    DESCRIPTION The 558D/559F electric cooling rooftop units are designed to deliver optimum performance and reliability in a commercial rooftop unit. The 3 to 25 ton units are one-piece electric cooling units that are prewired and precharged with R-22 at the factory , making jobsite installation easy . Every unit is factory run-tested prior to shipmen ...

  • Bryant 558F - page 2

    DUAL COMPRESSORS AND DUAL REFRIGERA TION CIR- CUITS (090-150 and 216-300 Units) are provided. T wo com- pressors, each on its own independent circuit, provide standby reliability and high operating eff iciency . ADV ANCED DESIGN of evaporator and condenser coils pro- vides optimum heat transfer and cooling eff iciency . Coils are computer-designed ...

  • Bryant 558F - page 3

    Controls Upgrade Kit (036-150 Units) — The controls kit in- cludes high-pressure, loss-of-charge/low-pressure, and freeze protection cutout switches. The high-pressure and loss-of- charge/low-pressure switches can be easily added by screwing the switches onto Schrader-type fittings provided on the refrig- erant lines. SUGGESTED USE: • Kit prov ...

  • Bryant 558F - page 4

    Head Pressure Control — Kit consists of an outdoor-air ther- mostat that permits adequate head pressure control during cooling operation at low outdoor-ambient temperatures. Refer to T rade Prices for more details or contact your local representative. SUGGESTED USE: • When cooling at low-ambient outdoor temperatures is desired. NOTE: The head p ...

  • Bryant 558F - page 5

    ARI* CAP ACITY RA TINGS UNIT 558D NOMINAL TONS ST ANDARD CFM NET COOLING CAP ACITY (Btuh) TOT AL kW SEER† EER SOUND RA TING (Bels) Belt Drive Direct Drive 036 3 1200 35,000 4.0 10.0 9.7 8.7 8.2 048 4 1600 47,000 5.5 10.0 9.7 8.6 8.2 060 5 2000 57,500 6.7 10.0 9.7 8.5 8.2 UNIT NOMINAL TONS ST ANDARD CFM NET COOLING CAP ACITY (Btuh) TOT AL kW EER I ...

  • Bryant 558F - page 6

    DIMENSIONAL DRA WING — 558D036-072 UNIT 558D CORNER WEIGHT* ABC D Lb Kg Lb Kg Lb Kg Lb Kg 036 126 57.2 89 40.4 1 1 1 50.3 39 17.7 048 128 58.1 90 40.8 1 14 51.7 43 19.5 060 132 59.9 94 42.6 120 54.4 49 22.2 072 148 67.1 103 46.7 155 70.3 64 29.0 *Weights are for unit only (aluminum plate fins) and do not include options or crating. CONNECTION SI ...

  • Bryant 558F - page 7

    DIMENSIONAL DRA WING — 558D090-150 UNIT 558D CORNER WEIGHT* DIMENSIONS A B C D ‘‘H’ ’ ‘‘J’ ’ ‘‘K’ ’ Lb Kg Lb Kg Lb Kg Lb Kg Ft-in. mm Ft-in. mm Ft-in. mm 090 164 74 140 64 208 94 243 110 1-2 7 ⁄ 8 378 3-5 5 ⁄ 16 1050 2-9 11 ⁄ 16 856 102 165 75 141 64 209 94 245 1 1 1 3-3 7 ⁄ 8 1013 3-5 5 ⁄ 16 1050 2-9 11 ⁄ 16 8 ...

  • Bryant 558F - page 8

    DIMENSIONAL DRA WING — 559F180,216 LEGEND K O— Knockout NOTES: 1. Dimensions in ( ) are in millimeters. 2. Center of gravity . 3. Direction of airflow . 4. Ductwork to be attached to accessory roof curb or adapter only . 5. For units with electric heat, a field-supplied 90° elbow must be installed in the supply ductwork below the unit discha ...

  • Bryant 558F - page 9

    DIMENSIONAL DRA WING — 559F240,300 NOTES: 1. Dimensions in ( ) are in millimeters. 2. Center of gravity . 3. Direction of airflow . 4. Ductwork to be attached to accessory roof curb or adapter only . 5. For units with electric heat, a field-supplied 90° elbow must be installed in the supply ductwork below the unit discharge connection. 6. Mini ...

  • Bryant 558F - page 10

    DIMENSIONAL DRA WING — ROOF CURB, 558D036-072 ROOF CURB ACCESSOR Y ‘‘ A’’ UNIT SIZE 558D CRRFCURB001A00 1 8 -2 9 [356] 036-072 CRRFCURB002A00 2 8 -0 9 [610] UNIT SIZE 558D ‘ ‘B’’ ‘ ‘C’’ ‘ ‘D’ ’ AL T DRAIN HOLE POWER CONTROL CONNECTOR PKG ACY 036-072 1 8 -9 11 ⁄ 16 9 [551] 1 8 -4 9 [406] 1 3 ⁄ 4 9 [45] 3 ⁄ 4 9 ...

  • Bryant 558F - page 11

    DIMENSIONAL DRA WING — ROOF CURB, 558D090-150 ROOF CURB ACCESSOR Y ‘‘ A’’ UNIT SIZE 558D CRRFCURB003A00 1 8 -2 9 [356] 090-150 CRRFCURB004A00 2 8 -0 9 [610] SERVICE PLA TE SIZES UNIT SIZE 558D ‘ ‘B’’ ‘ ‘C’’ ‘ ‘D’’ AL T DRAIN HOLE POWER CONTROL CONNECTOR PKG ACY 090-150 2 8 -8 7 ⁄ 16 9 [827] 1 8 -10 15 ⁄ 16 9 [5 ...

  • Bryant 558F - page 12

    DIMENSIONAL DRA WING — HORIZONT AL AND VERTICAL ROOF CURBS AND HORIZONT AL ADAPTER — 559F180-300 ACCESSOR Y P ACKAGE NO. CURB HEIGHT DESCRIPTION ‘‘A ’’ ‘ ‘B’’ ‘ ‘C’ ’ 308450-201 1 8 -2 9 (305) Standard Curb — 14 9 High —— — 308450-202 2 8 -0 9 (610) Standard Curb for Units Requiring High Installation —— — 3 ...

  • Bryant 558F - page 13

    DIMENSIONAL DRA WING — HORIZONT AL ADAPTER INST ALLA TION — 559F180-300 NOTE: 389210-201 is a fully factory preassembled horizontal adapter which includes an insulated high static regain transition duct and substantially improves fan static performance. 13 ...

  • Bryant 558F - page 14

    SPECIFICA TIONS — 558D036-072 UNIT SIZE 036 048 060 072 NOMINAL CAP ACITY (tons) 3456 OPERA TING WEIGHT (lb) Unit Al/Al* 365 375 395 470 Economizer Durablade 34 34 34 34 Parablade 42 42 42 42 Roof Curb† 11 5 11 5 11 5 11 5 COMPRESSOR Hermetic Quantity No. Cylinders (per circuit) 1 2 1 2 1 2 1 2 Oil (oz) 50 50 50 54 REFRIGERANT TYPE R-22 Operati ...

  • Bryant 558F - page 15

    SPECIFICA TIONS — 558D090-150 UNIT SIZE 090 102 120 150 NOMINAL CAP ACITY (tons) 7 1 ⁄ 2 8 1 ⁄ 2 10 12 1 ⁄ 2 OPERA TING WEIGHT (lb) Unit Al/Al* 755 760 915 930 Economizer Durablade 44 44 44 44 Parablade 62 62 62 62 Roof Curb† 143 143 143 143 COMPRESSOR Hermetic Quantity No. Cylinders (per circuit) 2 2 2 2 2 2 2 2 Oil (oz) 50 ea 50 ea 50 e ...

  • Bryant 558F - page 16

    SPECIFICA TIONS — 559F180-300 UNIT SIZE 180 216 240 300 208/230,460 V 575 V NOMINAL CAP ACITY (tons) 15 18 20 25 OPERA TING WEIGHT (lb) Unit Al/Al* 1500 2050 2100 2150 Economizer 11 0 11 0 11 0 11 0 Roof Curb† 200 200 200 200 COMPRESSOR Semi-Hermetic Quantity No. Cylinders (per circuit) 1 6 2 6 2 6 2 6 Oil (oz) 1 15 1 15,88 1 15 ea 128 ea REFRI ...

  • Bryant 558F - page 17

    SELECTION PROCEDURE (With 559F180 Example) I Determine cooling and heating requirements at design conditions. Given: Cooling Capacity Required (TC) ......... 177,000 Btuh Sensible Heat Capacity (SHC) .......... 127,000 Btuh Condenser Entering-Air T emperatur e..................9 5 F Edb/78 F Ewb Indoor-Air T emperature ...........8 0 F Edb/67 F Ewb ...

  • Bryant 558F - page 18

    GROSS COOLING CAP ACITIES 558D036 (3 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible 900 0.1 1 72 42.8 20.0 2.91 40.8 19.4 3.14 38.7 18.6 3.35 67 38.9 24.5 2.81 36.9 23.7 3.01 34.9 22 ...

  • Bryant 558F - page 19

    GROSS COOLING CAP ACITIES (cont) 558D060 (5 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible 1500 0.07 72 71.0 33.9 5.04 69.2 33.4 5.50 65.5 32.1 5.88 67 63.8 41.5 4.82 61.0 40.5 5.27 ...

  • Bryant 558F - page 20

    GROSS COOLING CAP ACITIES (cont) 558D090 (7 1 ⁄ 2 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible 2250 0.07 72 102.8 49.4 7.14 98.6 48.0 7.66 93.8 46.4 8.18 67 94.8 61.8 6.82 90.2 6 ...

  • Bryant 558F - page 21

    GROSS COOLING CAP ACITIES (cont) 558D120 (10 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible 3000 0.095 72 135.8 66.8 9.76 130.0 64.3 10.41 124.1 62.2 1 1.13 67 124.8 82.6 9.41 1 19.6 ...

  • Bryant 558F - page 22

    GROSS COOLING CAP ACITIES (cont) 559F180 (15 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible 4500 0.08 72 212.0 101.0 15.20 205.0 98.5 16.60 197.0 95.8 18.00 67 195.0 126.0 14.70 188. ...

  • Bryant 558F - page 23

    GROSS COOLING CAP ACITIES (cont) 559F216 (18 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 105 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible T otal Sensible 5400 0.06 72 242.0 121.6 14.72 231.0 1 16 ...

  • Bryant 558F - page 24

    GROSS COOLING CAP ACITIES (cont) 559F240 (20 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 105 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible T otal Sensible 6000 0.06 72 274.0 130.4 16.92 264.0 127. ...

  • Bryant 558F - page 25

    GROSS COOLING CAP ACITIES (cont) 559F300 (25 TON) Air Entering Evaporator Air Entering Condenser (F) 75 85 95 105 Cfm BF Ewb (F) Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW Capacity MBtuh Compressor kW T otal Sensible T otal Sensible T otal Sensible T otal Sensible 7,000 0.03 72 323.9 159.4 21.10 315.3 156 ...

  • Bryant 558F - page 26

    AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS 558D036 (3 TON) Airflow (Cfm) Standard Direct-Drive Motor Low Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts 900 0.67 0.21 253 0.68 0.23 277 0.69 0.26 307 0.69 0.31 363 1000 0.60 0.23 270 0.61 0.25 292 0.61 0.27 321 0.63 ...

  • Bryant 558F - page 27

    AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS (cont) 558D048 (4 TON) Airflow (Cfm) Standard Direct-Drive Motor Low Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts 1200 0.93 0.41 458 0.94 0.45 506 0.94 0.51 572 0.99 0.56 632 1300 0.86 0.42 471 0.87 0.46 521 0.87 0.52 ...

  • Bryant 558F - page 28

    AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS (cont) 558D060 (5 TON) Airflow (Cfm) Standard Direct-Drive Motor Low Speed Medium Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp Watts ESP Bhp W atts 1500 0.88 0.67 750 1.20 0.71 791 1.19 0. ...

  • Bryant 558F - page 29

    AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS (cont) 558D072 (6 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp Watts 1800 852 0.55 562 905 0.62 615 1002 0.78 739 1084 0.93 859 1 163 1.10 998 1900 894 0.64 630 945 0.72 692 ...

  • Bryant 558F - page 30

    AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS (cont) 558D090 (7 1 ⁄ 2 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 2250 51 1 0.52 539 592 0.74 708 659 0.95 875 722 1.19 1072 778 1.43 1275 82 ...

  • Bryant 558F - page 31

    AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS (cont) 558D102 (8 1 ⁄ 2 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 2550 557 0.71 684 633 0.94 867 697 1.18 1064 756 1.42 1267 81 1 1.69 1499 8 ...

  • Bryant 558F - page 32

    AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS (cont) 558D120 (10 TON) Airflow (Cfm) Standard and Alternate Belt-Drive Motors External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 3000 532 0.64 630 605 0.81 763 670 0.97 891 725 1.12 1014 778 1.28 ...

  • Bryant 558F - page 33

    AIR DELIVER Y — 558D036-150 VERTICAL DISCHARGE UNITS (cont) 558D150 (12 1 ⁄ 2 TON) Airflow (Cfm) Standard and Alernate Belt-Drive Motors External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp Watts 3750 661 1.16 1097 721 1.36 1255 774 1.55 1415 821 1.72 1556 867 ...

  • Bryant 558F - page 34

    AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS 558D036 (3 TON) Airflow (Cfm) Standard Direct-Drive Motor Low Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts 900 0.72 0.21 253 0.75 0.23 277 0.73 0.26 307 0.76 0.31 363 1000 0.67 0.23 270 0.69 0.25 292 0.70 0.27 321 0 ...

  • Bryant 558F - page 35

    AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS (cont) 558D048 (4 TON) Airflow (Cfm) Standard Direct-Drive Motor Low Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts 1200 0.93 0.41 458 0.97 0.45 506 1.04 0.51 572 1.09 0.56 632 1300 0.86 0.42 471 0.90 0.46 521 0.96 0. ...

  • Bryant 558F - page 36

    AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS (cont) 558D060 (5 TON) AIRFLOW (Cfm) Standard Direct-Drive Motor Low Speed Medium Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v 208 v 230, 460, 575 v ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp W atts ESP Bhp Watts ESP Bhp Watts 1500 1.01 0.67 750 1.25 0.71 791 1.26 0 ...

  • Bryant 558F - page 37

    AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS (cont) 558D072 (6 TON) AIRFLOW (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts 1800 765 0.45 487 821 0.51 532 923 0.65 638 1019 0.81 843 1099 0.96 883 1900 802 0.45 539 854 0.58 58 ...

  • Bryant 558F - page 38

    AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS (cont) 558D090 (7 1 ⁄ 2 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 2250 465 0.43 473 554 0.64 630 630 0.86 803 695 1.09 989 757 1.34 1 199 2300 471 0.45 487 5 ...

  • Bryant 558F - page 39

    AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS (cont) 558D102 (8 1 ⁄ 2 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 2550 501 0.57 577 587 0.79 747 659 1.05 956 722 1.29 1 156 780 1.55 1378 2660 507 0.59 592 ...

  • Bryant 558F - page 40

    AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS (cont) 558D120 (10 TON) Airflow (Cfm) Standard and Alternate Belt-Drive Motors External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 3000 484 0.55 562 560 0.70 677 631 0.87 810 690 1.03 940 747 1.20 1081 3100 495 0.6 ...

  • Bryant 558F - page 41

    AIR DELIVER Y — 558D036-150 HORIZONT AL DISCHARGE UNITS (cont) 558D150 (12 1 ⁄ 2 TON) Airflow (Cfm) Standard and Alternate Belt-Drive Motors External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts 3750 614 1.01 979 676 1.22 1142 737 1.41 1300 789 1.61 1465 838 1.78 1603 380 ...

  • Bryant 558F - page 42

    AIR DELIVER Y — 559F180-300 UNITS 559F180 (15 TON) Airflow (Cfm) Standard Belt-Drive Motor; 208/230-V and 460-V Units External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.1 Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts 4500 790 1.02 906 879 1.23 1092 960 1.43 1270 1039 1.64 1456 1 114 1.85 1643 1 152 ...

  • Bryant 558F - page 43

    AIR DELIVER Y — 559F180-300 UNITS (cont) 559F180 (15 TON) Airflow (Cfm) Standard Belt-Drive Motor; 575-V Units External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.1 Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts 4500 790 1.02 906 879 1.23 1092 960 1.43 1270 1039 1.64 1456 1 114 1.85 1643 1 152 1.97 17 ...

  • Bryant 558F - page 44

    AIR DELIVER Y — 559F180-300 UNITS (cont) 559F216 (18 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 5400 650 1.24 1095 750 1.54 1366 844 1.84 1646 930 2.14 1942 1011 2.54 2258 5500 658 1.30 1143 757 1.60 1418 850 1.90 17 ...

  • Bryant 558F - page 45

    AIR DELIVER Y — 559F180-300 UNITS (cont) 559F240 (20 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp Watts 6000 702 1.60 1428 796 1.90 1723 884 2.30 2025 965 2.60 2339 1041 3.00 2669 6500 747 2.00 1757 835 2.30 2073 919 2.70 2394 ...

  • Bryant 558F - page 46

    AIR DELIVER Y — 559F180-300 UNITS (cont) 559F300 (25 TON) Airflow (Cfm) Standard Belt-Drive Motor External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 7,000 832 2.49 2297 916 2.86 2634 993 3.23 2978 1065 3.62 3332 1 134 4.01 3,697 1200 4.43 4,076 7,500 ...

  • Bryant 558F - page 47

    ACCESSOR Y/FIOP ST A TIC PRESSURE* (in. wg) — 558D036-072 COMPONENT CFM 900 1200 1400 1600 1800 2000 2200 2400 2600 3000 1 Heater Module 0.05 0.07 0.09 0.09 0.10 0.1 1 0.1 1 0.12 0.13 0.15 2 Heater Modules 0.15 0.16 0.16 0.16 0.17 0.17 0.17 0.18 0.18 0.19 Durablade Economizer 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 Parablade Economizer ...

  • Bryant 558F - page 48

    F AN RPM A T MOTOR PULLEY SETTINGS* UNIT MOTOR PULLEY TURNS OPEN 0 1 ⁄ 2 11 1 ⁄ 2 22 1 ⁄ 2 33 1 ⁄ 2 44 1 ⁄ 2 55 1 ⁄ 2 6 558D036† 1000 976 952 928 904 880 856 832 808 784 760 — — 558D048† 1 185 1 150 1 1 15 1080 1045 1010 975 940 905 870 835 — — 558D060† 1300 1260 1220 1 180 1 140 1 100 1060 1020 980 940 900 — — 558D072 ...

  • Bryant 558F - page 49

    ELECTRICAL DA T A — 558D036-072 UNIT 558D NOMINAL V -PH-Hz IFM TYPE VOL T AGE RANGE COMPR (each) OFM IFM ELECTRIC HEA T* POWER SUPPL Y DISCONNECT SIZE† Min Max RLA LRA Quantity Hp FLA FLA Nominal kW** FLA MCA MOCP†† FLA LRA 036 (3 T on) 208/230-1-60 Std 187 254 16.9 86.7 1 1 ⁄ 4 1.4 2.8 — — 25.3/ 25.3 35/ 35 24/ 24 97/ 97 3.3/ 4.4 15. ...

  • Bryant 558F - page 50

    ELECTRICAL DA T A — 558D036-072 (cont) UNIT 558D NOMINAL V -PH-Hz IFM TYPE VOL T AGE RANGE COMPR (each) OFM IFM ELECTRIC HEA T* POWER SUPPL Y DISCONNECT SIZE† Min Max RLA LRA Quantity Hp FLA FLA Nom kW** FLA MCA MOCP†† FLA LRA 060 (5 T on) 208/230-1-60 Std 187 254 28.3 141 1 1 ⁄ 4 1.4 5.9 — — 42.7/ 42.7 50/ 50 43/ 43 155/155 4.9/ 6.5 ...

  • Bryant 558F - page 51

    ELECTRICAL DA T A — 558D090-150 UNIT 558D NOMINAL V -PH-Hz IFM VOL T AGE RANGE COMPR (ea) OFM (ea) IFM ELECTRIC HEA T* POWER SUPPL Y DISCONNECT SIZE† Min Max RLA LRA Qty Hp FLA FLA Nom kW** FLA MCA MOCP†† FLA LRA 090 (7 1 ⁄ 2 T ons) 208/230-3-60 Std 187 254 13.6 73.4 2 1 ⁄ 4 1.4 5.8 — — 39.2/ 39.2 45/ 45 41/ 41 194/194 7.8/10.4 21.7 ...

  • Bryant 558F - page 52

    ELECTRICAL DA T A — 558D090-150 (cont) UNIT 558D NOMINAL V -PH-Hz IFM VOL T AGE RANGE COMPR (ea) OFM IFM ELECTRIC HEA T* POWER SUPPL Y DISCONNECT SIZE† Min Max RLA LRA Qty Hp FLA FLA Nom kW** FLA MCA MOCP†† FLA LRA 150 (12 1 ⁄ 2 T ons) 208/230-3-60 Std 187 254 22.3 142.0 2 1 ⁄ 4 1.4 10.6 — — 63.6/ 63.6 70/ 70 67/ 67 375/375 7.8/10 ...

  • Bryant 558F - page 53

    ELECTRICAL DA T A — 559F180-300 UNITS UNIT 559F NOMINAL V -PH-Hz VOL T AGE RANGE COMPRESSOR OFM IFM POWER EXHAUST ELECTRIC HEA T* POWER SUPPL Y No. 1 No. 2 Min Max RLA LRA RLA LRA Quantity Hp FLA (ea) FLA FLA LRA FLA Nom kW** MCA MOCP†† 180 208/230-3-60 187 254 61.0 266 — — 3 1 ⁄ 2 1.70 10.5/10.5 —— —/— —/— 92/ 92 150/150 72 ...

  • Bryant 558F - page 54

    ELECTRICAL DA T A — 559F180-300 UNITS (cont) UNIT 559F NOMINAL V -PH-Hz VOL T AGE RANGE COMPRESSOR OFM IFM POWER EXHAUST ELECTRIC HEA T* POWER SUPPL Y No. 1 No. 2 Min Max RLA LRA RLA LRA Quantity Hp FLA (ea) FLA FLA LRA FLA Nom kW** MCA MOCP†† 240 208/230-3-60 187 254 35.6 198 35.6 198 2 1 5.50 25.0/25.0 —— —/— —/— 1 16/1 16 150/1 ...

  • Bryant 558F - page 55

    OPERA TING SEQUENCE COOLING, UNITS WITHOUT ECONOMIZER — When thermo- stat calls for cooling, terminals G and Y1 are energized. The in- door (evaporator) fan contactor (IFC) and compressor contactor no. 1 (C1) are energized and evaporator-fan motor , compressor no. 1 (036-150 and 216-300) or unloaded compressor (180), and condenser fan(s) start. T ...

  • Bryant 558F - page 56

    TYPICAL WIRING SCHEMA TIC — 558D036-150 (See Legend, page 59.) 56 ...

  • Bryant 558F - page 57

    TYPICAL WIRING SCHEMA TIC — 559F180-300 (See Legend, page 59.) 57 ...

  • Bryant 558F - page 58

    TYPICAL INST ALLA TION — 558D090-150 V ertical Discharge Ducting NEC — National Electrical Code Horizontal Discharge Ducting 58 ...

  • Bryant 558F - page 59

    TYPICAL INST ALLA TION — 559F180-300 NEC — National Electrical Code NOTES: 1. Illustration shown is a general guide only and is not intended to include all details for any specific installation. 2. Installation must comply with all applicable codes. LEGEND FOR TYPICAL WIRING SCHEMA TICS AHA — Adjustable Heat Anticipator BRK W/A T — Breaks ...

  • Bryant 558F - page 60

    APPLICA TION DA T A 1. Units approved for outdoor installation only . 2. Ductwork (036-150) — Secure vertical discharge ductwork to roof curb. For horizontal discharge applications, either at- tach ductwork to unit, or use field-supplied flanges attached to the horizontal discharge openings and attach all duct- work to flanges. 3. Ductwork (18 ...

  • Bryant 558F - page 61

    APPLICA TION DA T A (cont) OPTION AND ACCESSOR Y LIST ITEM OPTION* ACCESSOR Y† Durablade Economizer (036-150; Includes Hood) XX Parablade Economizer (036-150) X Integrated Economizer (180-300) XX Manual Outdoor-Air Dampers** X X†† Controls Upgrade Kit (036-150) | XX Condenser Coil Grille (036-150) XX Alternate Drive (090) X Alternate Motor an ...

  • Bryant 558F - page 62

    APPLICA TION DA T A (cont) EV APORA TOR-F AN MOTOR PERFORMANCE UNIT EV APORA TOR-F AN MOTOR UNIT VOL T AGE MAXIMUM ACCEPT ABLE CONTINUOUS BHP* MAXIMUM ACCEPT ABLE OPERA TING W A TTS MAXIMUM AMP DRA W 558D036 Standard 208/230 0.34 440 2.9 460 1.4 575 1.4 Alternate 208/230 1.00 1000 5.1 460 2.3 575 2.3 558D048 Standard 208/230 0.75 850 3.7 460 1.9 57 ...

  • Bryant 558F - page 63

    APPLICA TION DA T A (cont) Durablade Economizer/T wo-Position Damper Barometric Relief Damper Characteristics (558D036-150 Only) Parablade Economizer Barometric Relief Damper Characteristics — 558D090-150 Parablade Economizer Barometric Relief Damper Characteristics — 558D036-072 EV APORA T OR-F AN MOTOR EFFICIENCY UNIT MOTOR EFFICIENCY (%) 558 ...

  • Bryant 558F - page 64

    ELECTRIC HEA TER CAP ACITIES — 558D036-150 UNIT 558D VOL T AGE (60 Hz) ACCESSORY kW 036 208/230 (single phase) 4.4 6.5 8.7 10.5 13.0* 208/230 (3 phase) 4.4 6.5 8.7 10.5 16.0 460 (3 phase) 6.0 8.8 1 1.5 14.0 048 208/230 (single phase) 4.4 8.7 13.0* 17.4* 21.0* 208/230 (3 phase) 6.5 8.7 16.0 21.0* 460 (3 phase) 6.0 1 1.5 14.0* 23.0* 060 208/230 (si ...

  • Bryant 558F - page 65

    ENGINEERS’ SPECIFICA TION GUIDE — MODELS 558D036-150 (3 TO 12 1 ⁄ 2 TONS) GENERAL: Furnish and install single-package, outdoor rooftop- mounted, electrically controlled cooling unit utilizing a recipro- cating compressor . Unit shall discharge supply air vertically or horizontally as shown on the contract drawings. Nominal unit electrical cha ...

  • Bryant 558F - page 66

    ENGINEERS’ SPECIFICA TION GUIDE — MODELS 559F180-300 (15 TO 25 TONS) GENERAL: Furnish and install single-package, outdoor rooftop- mounted, electrically controlled cooling unit utilizing reciprocat- ing compressor(s) for cooling. Unit shall discharge supply air vertically or horizontally as shown on the contract drawings. Nominal unit electrica ...

  • Bryant 558F - page 67

    ...

  • Bryant 558F - page 68

    Bryant Air Conditioning Copyright 1996 Carrier Corporation SPECIFICA TIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INST ALLED IN ACCORDANCE WITH INST ALLATION INSTRUCTIONS Printed in U.S.A. 6/96 CA TALOG NO. BY -3255-818 ...

Manufacturer Bryant Category Automobile

Documents that we receive from a manufacturer of a Bryant 558F can be divided into several groups. They are, among others:
- Bryant technical drawings
- 558F manuals
- Bryant product data sheets
- information booklets
- or energy labels Bryant 558F
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bryant 558F.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bryant 558F, service manual, brief instructions and user manuals Bryant 558F. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bryant 558F.

Similar manuals

A complete manual for the device Bryant 558F, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bryant 558F by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bryant 558F.

A complete Bryant manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bryant 558F - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bryant 558F, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bryant 558F, that we can find in the current document
3. Tips how to use the basic functions of the device Bryant 558F - which should help us in our first steps of using Bryant 558F
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bryant 558F
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bryant 558F in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bryant 558F?

Use the form below

If you did not solve your problem by using a manual Bryant 558F, ask a question using the form below. If a user had a similar problem with Bryant 558F it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (1)

Estíbaliz

Hola ,buenas noches el año pasado nos compramos la polaroid cube en mediamark ,ha estado funcionando con normalidad tras un periodo de no usarla la hemos vuelto a utilizar y solo graba o hace fotos cuando el cable está conectado a la red ,cuando la cargamos en el ordenador o en la pared con adaptador enseguida se pone verde como si estaría cargada y cuando se desenchufa no se enciende en resumen no carga .Gracias .Un saludo