    Form No. PDS 593C.18.7 ELECTRIC AIR CONDITIONER Model 593C (60 Hz) Sizes 018 thru 060 WEA THER-PRO TECTIVE CABINET —Steel is galvaniz ed and coated with a la yer of zinc phosphate . A coat of modified poly- ester powder coating is then applied and bak ed-on, providing each unit with a hard, smooth finish that will last f or many y ears. All scr ...

  • Bryant 593C - page 2

    — 2 — AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW. 2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE ...

  • Bryant 593C - page 3

    — 3 — RECOMMENDED TUBE DIAMETERS * For tube sets betw een 50 and 175 ft, consult Residential Split System Long-Line Application Guideline. CHECK-FLO-RA TER ® PIST ON * Piston listed is f or any appro ved non-capillary tube coil combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil. UNIT SIZE LIQUID ...

  • Bryant 593C - page 4

    — 4 — SPECIFICA TIONS See notes on page 5. UNIT SIZE 018-C, D 024-C, D 030-C, D 036-C, D Operating W eight (Lb) 137 143 161 169 ELECTRICAL Unit V olts — Her tz — Phase 208 – 230 — 60 — 1 Operating V oltage Range* 197 — 253 Compressor — Rated Load Amps 8.6 10.9 13.7 15.0 Lock ed Rotor Amps 49.0 56.0 75.0 82.0 Condenser F an Motor ? ...

  • Bryant 593C - page 5

    — 5 — SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will operate satisf actorily . Operation outside these limits may result in unit f ailure. † If wire is applied at ambient greater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70). The ampacity of nonmetallic-sheathed cab le ...

  • Bryant 593C - page 6

    — 6 — A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) 1. Ball Bearing Fan Motor A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication. SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation f eature) or MotorMaster ® Control has been added. 2. Coastal Filter A ...

  • Bryant 593C - page 7

    — 7 — A CCESSOR Y DESCRIPTION AND USE (Listed Alphabetically) Continued 17. Time Delay Rela y An SPST dela y relay which brie fl y continues oper ation of the indoor blower motor to pro vide additional cooling after the compressor cycles off. SUGGESTED USE: For impro ved ef fi ciency ratings f or cer tain combinations of indoor and outdoor un ...

  • Bryant 593C - page 8

    — 8 — COMBINA TION RA TINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 018-C, D CC5A/CD5AA018* 17,200 NONE 10.00 10.50 10.50 CC5A/CD5AA024 17,800 NONE 10.50 11.00 11.00 CC5A/CD5A W024 17,800 NONE 10.50 11. ...

  • Bryant 593C - page 9

    — 9 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 030-C, D CC5A/CD5AA030* 28,600 NONE 10.00 10.20 10.20 CC5A/CD5AA036 29,000 NONE 10.10 10.50 10.50 CC5A/CD5A W030 28,600 NON ...

  • Bryant 593C - page 10

    — 10 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 036-C, D CC5A/CD5AA036* 34,600 NONE 10.00 10.20 10.20 CC5A/CD5AA042 34,600 NONE 10.00 10.20 10.20 CC5A/CD5A W042 34,600 NO ...

  • Bryant 593C - page 11

    — 11 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 036-C, D COILS + 355MA V042040 V ARIABLE-SPEED FURNA CE CC5A/CD5AA036 34,600 NONE 11.00 — 11.00 CK3BA036 34,000 NONE 10. ...

  • Bryant 593C - page 12

    — 12 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 042-C, D CK5A/CK5BA042 39,500 TDR 11 11 10.15 CK5A/CK5BA048 40,000 TDR 11 11 10.25 CK5A/CK5BT042 39,500 TDR 11 11 10.15 CK ...

  • Bryant 593C - page 13

    — 13 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 048-C FB4(A,B)NB070 48,000 TDR 11.00 — 11.00 FC4(B,C)N(F ,B)048 46,500 TDR & TXV 10.40 —— FC4(B,C)N(F ,B)060 47, ...

  • Bryant 593C - page 14

    — 14 — COMBINA TION RA TINGS Contin ued * T ested combination. † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system may cause deg radation in performance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a fur nace equipped with TDR. Most Bryant furnaces are equipped with TDR. ...

  • Bryant 593C - page 15

    — 15 — DET AILED COOLING CAP ACITIES* See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** T otal Sen ...

  • Bryant 593C - page 16

    — 16 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 17

    — 17 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 18

    — 18 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 19

    — 19 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 20

    — 20 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 21

    — 21 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 22

    — 22 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 23

    — 23 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** Capacity MBtuh † T otal System kW** ...

  • Bryant 593C - page 24

    — 24 — DET AILED COOLING CAP ACITIES* Contin ued NO TE: When the required data fall betw een the published data, interpolation may be perf ormed. Extrapolation is not an acceptab le practice. * Detailed cooling capacities are based on indoor and outdoor unit at same ele vation per ARI standard 210/240-94. If additional tubing length and/or indo ...

  • Bryant 593C - page 25

    — 25 — CONDENSER ONL Y RA TINGS* See notes on page 26. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 593C018-C, D TCG 17.9 16.6 15.3 14.0 12.7 11.3 10.0 30 SDT 75.7 84.2 93.0 102.0 111.0 120.0 129.0 KW 1.10 1.18 1.26 1.33 1.39 1.44 1.46 TCG 19.8 18.5 17.1 15.7 14.3 12.9 11.5 35 SDT 77.7 86.2 94.8 104.0 112.0 121.0 13 ...

  • Bryant 593C - page 26

    — 26 — CONDENSER ONL Y RA TINGS* Continued * ARI listing applies only to systems shown in Ratings and P erformance table. KW — T otal P ower (kW) SDT — Saturated T emperature Lea ving Compressor ( ° F) SST — Saturated T emperature Entering Compressor ( ° F) TCG — Gross Cooling Capacity (1000 Btuh) SST ° F CONDENSER ENTERING AIR TEMPE ...

  • Bryant 593C - page 27

    — 27 — SYSTEM DESIGN 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan e xter nal static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature without lo w ambient operation accessor y is 55 ° F (12.8 ° C). 3. Maximum outdoor operating air temperature is 125 ° F (51.7 ° C). ...

  • Bryant 593C - page 28

    — 28 — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 593C.18.6 © 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 PRINTED IN U.S.A. Catalog No. 5259-301 2-03 GUIDE SPECIFICATIONS GENERAL System Description Outdoor-mounted, air-coo ...

Manufacturer Bryant Category Air Conditioner

Documents that we receive from a manufacturer of a Bryant 593C can be divided into several groups. They are, among others:
- Bryant technical drawings
- 593C manuals
- Bryant product data sheets
- information booklets
- or energy labels Bryant 593C
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bryant 593C.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bryant 593C, service manual, brief instructions and user manuals Bryant 593C. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bryant 593C.

Similar manuals

A complete manual for the device Bryant 593C, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bryant 593C by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bryant 593C.

A complete Bryant manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bryant 593C - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bryant 593C, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bryant 593C, that we can find in the current document
3. Tips how to use the basic functions of the device Bryant 593C - which should help us in our first steps of using Bryant 593C
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bryant 593C
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bryant 593C in a specific country, if it was not possible to solve the problem on our own.