Manual Vector 6SE70 VC

57 pages 0.61 mb
Download

Go to site of 57

Summary
  • Vector 6SE70 VC - page 1

    DROM-02069 Quick Startup Gu ide for SIMOVERT MASTERDRIVES 6SE70 VC Vector Control Section 1: Parameterization of Base Dri ve Section 2: Parameterization of Rectifier Section 3: Simovis Trace Setu p Method Section 4: When Shoul d a Dri ve be re-Tune d ...

  • Vector 6SE70 VC - page 2

    Page 2 Versio n 1.0 March 1, 2000 We reserv e the right to modify functions, technical data, standards, dr awings and parameters. We have che cked the content s of this document to ensure th at they coincide with the described hard ware and software. However, dev iations cannot be completely ruled-out, so we cannot guarantee complete conformance. H ...

  • Vector 6SE70 VC - page 3

    Version 1.0 March 1, 2000 Page 3 Note: This Quick Startup Guide is not an autonomous document, but is intended to direct users to the section in the Operating Instructio ns which are important for start -up. Thus, these brief instructions can only be completel y valid when used in conjunction with the Operating Instructions. It is especially import ...

  • Vector 6SE70 VC - page 4

    Page 4 Versio n 1.0 March 1, 2000 ...

  • Vector 6SE70 VC - page 5

    Version 1.0 March 1, 2000 Page 5 Section 1: Parameterization of Base Unit SIMOVERT MASTERDRIVES 6SE70 VC Vector Control 1.1 Power Section Defintion 1.2 Factory Reset 1.3 Basic Start-up 1.3.1 Volts/Hz w ithout encoder feedback 1.3.2 Volts/Hz with encod er feedback 1.3.3 Vector Control without enc oder feedb ack 1.3.4 Vector Control with encod er fee ...

  • Vector 6SE70 VC - page 6

    Page 6 Versio n 1.0 March 1, 2000 ...

  • Vector 6SE70 VC - page 7

    Version 1.0 March 1, 2000 Page 7 1.1 Power Section Definition Note: Pow er Section is pre -defined at the factory . Powe r Section Definition is required if a new board CUVC board is put in to the drive or boards are switched between uni ts with d ifferent ratings. Driv e should be defaulted and re-parame terized after Pow er Sectio n Definition. P ...

  • Vector 6SE70 VC - page 8

    Page 8 Versio n 1.0 March 1, 2000 Unit List P070: Parameter Value (P WE) P072: Rated Output Current in Amp s In[A] Frequency Conv erter AC-AC type 3 AC 200V to 230V PWE Order Number In[A ] *1 14 6SE7021-1CA60 10.6 21 6SE7021-3CA60 13.3 27 6SE7021-8CB60 17.7 32 6SE7022-3CB60 22.9 39 6SE7023-2CB60 32.2 48 6SE7024-4CC60 44.2 54 6SE7025-4CD60 54.0 64 6 ...

  • Vector 6SE70 VC - page 9

    Version 1.0 March 1, 2000 Page 9 Frequency Conv erter AC-AC type 3 AC 380V to 460V PWE A ir Cool ed PWE Water Cooled Order Number In[A ] *1 3 6SE7016-1EA61 6.1 9 6SE7018-0EA61 8.0 11 6SE7021-0EA61 10.2 18 6SE7021-3EB61 13.2 25 6SE7021-8EB61 17.5 35 6SE7022-6EC61 25.5 42 6SE7023-4EC61 34.0 46 6SE7023-8ED61 37.5 52 6SE7024-7ED61 47.0 56 6SE7026-0ED61 ...

  • Vector 6SE70 VC - page 10

    Page 10 Versio n 1.0 March 1, 2000 Frequency Inv erter DC-AC type DC 510V to 650V PWE A ir Cool ed PWE Water Cooled Order Number In [A ] *1 4 6SE7016-1TA61 6.1 10 6SE7018-0TA61 8.0 12 6SE7021-0TA61 10.2 19 6SE7021-3TB61 13.2 26 6SE7021-8TB61 17.5 36 6SE7022-6TC61 25.5 43 6SE7023-4TC61 34.0 47 6SE7023-8TD61 37.5 53 6SE7024-7TD61 47.0 57 6SE7026-0TD6 ...

  • Vector 6SE70 VC - page 11

    Version 1.0 March 1, 2000 Page 11 Frequency Conv erter AC-AC type 3 AC 500V to 575V PWE A ir Cool ed PWE Water Cooled Order Number In[A ] *1 1 6SE7014-5FB61 4.5 5 6SE7016-2FB61 6.2 7 6SE7017-8FB61 7.8 16 6SE7021-1FB61 11.0 23 6SE7021-5FB61 15.1 30 6SE7022-2FC61 22.0 37 6SE7023-0FD61 29.0 44 6SE7023-4FD61 34.0 50 6SE7024-7FD61 46.5 60 6SE7026-1FE60 ...

  • Vector 6SE70 VC - page 12

    Page 12 Versio n 1.0 March 1, 2000 Frequency Inv erter DC-AC type DC 675V to 810V PWE A ir Cool ed PWE Water Cooled Order Number In [A ] *1 2 6SE7014-5UB61 4.5 6 6SE7016-2UB61 6.2 8 6SE7017-8UB61 7.8 17 6SE7021-1UB61 11.0 24 6SE7021-5UB61 15.1 31 6SE7022-2UC61 22.0 38 6SE7023-0UD61 29.0 45 6SE7023-4UD61 34.0 51 6SE7024-7UD61 46.5 61 6SE7026-1UE60 6 ...

  • Vector 6SE70 VC - page 13

    Version 1.0 March 1, 2000 Page 13 Frequency Inv erter DC-AC type DC 675V to 810V PWE A ir Cool ed PWE Water Cooled Order Number In [A ] *1 161 6SE7043-3UR60 3270.0 165 6SE7044-1UR60 4090.0 169 6SE7044-8UR60 4900.0 173 6SE7045-7UR60 5720.0 177 6SE7046-5UR60 6540.0 179 245 6SE7036-5UR60 4940.0 182 248 6SE7038-6US60 6540.0 186 251 6SE7041-1US60 6160.0 ...

  • Vector 6SE70 VC - page 14

    Page 14 Versio n 1.0 March 1, 2000 DC 890V to 930V PWE A ir Cool ed PWE Water Cooled Order Number In[A ] *1 77 6SE7031-0WG60 97.0 81 6SE7031-2WF60 118.0 89 6SE7031-5WF60 145.0 97 6SE7031-7WG60 171.0 107 6SE7032-1WG60 208.0 111 201 6SE7033-0WJ60 297.0 115 203 6SE7033-5WJ60 354.0 119 205 6SE7034-5WJ60 452.0 122 208 6SE7035-7WK60 570.0 125 211 6SE7036 ...

  • Vector 6SE70 VC - page 15

    Version 1.0 March 1, 2000 Page 15 1.2 Factory Reset P053 = 6 P060 = 2 P366 = 0 P970 = 0 6: Paramete r Changes permitte d via PMU and Seria l Interfa ce (OP1 and PC) 2: Menu Sele ct = Fix ed Settings Select Factory Setting 0: Standard Start Pa rameter Reset 0: Paramete r Reset 1: No Parameter Change ...

  • Vector 6SE70 VC - page 16

    Page 16 Versio n 1.0 March 1, 2000 ...

  • Vector 6SE70 VC - page 17

    Version 1.0 March 1, 2000 Page 17 1.3 Basic Start-up without Motor C onnected to Load 1.3.1 Volts/Hz w ithout Encoder P060 = 5 P071 = ? P095 = ? P097 = ? P101 = 460 P102 = xxx P104 = ? P105 = ? P060=5 Select “Driv e Setti ngs” P071 = Inp ut Line Voltage AC-AC Converter=460Vol t DC-AC Inverter = 620Volt P095 = Sele ct Motor Type 2: Asy nchronous ...

  • Vector 6SE70 VC - page 18

    Page 18 Versio n 1.0 March 1, 2000 P106 = ? P107 = 60 P108 = xxxx P115 = 1 P340 = 3 P383 = xxxx P452 = 100 P106 = NEMA Mo tor Nameplated efficien cy (if un known se t =0.8) P107 = Rated Motor Frequency P108 = Nameplated Rotor RPM P115 = 1 “Automatic Parameteri zation” P340 = Carrier Frequency Low # = Cooler Motor and Driv e High # = Low er Moto ...

  • Vector 6SE70 VC - page 19

    Version 1.0 March 1, 2000 Page 19 P453 = -100 P060 = 1 P128 = xxxx P462 = xxxx P464 = xxxx P443i2= 11 P453 = Max imum Reverse Speed in Percentage (usually -100%) P060 = Return to Paramete r Menu P128 = Max imum Motor Current Options: P128 = P102 P128=1.1*P102 P128=1.5*P102 P462 = Accele ration Time in second s P464 = Decele ration Time in second s ...

  • Vector 6SE70 VC - page 20

    Page 20 Versio n 1.0 March 1, 2000 Connect External Wiring as connection diagram . Step 1: Dry set of contacts be tween terminal s X101, p in#1 and pin#5 for Local/Remote Mode Selecti on. Jumper i f not required. Step 2: Dry set of contacts be tween terminal s X101, p in#1 and pin#8 for Coast to Stop Selecti on. Jumper if no t required . Step 3: Dr ...

  • Vector 6SE70 VC - page 21

    Version 1.0 March 1, 2000 Page 21 Speed value i s determined by P402. A se lection of P40 2=100% w ill be a full speed reference setpoin t. Step 6: Fault Sta tus is prov ided by a 24 Vdc signal at terminal s X101 pin#3 with r espec t to pin#2 . Leav e open if no t required . Step 7: Driv e Operating S tatus is prov ided by a 24 Vd c signal at termi ...

  • Vector 6SE70 VC - page 22

    Page 22 Versio n 1.0 March 1, 2000 1.3.2 Volts/Hz w ith Encoder Note: Com plete section 1.3.1 b efore op erating th e mot or wi th encoder fee dback. P060 = 5 P100 = 0 P130 = ? P151 = ? P060 = 1 P060=5 Select “Driv e Setti ngs” P100=0 Selects Volts/ Hz with Encode r Feedback P130 = Sele ct Type of Encoder 11: Pulse Encoder 15: Pulse Encod er w ...

  • Vector 6SE70 VC - page 23

    Version 1.0 March 1, 2000 Page 23 Additional Conn ection for +15 Vdc E ncoder. Step 10: Set Spe ed Referen ce to 20% . Step 11: Prov ide Start command. No te tha t if Signal A and Signal B are reversed, the motor w ill accele rate rapid ly. Step 12: Conne ct the motor to the load, unl ess the plan is to change to Vector Control. Standard Commission ...

  • Vector 6SE70 VC - page 24

    Page 24 Versio n 1.0 March 1, 2000 1.3.3 Vector Control without Encoder Feedback Note: Com plete section 1.3.1 ( Volts/Hz contr ol wi thout encod er feedback) . P060 = 5 P100 = 3 P060 = 1 P115 = 4 Wait P060=5 Select “Driv e Setti ngs” P100=3 Selects Vector Control without En coder Feedback P060 = Return to Paramete r Menu If you plan to use an ...

  • Vector 6SE70 VC - page 25

    Version 1.0 March 1, 2000 Page 25 P115=5 Wait P115=5 Contr oller Optimiza tion Alarm messag e “A080” w ill appear, and a start command must be issued within 20 second s to perform the test, otherwise P 115 will un set. This te st is best performed on a coupled motor u nder actual condi tions; howev er, if the load is cy clic (0-100% load variat ...

  • Vector 6SE70 VC - page 26

    Page 26 Versio n 1.0 March 1, 2000 1.3.4 Ve ctor Control with En coder Feedba ck Note: Complete section 1.3. 1 (Volts/Hz control w ithout e ncoder feedb ack), and section 1.3 .3 (Vector co ntrol w ithout enc oder fee dback) Step 10: Op erat e the unco upled motor if sectio ns 1.3.1 and 1.3. 3 are co mplete a nd veri fy operation of the m otor wi th ...

  • Vector 6SE70 VC - page 27

    Version 1.0 March 1, 2000 Page 27 Wait P115=5 Wait This test w ill adjust the following parameters P103, P120 Wait for di splay to change back to o 009. P115=5 Contr oller Optimiza tion Alarm messag e “A080” w ill appear, and a start command must be issued within 20 second s to perform the test, otherwise P 115 will un set. This test is be st p ...

  • Vector 6SE70 VC - page 28

    Page 28 Versio n 1.0 March 1, 2000 ...

  • Vector 6SE70 VC - page 29

    Version 1.0 March 1, 2000 Page 29 1.4 Drive Control Word Function Diagra m s will be refe rred to in brackets with their num ber. Please refer to function di agrams i n the co mpendiu m. Ex ample [Di agram N umber] Assign Digital Inputs Assign Off2(Coast Stop) Assign Off3(Quick Stop) Assign ON/OFF1 [180] Assign Other Functionalit y as Required See ...

  • Vector 6SE70 VC - page 30

    Page 30 Versio n 1.0 March 1, 2000 ...

  • Vector 6SE70 VC - page 31

    Version 1.0 March 1, 2000 Page 31 1.5 Communication Bo ard Co nfiguration P060 = 4 CBx Inserted? P711 = ? to P721.1…5 = ? SLB Inserted? P740 = ? P741 = ? P742 = ? P743 = 0 P745 = ? P746 = ? P749.1…8 = ? CBP Inserted? P918.1…2 = ? P060 = 1 Select “Board Config uration” Menu Parameterize CBx Boards See Function Diagram s Simolink Address 0: ...

  • Vector 6SE70 VC - page 32

    Page 32 Versio n 1.0 March 1, 2000 ...

  • Vector 6SE70 VC - page 33

    Version 1.0 March 1, 2000 Page 33 Section 2: Parameterization of a Rectifer Unit SIMOVERT MASTERDRIVES 6SE70 VC Vector Control 2.0 Power Section Defintion 2.1 Factory Reset Basic Start-up 2.2 Rectifier or Regen without auto-transformer 2.3 Regen w ith auto-transform er ...

  • Vector 6SE70 VC - page 34

    Page 34 Versio n 1.0 March 1, 2000 ...

  • Vector 6SE70 VC - page 35

    Version 1.0 March 1, 2000 Page 35 2.0 Power Section Definition Note: Pow er Section is pre -defined at the factory . Powe r Section Definition is required i f a new board CUR board is p ut into the driv e or boards are sw itched between units with different ratings. CUR cards will exist Regen Rectifiers and Larg e Common Rectifie rs. The smalle r C ...

  • Vector 6SE70 VC - page 36

    Page 36 Versio n 1.0 March 1, 2000 Unit List P070: Parameter Value (P WE) P075: Rated DC Output Curren t in Amp s In[A] Large Common Rectifier AC-DC type 3 AC 380V to 460V PWE Order Number In[A 103 6SE7038-2EH85-0AA0 821.0 105 6SE7041-0EH85-0AA0 1023.0 109 6SE7041-3EK85-0AA0 1333.0 118 6SE7041-8EK85-0AA0 1780.0 3 AC 500V to 575V 101 6SE7037-7FH85-0 ...

  • Vector 6SE70 VC - page 37

    Version 1.0 March 1, 2000 Page 37 Regenerative Rectifier AC-DC type 3 AC 380V to 460V PWE Air Cool PWE Water Cool Order Number In[A ] 14 6SE7022-1EC85-1AA0 21.0 20 6SE7024-1EC85-1AA0 41.0 31 6SE7028-6EC85-1AA0 86.0 39 6SE7031-7EE85-1AA0 173.0 42 6SE7032-2EE85-1AA0 222.0 48 6SE7033-1EE85-1AA0 310.0 51 6SE7033-8EE85-1AA0 375.0 54 6SE7034-6EE85-1AA0 4 ...

  • Vector 6SE70 VC - page 38

    Page 38 Versio n 1.0 March 1, 2000 Regenerative Rectifier AC-DC type 3 AC 660V to 690V PWE Air Cool PWE Water Cool Order Number In[A ] 36 6SE7031-4HE85-1AA0 140.0 43 6SE7032-2HE85-1AA0 222.0 47 6SE7032-7HE85-1AA0 270.0 53 6SE7034-2HE85-1AA0 420.0 56 6SE7035-3HE85-1AA0 536.0 62 6SE7037-7HH85-1AA0 774.0 68 6SE7041-0HH85-1AA0 1023.0 72 6SE7041-3HK85-1 ...

  • Vector 6SE70 VC - page 39

    Version 1.0 March 1, 2000 Page 39 2.1 Factory Reset P051 = 3 P052 = 2 P077 = 0 P052 = 0 P052 = 1 P51=3 : Ex port Mode P52=2: Function select “Ini tialization” P077=0 for standard defaul t P052=0 Return to Parameter Menu P052=1 Perform Factory Rese t ...

  • Vector 6SE70 VC - page 40

    Page 40 Versio n 1.0 March 1, 2000 ...

  • Vector 6SE70 VC - page 41

    Version 1.0 March 1, 2000 Page 41 2.2 Basic Start-up (Regenerative Rectifier without Autotransformer) P051 = 2 P053 = 6 P052 = 5 P071 = 460 P320 = 20 P773 = 1.00 P051=2 Select “Basic Mode Setting s” P053 =6 A ccess Pa rameter P052 = 5 Drive Setting s P071 = Inp ut Rectifier Voltage Generally = 460 Volt P320 = 20 Smooth Load Amps, to prevent inp ...

  • Vector 6SE70 VC - page 42

    Page 42 Versio n 1.0 March 1, 2000 P052 = 21 P052 = 0 With DC BUS connected to the COMM ON DC BU S of the sy stem, set P52=21 and prov ide a start command at terminal X101, pin #9 The circui t iden tifica tion te st will take about 10 second s. P052=0 Drive back to ready mode. Standard Commissioning for a Common Rectifier or a Regenerative Rectifie ...

  • Vector 6SE70 VC - page 43

    Version 1.0 March 1, 2000 Page 43 Connect External Wiring as connection diagram . Step 1: Dry set of contacts be tween terminal s X101, p in#6 and pin#13 for Local/Remo te Mode Sele ction. Jumper if not requ ired. Step 2: Dry set of contacts be tween terminal s X101, p in#6 and pin#10 for Coast to Stop Selection. Jumper if no t require d. Step 3: D ...

  • Vector 6SE70 VC - page 44

    Page 44 Versio n 1.0 March 1, 2000 ...

  • Vector 6SE70 VC - page 45

    Version 1.0 March 1, 2000 Page 45 2.3 Basic Start-up (Regenerative Rectifier with Autotransformer) P051 = 2 P053 = 6 P052 = 5 P071 = 460 P320 = 20 P773 = 1.00 P051=2 Select “Basic Mode Setting s” P053 =6 A ccess Pa rameter P052 = 5 Drive Setting s P071 = Inp ut Rectifier Voltage Generally = 460 Volt P320 = 20 Smooth Load Amps, to prevent inpu t ...

  • Vector 6SE70 VC - page 46

    Page 46 Versio n 1.0 March 1, 2000 P571 = 0 P318 = 95 P052 = 21 P052 = 0 P571=0 Selects Au totransformer P318 = 95% Selects percentage of nomin al DC BUS voltage. In cases w here the input line v oltage is dependable a setting o f 100% i s permissible. With DC BUS connected to the COMM ON DC BU S of the sy stem, set P52=21 and prov ide a start comm ...

  • Vector 6SE70 VC - page 47

    Version 1.0 March 1, 2000 Page 47 Section 3: Simovis Trace Setup Method SIMOVERT MASTERDRIVES 6SE70 VC Vector Control ...

  • Vector 6SE70 VC - page 48

    Page 48 Versio n 1.0 March 1, 2000 ...

  • Vector 6SE70 VC - page 49

    Version 1.0 March 1, 2000 Page 49 3.0 Simovis Trace Load Simovis from Vector Control Documentation CD Launch Simovis from Desktop Icon Add a Drive in Simovis Bus Configuration Select USS Bus Address, Drive and SW Version. N ote: Proper S imovis Ca ble must be us ed. ( RS 232 ) A B B A Option : To sp eed up your communicatio n link set th e drive P ...

  • Vector 6SE70 VC - page 50

    Page 50 Versio n 1.0 March 1, 2000 Select Tr ace from Diagnostics Menu Bar Verify Drive Connection Green Box should be li t up in the l ower left c o rner Double Click Selected Drive to start Sim ovis Window A A B B ...

  • Vector 6SE70 VC - page 51

    Version 1.0 March 1, 2000 Page 51 A D C B Select Record Se ttings in the Lower Left Corner Select Desired Channels to Record Set the Record In terval and Pre-trigger Select Trigger Channel To Trigger W ith a Binector, Select: Trigge r Channel = K431 Trigger C ondition “ =” “1 Hex” K431 is the out put of a Binect or to Connect or Converter t ...

  • Vector 6SE70 VC - page 52

    Page 52 Versio n 1.0 March 1, 2000 B A C D Select “Function Block Grafics” from the Parameter Menu Bar Select Function N umber 289 Zoom X 2 (with right Mo use click) Set Trigger B inector in U076.01 (i.e. U 076.01 = 18 Din5) Activate B lock U952.89 = 4 A C B D K431 ca n now be used to trigger th e Trace function when Bi nector (i .e. DIN 5) is ...

  • Vector 6SE70 VC - page 53

    Version 1.0 March 1, 2000 Page 53 Go to the Trace Window (Diagnost ics Menu – Trace) Verify Record Settings Start Trace Trigger Tr ace Observe S t atus Me ssage A D C B A C D B ...

  • Vector 6SE70 VC - page 54

    Page 54 Versio n 1.0 March 1, 2000 A B C Select Dat a Trace A Click Da ta Set to make it A ctive Scale Vertical Axis B Click a nd Drag scale to s hift it up and down. Y ▲ & Y ▼ to ch ange Scal e Scale Horizontal Axis C Click a nd dra g “T ” marker to sh ift Hori zon tal Sc ale . Move “[ ]” to ch ange sc ale N ote: Background can be ...

  • Vector 6SE70 VC - page 55

    Version 1.0 March 1, 2000 Page 55 Section 4: When to Re-Tune the Drive SIMOVERT MASTERDRIVES 6SE70 VC Vector Control ...

  • Vector 6SE70 VC - page 56

    Page 56 Versio n 1.0 March 1, 2000 ...

  • Vector 6SE70 VC - page 57

    Version 1.0 March 1, 2000 Page 57 4.0 Conditions that would merit re-tuning the d rive Hardware addition s made to the drive, su ch as an output rea c tor or a dv/dt fil t er. Physical change s to the process, such as the motor b eing changed (even if the it is an identi cal motor, b earing changes a nd coupling changes can have an influ ence on pe ...

Manufacturer Vector Category Computer Drive

Documents that we receive from a manufacturer of a Vector 6SE70 VC can be divided into several groups. They are, among others:
- Vector technical drawings
- 6SE70 VC manuals
- Vector product data sheets
- information booklets
- or energy labels Vector 6SE70 VC
All of them are important, but the most important information from the point of view of use of the device are in the user manual Vector 6SE70 VC.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Vector 6SE70 VC, service manual, brief instructions and user manuals Vector 6SE70 VC. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Vector 6SE70 VC.

Similar manuals

A complete manual for the device Vector 6SE70 VC, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Vector 6SE70 VC by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Vector 6SE70 VC.

A complete Vector manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Vector 6SE70 VC - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Vector 6SE70 VC, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Vector 6SE70 VC, that we can find in the current document
3. Tips how to use the basic functions of the device Vector 6SE70 VC - which should help us in our first steps of using Vector 6SE70 VC
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Vector 6SE70 VC
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Vector 6SE70 VC in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Vector 6SE70 VC?

Use the form below

If you did not solve your problem by using a manual Vector 6SE70 VC, ask a question using the form below. If a user had a similar problem with Vector 6SE70 VC it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)