryant 550A - page 41

    —41— SYSTEM DESIGN SUMMAR Y 1. Intended f or outdoor installation with free air inlet and outlet. Outdoor f an external static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor operating air temper ature without low-ambient operation accessor y is 55°F (12.8°C). 3. Maximum outdoor operating air temper ature is 125°F (51.7°C). ...

  • Bryant 550A - page 42

    —42— ...

  • Bryant 550A - page 43

    —43— ...

  • Bryant 550A - page 44

    SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 550A.24.9 © 2004 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 —4 4— PRINTED IN U.S.A. Catalog No. 5255-007 12-04 GUIDE SPECIFICATIONS GENERAL System Description Outdoor-mounted, air-coole ...

Manufacturer Bryant Category Air Conditioner

Documents that we receive from a manufacturer of a Bryant 550A can be divided into several groups. They are, among others:
- Bryant technical drawings
- 550A manuals
- Bryant product data sheets
- information booklets
- or energy labels Bryant 550A
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bryant 550A.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bryant 550A, service manual, brief instructions and user manuals Bryant 550A. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bryant 550A.

Similar manuals

A complete manual for the device Bryant 550A, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bryant 550A by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bryant 550A.

A complete Bryant manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bryant 550A - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bryant 550A, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bryant 550A, that we can find in the current document
3. Tips how to use the basic functions of the device Bryant 550A - which should help us in our first steps of using Bryant 550A
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bryant 550A
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bryant 550A in a specific country, if it was not possible to solve the problem on our own.