Инструкция обслуживания GE Monogram GFK-1115

175 страниц 1.5 mb
Скачать

Перейти на страницу of 175

Summary
  • GE Monogram GFK-1115 - page 1

    GE Fanuc Automation Progr ammable Contr o l Pr oducts PA NELWA RE™ MMI A pplication Manual for GE Fanuc Genius™ Pr otocol User' s Manual GFK - 1115 June 1995 ...

  • GE Monogram GFK-1115 - page 2

    GFL-002 Warnings, Cautions, and Notes as Used in this Publication Warning Warning notices are used in this publication to emphasize that hazardous voltages, currents, temperatures, or other conditions that could cause personal injury exist in this equipment or may be associated with its use. In situations where inattention could cause either person ...

  • GE Monogram GFK-1115 - page 3

    Preface GFK- 1115 iii This manual provides a quick guide to installing and operating PANELWARE ™ Panels, describes configuration techniques, and outlines general use of the PANELWARE Configuration Software (PCS) with GE Fanuc Genius Protocol. Some of the products mentioned or illustrated in this manual may not be released when this document is pu ...

  • GE Monogram GFK-1115 - page 4

    Preface iv PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GF K-1115 Related Publications PANELWARE Manuals GFK-0848 PANELWARE ™ Hardware Installation User's Manual Describes the PANELWARE Operator Panels and contains technical data, hardware installation instructions, and the general information required for puttin ...

  • GE Monogram GFK-1115 - page 5

    Preface GFK- 1115 Preface v GFK-0852 Series 90 ™ PLC Serial Communications User's Manual This manual describes serial communications products for the Series 90 Programmable Logic Controller. Information is provided to implement a serial communications link between the Series 90 PLC, a host computer, peripheral device, or another PLC. GFK-089 ...

  • GE Monogram GFK-1115 - page 6

    Contents GFK- 1115 vii Chapter 1 Overview ................................................................................................ ............... 1-1 PANELWARE Configuration Software .............................................................................. 1- 2 Hardware and Software Requirements ....................................... ...

  • GE Monogram GFK-1115 - page 7

    Contents viii PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GF K-1115 Section 5 Creating a New Project ................................................................ .......3-10 Section 6 Defining Connections ................................ ..........................................3-13 Connection to a GE Fanuc PLC vi ...

  • GE Monogram GFK-1115 - page 8

    Contents GFK- 1115 Table of Contents ix Elements of the Connection List ......................................................................................... 5-3 Using Function Keys in the Connection List ........................................................................ 5-3 Overview ....................................................... ...

  • GE Monogram GFK-1115 - page 9

    Contents x PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GF K-1115 Creating a Project ............................................................................................................ 6-16 Preparing a Concept ................................................................ ................................... 6 ...

  • GE Monogram GFK-1115 - page 10

    GFK- 1115 1 - 1 Chapter Overview This chapter provides a short overview/description of the PANELWARE Configuration Software (PCS) and outlines the requirements for PCS operation with the PC and PLC. It includes the following information: ■ PANELWARE Configuration Software (PCS) ............................................................1- 2 ■ ...

  • GE Monogram GFK-1115 - page 11

    1 - 2 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 1 PANELWARE Configuration Software PANELWARE Configuration Software allows complex projects to be created, using easy-to- follow, menu-controlled instructions. These projects are actually programs that are transferred to a Panel and started there via a Panel p ...

  • GE Monogram GFK-1115 - page 12

    GFK- 1115 Chapter 1 Overview 1 - 3 1 Hardware and Software Requirements PCS is delivered on two 3½-inch disks in 2DD (720K) format and on one 5¼-inch disk in 2S/HD (1.2M) format. The diskette(s) you use to install the PCS depends on your PC configuration. Description Catalog Number PANELWARE Configuration Software (includes cable assembly) IC641S ...

  • GE Monogram GFK-1115 - page 13

    1 - 4 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 1 PLC Requirements To communicate with the C400 Genius Panel Controller, the PLC must meet the following requirements: ■ Series 90-70 PLC ❏ Genius Bus Controller (GBC), IC697BEM731 ■ Series 90-30 PLC ❏ Genius Communications Module (GCM), IC693CMM301 ? ...

  • GE Monogram GFK-1115 - page 14

    GFK- 1115 Chapter 1 Overview 1 - 5 1 Document Conventions Key Symbols All keys used to operate PCS are shown in bold in this manual: Table 1 - 2. Key Symbols Key German English Description ↑ ↑↑ ↑ Cursor up ↓ ↓↓ ↓ Cursor down ← ←← ← Cursor left → →→ → Cursor right ↵ ↵↵ ↵ Enter (Return) Bild ↑ ↑ PgUp Cursor ...

  • GE Monogram GFK-1115 - page 15

    GFK- 1115 2 - 1 Chapter C400 Panel Controller Hardware This chapter describes the C400 PANELWARE Panel Controller (IC750CTR400), its connections (interfaces) and all operational elements for which hardware must be configured on the modular Panel. The following sections of information are included: ■ General Information ........................... ...

  • GE Monogram GFK-1115 - page 16

    2 - 2 PANELWARE MMI Application Manual for Genius Protocol - June 1995 GF K-1115 2 General Information Power Requirement 24 VDC power must be supplied to the PANELWARE Controller unit. The Controller, in turn, supplies the Keyblock and Display modules with power. When estimating the total 24 VDC power consumption for a system, add up the 24 VDC pow ...

  • GE Monogram GFK-1115 - page 17

    GFK- 1115 Chapter 2 C400 Panel Controller Hardware 2 - 3 2 Genius Panel Controller (C400) Specifications a45517 2.165" (55mm) 7.165" (182mm) 7.165" (182mm) GENIUS SHLD OUT SHLD IN X2 X1 Figure 2 - 1. Genius Panel Controller (C400) Table 2 - 1. Specifications for Genius Panel Controller (C400) Technical Data Interfaces IF0: RS-232 (no ...

  • GE Monogram GFK-1115 - page 18

    2 - 4 PANELWARE MMI Application Manual for Genius Protocol - June 1995 GF K-1115 2 Table 2 - 1. - Continued Shock conforms to IEC 68-2-27 15g equivalent, 150 m/sec 2 , 11 msec, 3 axes (positive and negative) Vibration conforms to IEC 68-2-6 1g equivalent, 10-58 Hz; 0.075 mm 58-150 Hz; 9.8m/sec 2 20 cycles per axis Processor Motorola 68302 @ 16 MHz ...

  • GE Monogram GFK-1115 - page 19

    GFK- 1115 Chapter 2 C400 Panel Controller Hardware 2 - 5 2 Overview of Connections and Operational Elements a45516 1 3 8 2 5 6 9 7 4 Figure 2 - 2. Genius Panel Controller (C400) Elements/Connections 1 . Display Module Connector (ribbon cable) 2 . 24 VDC Power Supply Connector 3 . IF0: RS-232 (to PC), labeled 0 4 . Genius Bus Connector 5 . Keyblock ...

  • GE Monogram GFK-1115 - page 20

    2 - 6 PANELWARE MMI Application Manual for Genius Protocol - June 1995 GF K-1115 2 24 VDC Power Supply (item 2, Figure 2-2) Pin Description + +24 V - 0 V Ground Ground The pins are to be connected using as short a cable as is possible. If the Panel is mounted in a cabinet, the connecting cable should be as short as possible. IF0 - RS-232, Non-isola ...

  • GE Monogram GFK-1115 - page 21

    GFK- 1115 Chapter 2 C400 Panel Controller Hardware 2 - 7 2 Genius Bus Connector, Isolated (item 4, Figure 2-2) GE NIUS a45318 SHLD OUT SHLD IN X2 X1 Pin Description SHLD OUT Shield Out (to next physical device on bus) SHLD IN Shield In (from previous physical device on bus) X2 Serial 2 X1 Serial 1 Mode Switch (item 6, Figure 2-2) The mode of operat ...

  • GE Monogram GFK-1115 - page 22

    2 - 8 PANELWARE MMI Application Manual for Genius Protocol - June 1995 GF K-1115 2 Reset Button (item 9, Figure 2-2) A hardware reset can be executed by pressing this button. Depending on the setting of the mode selection switch, different functions can be executed. These functions are explained in the descriptions of the connections and operationa ...

  • GE Monogram GFK-1115 - page 23

    GFK- 1115 Chapter 2 C400 Panel Controller Hardware 2 - 9 2 Operating the C400 Controller FlashPROM The Panel Controller has non-volatile memory called FlashPROM, which is split into two separate areas (banks) as follows: System Bank contains the operating system, which is necessary for the Panel program created by the user to be processed. The syst ...

  • GE Monogram GFK-1115 - page 24

    2 - 10 PANELWARE MMI Application Manual for Genius Protocol - June 1995 GF K-1115 2 Loading and Starting Panel Programs A Panel program is created using PCS and then transferred (loaded) to the Panel through the serial interface when Teach Mode is selected. To start an application, RUN Mode must be selected. The following sections outline how to lo ...

  • GE Monogram GFK-1115 - page 25

    GFK- 1115 3 - 1 Chapter Quick Start This chapter provides a quick guide to installing and using PCS and, using step-by-step instructions, explains how to create a project. It includes the following information: ■ Software Installation ........................ 3-2 ❏ Calling the Setup Program........ 3-2 ❏ Language Selection ................... ...

  • GE Monogram GFK-1115 - page 26

    3 - 2 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Section 1 Software Installation The Genius protocol driver is copied to your computer as part of the standard PCS installation (PCS version 1.8 or later). The PCS should be installed according to the instructions in the following sections. Calling the Setup ...

  • GE Monogram GFK-1115 - page 27

    GFK- 1115 Chapter 3 Quick Start 3 - 3 3 Installation Menu All system information that the software requires is entered or displayed in the Install Program menu. Computer type, DOS version, source path and memory size are entered automatically. You must enter the desired destination path. From the Install Program menu, you can change destination pat ...

  • GE Monogram GFK-1115 - page 28

    3 - 4 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Screen Configuration The Screen Configuration menu is displayed once the CONFIG.SYS file changes are made. This screen allows you to set up the appropriate PCS screen type by pressing the function key that corresponds to your computer's display. When yo ...

  • GE Monogram GFK-1115 - page 29

    GFK- 1115 Chapter 3 Quick Start 3 - 5 3 Section 2 Starting PCS To start PCS, type the following command at the C: prompt, then press ↵ ↵ (if you installed the software on a drive other than C, substitute the correct drive ID for C:): C:> panel The PCS is called up and the following copyright information is displayed on the screen: After a d ...

  • GE Monogram GFK-1115 - page 30

    3 - 6 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Section 3 General Operation Pull-Down Menus (Main Menu) The pull-down menus of the Main menu can be opened at any time using two different methods: ■ By pressing the alternate ( Alt ) key simultaneously with the desired function key ( F1 to F5 ) ■ By pre ...

  • GE Monogram GFK-1115 - page 31

    GFK- 1115 Chapter 3 Quick Start 3 - 7 3 Selection Windows If the ↵ ↵ character is displayed in the bottom line of a screen, a selection window can be opened by pressing the enter ( ↵ ↵ ) key. A selection can be made from these windows by moving through the list using the cursor keys until the desired entry is highlighted, then pressing ↵ ...

  • GE Monogram GFK-1115 - page 32

    3 - 8 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Screen Elements The PCS display contains a few basic elements that are displayed at all times: Figure 3 - 1. Basic PCS Screen Elements ■ In the top line (title line) of the screen, the software version number is displayed at the left, the name of the curre ...

  • GE Monogram GFK-1115 - page 33

    GFK- 1115 Chapter 3 Quick Start 3 - 9 3 Section 4 PCS Configuration Before you can begin creating projects using the PCS, the appropriate interface to be used to connect your PC to the PANELWARE controller must be defined. The F4 Config. pull-down menu shown below can be opened by pressing Alt + F4 or Alt + C : To set up the interface, select the C ...

  • GE Monogram GFK-1115 - page 34

    3 - 10 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Section 5 Creating a New Project Throughout the remainder of this chapter, you will create an example project (named QUICKST ) by following the steps that are outlined in the text. This sample project is designed to provide an overview of how the PCS works. ...

  • GE Monogram GFK-1115 - page 35

    GFK- 1115 Chapter 3 Quick Start 3 - 11 3 Press ↵ ↵ again to open a selection window that contains a list of the available Controllers. Note The available Controllers are listed in the form <type>.#<OS version>, where <type> is the basic controller model (e.g., C400) and <OS version> is the operating system version number ...

  • GE Monogram GFK-1115 - page 36

    3 - 12 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Select the Display Type entry and press ↵ ↵ to display a window that lists all display types. Select one of the display types (in the example, LCD 4x20) and press ↵ ↵ . The cursor jumps to the next line, Number of Keyblock Modules . Enter a number ( ...

  • GE Monogram GFK-1115 - page 37

    GFK- 1115 Chapter 3 Quick Start 3 - 13 3 The new project definition can be saved and closed by pressing the F4 Accept function key. While the system is saving the project, the following screen is displayed: After the project is saved, the New Project window is closed and the project name (QUICKST) is displayed in the title line. ...

  • GE Monogram GFK-1115 - page 38

    3 - 14 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Section 6 Defining Connections The next step after creating a new project is to define the connections. All PLCs and other devices that are to communicate with the Panel must be entered in the connection editor. To change or insert connections, select the C ...

  • GE Monogram GFK-1115 - page 39

    GFK- 1115 Chapter 3 Quick Start 3 - 15 3 Connection to a GE Fanuc PLC via Genius Press F1 Edit to edit the connection DD Genius : Move the cursor to the PLC Type line using the → → or ↵ ↵ key: The PLC type to communicate with can be chosen from this selection window. For this example, use the cursor keys to highlight the entry GBC Series 90 ...

  • GE Monogram GFK-1115 - page 40

    3 - 16 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 The Connection Definition window containing the new connection is displayed. By pressing F4 Accept , the change is confirmed and shown in the Connection List window: To configure the Genius bus aspects of the connection, press the F4 PLC Node Parameters Key ...

  • GE Monogram GFK-1115 - page 41

    GFK- 1115 Chapter 3 Quick Start 3 - 17 3 Here, the Target device number , or Genius bus address, of the connection is specified. Enter the bus address of your GBC (typically bus address 31) in the Target device number field. No other data needs to be entered into the PLC Node Parameter Definition screen for this example. Pressing F4 Accept complete ...

  • GE Monogram GFK-1115 - page 42

    3 - 18 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Internal Connection Now insert an internal connection into the connection list. This is done by first pressing the F2 Ins key and then specifying the ID DI in the window that appears. Choose Internal as the connection. Press F4 to confirm this definition an ...

  • GE Monogram GFK-1115 - page 43

    GFK- 1115 Chapter 3 Quick Start 3 - 19 3 Genius Internal Connection As a final connection, insert a Genius internal connection into the connection list. this is done by first pressing the F2 Ins key and then specifying the ID GI in the window that appears. Choose Genius as the Connection and Genius Internal as the PLC Type . This definition is now ...

  • GE Monogram GFK-1115 - page 44

    3 - 20 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Section 7 Key Assignments Every key on every Keyblock module can be defined according to the project's unique needs. You can also assign keys for numbers, letters, and the Next and Previous functions. In order to assign functions to the keys, the Edit ...

  • GE Monogram GFK-1115 - page 45

    GFK- 1115 Chapter 3 Quick Start 3 - 21 3 The abbreviations on the Keyblock module keys have the following meanings: Table 3 - 2. Keyblock Abbreviation Definitions Abbr. Description F1 ... F4 Function keys 1 through 4 (used for commands and picture changes) +p+ Moves cursor to the previous INPUT field +n+ Moves cursor to the next INPUT field +P + Ch ...

  • GE Monogram GFK-1115 - page 46

    3 - 22 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Section 8 Creating Pictures Pictures make up the basic elements of every Panel project. They include static elements such as text and lines 1 , and/or dynamic elements like input and output fields. Output fields allow information, such as temperature, RPM, ...

  • GE Monogram GFK-1115 - page 47

    GFK- 1115 Chapter 3 Quick Start 3 - 23 3 The blank Edit Picture window shown below is displayed: The size of the dark rectangle (picture) at the bottom of the screen corresponds to the selected display type (display type LCD 4x20 is shown above, i.e., the rectangle consists of 4 lines and 20 characters per line). Text or fields can now be entered i ...

  • GE Monogram GFK-1115 - page 48

    3 - 24 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Press the F2 Field function key to open the Field Class selection window. Select the Output Field entry from the list and press ↵ ↵ to access the Select Field Type window. Several output field types can be chosen from this widow: For this example, selec ...

  • GE Monogram GFK-1115 - page 49

    GFK- 1115 Chapter 3 Quick Start 3 - 25 3 Move the cursor to the Input: text line and press the F2 Field function key. Select the Input field option from the Field Class window that is displayed: The Select Field Type window containing all of the input field types is displayed. For this example, select the Input Word (signed) field type: In the Inpu ...

  • GE Monogram GFK-1115 - page 50

    3 - 26 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Press the F10 Exit function key to end this picture editing session. Because this is a new picture, a window will open to confirm whether or not the picture should be saved: Type Y to request that the picture be saved, and a prompt will request you to enter ...

  • GE Monogram GFK-1115 - page 51

    GFK- 1115 Chapter 3 Quick Start 3 - 27 3 From the Select field type window that is displayed, select the Output Date/Time option: The output format for the date and time is selected from the following window that is displayed: Do not make any changes in this window and press the F4 Accept function key. The Date/Time field will be displayed in the s ...

  • GE Monogram GFK-1115 - page 52

    3 - 28 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Press the F4 Accept key to close the field and confirm it as part of the picture. The field should be displayed within the picture as shown below: Press the F10 Exit function key to end this picture editing session. Because this is a new picture, a window w ...

  • GE Monogram GFK-1115 - page 53

    GFK- 1115 Chapter 3 Quick Start 3 - 29 3 Section 9 Defining the Project Variables All variables used in the project (symbolic variable names) must be connected to specific addresses in the PLC CPU. In order to define these connections, access the connection list by selecting the Connection option from the F2 Edit pull-down menu or by pressing Ctrl ...

  • GE Monogram GFK-1115 - page 54

    3 - 30 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Genius Device Connection Use the cursor keys to highlight connection DD Genius , and then press the F5 VAT function key to display the associated variable assignment table (VAT) on the screen. All variables that have been used in a picture's input or o ...

  • GE Monogram GFK-1115 - page 55

    GFK- 1115 Chapter 3 Quick Start 3 - 31 3 The definition that is entered can be saved by pressing the F4 Accept function key. Once saved, the newly selected variable is shown in the VAT. Pressing the F10 Exit function key causes the connection list to appear on the screen again. Genius Internal Connection Select the GE Genius Internal connection fro ...

  • GE Monogram GFK-1115 - page 56

    3 - 32 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Internal Connection Select the DI Internal connection from the connection list and press F5 or ↵ ↵ to view its VAT: This is the variable that will be output in the error picture. The internal variables cannot be edited. You can close the VAT by pressing ...

  • GE Monogram GFK-1115 - page 57

    GFK- 1115 Chapter 3 Quick Start 3 - 33 3 Section 10 Binding Pictures in the Project The pictures that you have created for this project still have to be bound into the project definition. To begin the binding process, select the Project option from the F2 Edit pull-down menu or press Ctrl + P . The Edit Project window shown below is opened: The pic ...

  • GE Monogram GFK-1115 - page 58

    3 - 34 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Picture for a Communications Error From the Edit Project window, press the F 1 Project Def. function key to move the cursor to the Picture for Communications Error line in the window. The function line options are changed as shown below: The file name of th ...

  • GE Monogram GFK-1115 - page 59

    GFK- 1115 Chapter 3 Quick Start 3 - 35 3 Picture Binding Overview Binding a picture into the project means that all possible branches (picture changes) that the picture can have are defined. A picture change can be made using the Next , Previous or optional function keys 2 . When you press the F2 Bind Picture function key from the Edit Project wind ...

  • GE Monogram GFK-1115 - page 60

    3 - 36 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Error Picture Bind the ERROR picture into the example project as follows: Caution You should not branch from the ERROR picture to a picture that has fields displaying data from the PLC in it because the fields will not be updated or processed if a communica ...

  • GE Monogram GFK-1115 - page 61

    GFK- 1115 Chapter 3 Quick Start 3 - 37 3 Start-up Picture Bind the START-UP picture into the example project as follows: If the START-UP picture is bound into the project as shown, the user will be able to switch to the PICT_1 picture by pressing the Next key on the Panel. The Previous key performs a refresh of the screen for the START-UP picture. ...

  • GE Monogram GFK-1115 - page 62

    3 - 38 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Pict_1 Bind the PICT_1 picture into the example project as follows: If the PICT_1 picture is bound into the project as shown, the operator will be able to switch back to the START-UP picture using the Previous key on the Panel. Pressing the Next key causes ...

  • GE Monogram GFK-1115 - page 63

    GFK- 1115 Chapter 3 Quick Start 3 - 39 3 Picture List Organization When you press the F3 Picture List function key from the Edit Project window, a list of all of the pictures that are bound to the project is displayed: The picture defined as the ERROR picture is not allowed to be placed in the top position in the picture list; the picture in the to ...

  • GE Monogram GFK-1115 - page 64

    3 - 40 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Section 11 Compiling the Project In order to create, transfer and run your project on the Panel, it must be compiled (translated). To compile the example project, select the Compile option from the F3 Utilities pull-down menu or press Ctrl + Q : The compila ...

  • GE Monogram GFK-1115 - page 65

    GFK- 1115 Chapter 3 Quick Start 3 - 41 3 Section 12 Downloading the Project to the Panel In order to download a compiled project to the Panel, the Panel must first be connected to the PC. The connection and the cable that should be used are described in Appendix A of the PANELWARE™ Hardware Installation User's Manual (GFK-0848). Caution Ensu ...

  • GE Monogram GFK-1115 - page 66

    3 - 42 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Once these steps have been performed, the download process can be started by selecting the Download option from the F3 Utilities pull-down menu or by pressing Ctrl + X : The Download Project title and the number of the channel ( Channel #2 ) are centered in ...

  • GE Monogram GFK-1115 - page 67

    GFK- 1115 Chapter 3 Quick Start 3 - 43 3 Section 13 Connecting the PLC and the Panel In order for communication to take place between the Panel and the PLC, the following connection must be made: Figure 3 - 3. PLC/Panel Connection ...

  • GE Monogram GFK-1115 - page 68

    3 - 44 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 3 Section 14 Starting the Project If the project has been downloaded completely, the application can be started after the following steps are completed: 1. Set the operating mode to Run-Mode (operating mode switch to position 5). 2. Connect the PLC and the Pa ...

  • GE Monogram GFK-1115 - page 69

    GFK- 1115 Chapter 3 Quick Start 3 - 45 3 Section 15 Exiting PCS If the Main menu is active, the PCS program can be ended by pressing the F10 Exit function key or by selecting the Exit option from the F1 File pull-down menu. This causes the following message to appear on the screen. If you enter Y , the PCS program is exited. If you enter N , the PC ...

  • GE Monogram GFK-1115 - page 70

    GFK- 1115 4 - 1 Chapter Configuring Communication with the PLC This chapter provides information on how to configure the interfaces of the Panel Controller and the PLC to make the connection between them. The following information is included: ■ Genius Protocol Parameters (Definition in PCS) ....................................................... ...

  • GE Monogram GFK-1115 - page 71

    4 - 2 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 4 Genius Protocol Parameters (Definition in PCS) The parameter definitions for the Genius bus network, and the devices being communicated with on it, are entered in the connection editor of the PCS as follows: Access the connection list by pressing Ctrl + C or ...

  • GE Monogram GFK-1115 - page 72

    GFK- 1115 Chapter 4 Configuring Communication with the PLC 4 - 3 4 PLC Types Every Genius connection must be configured to specify a PLC Type . Except for the case of the PCS-created DD GENIUS default connection, this PLC type must be provided when inserting a new connection. For the DD GENIUS default connection, the PLC type must be provided befor ...

  • GE Monogram GFK-1115 - page 73

    4 - 4 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 Table 4 - 1. Summary of PLC Data Types PLC Type Interface Memory Types Supported GBC Series 90-70 Series 90-70 Genius Bus Controller (GBC), IC697BEM731 %R, %AI, %AQ, %P, <block> %L, %I, %Q, %T, %M, %S, %SA, %SB, %SC, %G, %GA, %GB, %GC, %GD, %GE, %GI * , ...

  • GE Monogram GFK-1115 - page 74

    GFK- 1115 Chapter 4 Configuring Communication with the PLC 4 - 5 4 PLC Node Parameter Definitions Additional information must be supplied for every defined connection except for an Internal or GENIUS Internal connection. Use the cursor keys to highlight the desired connection, then press the F4 PLC Node Parameters key to access the PLC Node Paramet ...

  • GE Monogram GFK-1115 - page 75

    4 - 6 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 4 ❏ Write priority Data can be written to another device on the Genius bus in one of two ways: via global data, or via datagrams. Only the %GQ and %GAQ data types are handled by global data writes; all other memory types are handled by datagrams. Datagrams c ...

  • GE Monogram GFK-1115 - page 76

    GFK- 1115 Chapter 4 Configuring Communication with the PLC 4 - 7 4 PLC Network Parameter Definitions In addition to the unique information that must be supplied for each defined connection, information must be provided concerning the Genius bus itself. From any PLC Node Parameter Definition window, you can access the PLC Network Parameter Definitio ...

  • GE Monogram GFK-1115 - page 77

    4 - 8 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 4 ❏ Command timer (10 ms) Specifies the time, in increments of 10 ms, allotted for the C400 Controller to execute each command on the Genius bus. The default is 1 second (100 x 10 ms). Note that this timer controls only the execution of the command; it does ...

  • GE Monogram GFK-1115 - page 78

    GFK- 1115 Chapter 4 Configuring Communication with the PLC 4 - 9 4 ❏ Global data starting reference* This parameter must be set only if you will be communicating with a Series Six or Series Five PLC. It specifies the offset within the Series Six/Five register memory where global data broadcast by the C400 Controller is to be placed. Note that thi ...

  • GE Monogram GFK-1115 - page 79

    4 - 10 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 4 Settings on the Panel A Panel with a C400 Panel Controller can read from and write to a PLC, either through a Genius interface or an RS-232 interface. In order to make this possible, the following must take place: 1 . A project compiled with PCS is download ...

  • GE Monogram GFK-1115 - page 80

    GFK- 1115 Chapter 4 Configuring Communication with the PLC 4 - 11 4 Table 4 - 2. Panel to PLC Interface Connections for Genius Protocol Module Interface Series 90-30 Genius bus interface module, found on one of the following backplanes: 5-slot backplane with built-in CPU (Model 311) 10-slot backplane with built-in CPU (Model 321) 5-slot backplane w ...

  • GE Monogram GFK-1115 - page 81

    GFK- 1115 5 - 1 Chapter PCS Connection Editor This chapter provides a description of the PCS Connection Editor. It includes the following information: ■ General Information ...................................................................................................5-2 ■ Accessing the Connection List ...................................... ...

  • GE Monogram GFK-1115 - page 82

    5 - 2 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 5 General Information All of the variables (symbolic variable names) that are to be used in a project must be assigned an address in the PLC CPU. Every PLC connected to the Panel must be entered in the project's connection list. Each of these entries acce ...

  • GE Monogram GFK-1115 - page 83

    GFK- 1115 Chapter 5 PCS Connection Editor 5 - 3 5 Elements of the Connection List A single entry in the connection list consists of the following three segments: ■ ID: Identification for a connection (PLC station). The assignment of variables to certain connections is accomplished through the ID. If input or output fields are defined as part of a ...

  • GE Monogram GFK-1115 - page 84

    5 - 4 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 5 Editing/Inserting Connections Pressing F1 Edit or F2 Ins in the Connection List window opens the Connection Definition window, in which a connection can be entered or modified: F4 Accept ............. Sav e s an d then closes the connection definition. F10 E ...

  • GE Monogram GFK-1115 - page 85

    GFK- 1115 Chapter 5 PCS Connection Editor 5 - 5 5 With the cursor in the PLC Type line, press ↵ ↵ to display a selection window that lists PLCs. After selecting a PLC Type, press F4 to accept the new connection and return to the Connection List window. Deleting Connections Connections can be deleted from the connection list by highlighting the ...

  • GE Monogram GFK-1115 - page 86

    5 - 6 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 5 Editing the Variable Assignment Table The VAT is used to assign absolute PLC addresses to symbolic variables. All connection variables that are entered as PLC addresses during the project creation are listed in the Variable Assignment Table. When you press t ...

  • GE Monogram GFK-1115 - page 87

    GFK- 1115 Chapter 5 PCS Connection Editor 5 - 7 5 ■ PLC Address: The PLC address can only be defined for Genius and SNP90 connections. You must enter the PLC address using the syntax and format that the connected PLC will understand. For a series 90-30 or 90-70 PLC, an address is constructed as shown below: Example: %Yxxxxx % Y xxxxx Offset The a ...

  • GE Monogram GFK-1115 - page 88

    5 - 8 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 5 Editing/Inserting Variable Assignments Pressing the F1 Edit or F2 Ins key from the VAT window opens the VAT Definition window, which allows a variable assignment to be entered or modified: Note Only the Tagname and PLC Address fields may be defined prior to ...

  • GE Monogram GFK-1115 - page 89

    GFK- 1115 Chapter 5 PCS Connection Editor 5 - 9 5 Entering/Changing PLC Variable Types If the cursor is in the PLC Variable Type line, a selection window can be opened by pressing the ↵ ↵ (Enter) key. This window lists the data types that are permitted for this PLC address. Table 5-1 provides a list of the data types allowed for PLC addresses, ...

  • GE Monogram GFK-1115 - page 90

    5 - 10 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 5 Table 5 - 2. Address Code Groups Series 90-30/Series 90-70 Group 1 Address codes %R, %AI, %AQ, %P, %L, %GAI, %GAQ Group 2 Address codes %I, %Q, %T, %M, %G, %GA, %GB, %GC, %GD, %GE, %S, %SA, %SB, %SC, %GI, %GQ Series 5 Group 1 Address codes %R, %GAI, %GAQ Gr ...

  • GE Monogram GFK-1115 - page 91

    GFK- 1115 Chapter 5 PCS Connection Editor 5 - 11 5 Global Data Format Global Data is used to automatically broadcast up to 128 bytes of data from one host to all others on the Genius bus. Typically, this data is a collection of both discrete and analog values. To facilitate transmitting/receiving global data as either discrete or analog values, a d ...

  • GE Monogram GFK-1115 - page 92

    5 - 12 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 5 Data Type Conversions The following basic Panel and PLC data types are supported: Table 5 - 3. Variable Data Types Format in the PCS Panel Data Type PLC Data Type Value Range Bit B I T 0 ... 1 Byte unsigned (does not exist) 0 ... + 255 Word unsigned WORD 0 ...

  • GE Monogram GFK-1115 - page 93

    GFK- 1115 Chapter 5 PCS Connection Editor 5 - 13 5 Table 5 - 4. Data Type Conversions (Panel Data Type/PLC) Legend: Byte u. .................. Byte unsigned Word u. ................ Word unsigned Word s. ................. Word signed Long u. ................. Long unsigned LSB ...................... Least Significant Bit (Lower Bit) MSB ........... ...

  • GE Monogram GFK-1115 - page 94

    5 - 14 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 5 Table 5 - 4. - Continued Word s. → Negative values are limited to 0. → WORD * ← Values higher than 32767 are limited to 32767. ← Word s. → No conversion. → INT * ← No conversion. ← Word s. → Word s. is copied to the lower word. For a negat ...

  • GE Monogram GFK-1115 - page 95

    GFK- 1115 Chapter 5 PCS Connection Editor 5 - 15 5 Tables 5-5 and 5-6 provides another overview of the permitted combinations of Panel and PLC data types. In addition, the address codes and possible limitations on the offset are listed for the PLC data types. Note The statement (offset - 1)%8 calculates the modulo (remainder) of the division from ( ...

  • GE Monogram GFK-1115 - page 96

    5 - 16 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 5 Table 5 - 6. Possible Data Type Conversions for Series Five/Series Six Panel Data PLC Data Types Types BIT WORD INT DWORD DINT FLOAT STRING Bit I, I1+,I2+, I1-, O, O1+, O2+, O1-, O2-, GI, GQ I, O, GI, GQ (offset-1)%8=0 R, GAI, GAQ (offset-1)%8=0 Byte u. I, ...

  • GE Monogram GFK-1115 - page 97

    GFK- 1115 6 - 1 Chapter Demo Project ■ General Information ........................ 6-2 ■ Required Hardware .......................... 6-3 ■ Downloading the Demo Project ....... 6-4 ❏ Defining the User Path ............. 6-4 ❏ Loading the Project ................... 6- 5 ❏ Do w nlo ading/Startin g the P roj ec t . . . 6 - 6 ■ Descript ...

  • GE Monogram GFK-1115 - page 98

    6 - 2 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 Section 1 General Information A demo project, which is copied to the hard disk during the installation, is delivered in the same package as PCS. Project DEMO_400 is for use with a C400 Controller. The demo provides an overview of PANELWARE features. Even if ...

  • GE Monogram GFK-1115 - page 99

    GFK- 1115 Chapter 6 Demo Project 6 - 3 6 Section 2 Required Hardware The following PANELWARE hardware components are required for the demo project (see the PANELWARE™ Hardware Installation User’s Manual –GFK-0848): ❏ 1 - C400 Panel Controller ❏ 1 - 8 x 40 LCD Display Module ❏ 1 - 12+4 key Keyblock Module ❏ 1 - 16 key Keyblock Module ? ...

  • GE Monogram GFK-1115 - page 100

    6 - 4 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 Section 3 Downloading the Demo Project Defining the User Path In order to load the demo project into PCS, make sure that the user path is set to Dest.pathUSER . To define the user path, open the pull-down menu, F4 Config , and select the function User Path ...

  • GE Monogram GFK-1115 - page 101

    GFK- 1115 Chapter 6 Demo Project 6 - 5 6 Loading the Project To load the DEMO project, select the Open Project option from the F1 File pull-down menu and press the ↵ ↵ (Enter) key to access the selection window containing the list of current projects. Highlight the desired DEMO project and press ↵ ↵ to select/open it. The cursor can be move ...

  • GE Monogram GFK-1115 - page 102

    6 - 6 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 Downloading and Starting the Project Download the project to the Panel by following these steps: ■ Panel: ❏ Supply the Panel with power by connecting the 24 VDC power. ❏ Select Teach Mode (operating mode switch in position 7). ❏ Press the RESET butto ...

  • GE Monogram GFK-1115 - page 103

    GFK- 1115 Chapter 6 Demo Project 6 - 7 6 Section 4 Description of the Demo Project General Information The following symbols and representations will be used in the project description: Keys: F1 ... F4 Function 1 to 4 (Function depends on the current picture) +p+ / +n+ Cursor to previous/next input field +P+ / +N+ Change to previous/next picture +G ...

  • GE Monogram GFK-1115 - page 104

    6 - 8 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 Main Menu If the demo project has been successfully downloaded to the Panel and if you have started the Panel in Run-Mode , the main menu appears (This is the same as the Startup Picture): The date and time are displayed in the top right- hand corner of the ...

  • GE Monogram GFK-1115 - page 105

    GFK- 1115 Chapter 6 Demo Project 6 - 9 6 Value Entries INPUT VALUES Picture If you have pressed the F1 key in the main menu, the following picture appears on the screen: Key LEDs: 9 8 7 4 5 1 6 2 0 3 EC F1 F2 F3 +P+ +p+ F4 +N+ +n+ +G+ . F5 F6 F7 F8 By pressing key F1 / F2 , the content of PLC address %R0001 is increased/decreased in steps: F1 Incre ...

  • GE Monogram GFK-1115 - page 106

    6 - 10 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 CLOCK Picture If you press the F3 function key while the INPUT VALUES picture is on the screen, the CLOCK picture appears on the Panel display: Key LEDs: To change the date and time, enter the desired data in the input fields, using the +p+ and +n+ keys to ...

  • GE Monogram GFK-1115 - page 107

    GFK- 1115 Chapter 6 Demo Project 6 - 11 6 Entering a Password The following sections describe how to use the pictures that have to do with passwords and locked input. INPUT PASSWORD Picture If you press the F2 function key while in the main menu, the Input Password picture appears on the Panel display: Key LEDs: This picture allows you to enter the ...

  • GE Monogram GFK-1115 - page 108

    6 - 12 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 LOCKED INPUT Picture If you press the F1 function key while in the INPUT PASSWORD picture, the LOCKED INPUT picture appears on the Panel display: Key LEDs: If an invalid password has been entered, you cannot change the value for INPUT #1. The value for INPU ...

  • GE Monogram GFK-1115 - page 109

    GFK- 1115 Chapter 6 Demo Project 6 - 13 6 Key Functions If you press the F3 function key while in the main menu, the KEY FUNCTIONS picture appears on the Panel screen: Key LEDs: Keys F1 – F3 are assigned with key functions, i.e., specific variables in the PLC are changed when they are pressed. F1 A value of 10000 is written to PLC address %R0005 ...

  • GE Monogram GFK-1115 - page 110

    6 - 14 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 Alarm List Pressing the F4 key while in the main menu causes the ACTIVE ALARM LIST to appear on the Panel display: Key LEDs: Alarms are displayed according to an alarm bit field that is found in memory location %M001 through %M016 in the PLC. For example, i ...

  • GE Monogram GFK-1115 - page 111

    GFK- 1115 Chapter 6 Demo Project 6 - 15 6 Error Picture Note To simulate an error, simply unplug the cable between the Panel and the PLC and the ERROR picture will be displayed. If the connection between the Panel and the PLC is disrupted for any reason, the error picture, which contains information about the error, is displayed on the Panel displa ...

  • GE Monogram GFK-1115 - page 112

    6 - 16 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 Section 5 Creating the Demo Project General Information This section presents a step by step description explaining how to create a demo project. The section also contains useful information for creating your own projects in the future. More information on ...

  • GE Monogram GFK-1115 - page 113

    GFK- 1115 Chapter 6 Demo Project 6 - 17 6 Preparing a Concept Before you create a new project with PCS, you should form a concept based on the following information: ■ What information should be displayed? ■ What do you need to enter using the Keyblocks? For modular PANELWARE Panels, the first two questions will help you determine the type of D ...

  • GE Monogram GFK-1115 - page 114

    6 - 18 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 Creating a New Project A new project is created by selecting the New Project option from the File menu. Before you execute this function you should know exactly what Panel components will be used . Carry out the following steps: ■ Select the New Project o ...

  • GE Monogram GFK-1115 - page 115

    GFK- 1115 Chapter 6 Demo Project 6 - 19 6 ■ If all of the entries that are required have been defined, you can confirm the whole definition by pressing the F4 Accept key, which closes and saves the hardware definition. The window is closed and the main menu appears. At the top of the screen, the project name DEMO_PRO is displayed. If, instead of ...

  • GE Monogram GFK-1115 - page 116

    6 - 20 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 2 . Edit the default connection DD Genius. • Press F1 Edit . • Specify the GBC type corresponding to your PLC (90-70 in this example). • Press F4 Accept , to confirm your changes. The connection list is displayed with the changed default connection. 3 ...

  • GE Monogram GFK-1115 - page 117

    GFK- 1115 Chapter 6 Demo Project 6 - 21 6 The standard definitions for the parameters shown above can be used as they are for our demo project, with the exception of the target device number. Enter the Genius serial bus address of your GBC (typically 31) and press F4 Accept . For the specific meanings of the protocol parameters and the PLC configur ...

  • GE Monogram GFK-1115 - page 118

    6 - 22 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 Defining Key Assignments 1. Select the Keyboard function from the Edit menu. 2. Define function keys F5 – F8 now. This is started by moving the cursor to the respective key. 3. Press F4 . A small window appears in the lower right-hand corner of the screen ...

  • GE Monogram GFK-1115 - page 119

    GFK- 1115 Chapter 6 Demo Project 6 - 23 6 Creating the Pictures The picture is the basis of a Panel project. Pictures consist of text, lines, fields, key functions and LED functions. These elements can be divided into two groups. There are static elements such as text and lines or dynamic elements like input and output fields. (Lines can only be in ...

  • GE Monogram GFK-1115 - page 120

    6 - 24 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 MAIN Picture (Main Menu) No data from the PLC is shown in this picture. The date and time are taken from the internal real-time clock in the Panel. Text is also displayed informing the user of the function keys that can be used for switching to the next pic ...

  • GE Monogram GFK-1115 - page 121

    GFK- 1115 Chapter 6 Demo Project 6 - 25 6 ● Press ↵ ↵ to open a selection window where you can define the output format. Select the desired format from the window: ● Confirm the selection with ↵ ↵ . ● Confirm the entered field parameters with F4 Accept . ● The output field Date/Time is inserted in the picture: ...

  • GE Monogram GFK-1115 - page 122

    6 - 26 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 5. The next step is to define the LED functions. The key LEDs of function keys F1 to F4 should light up if the main menu is on the display. ● Press F5 Key . All Keyblock modules that are defined in the project are displayed: ...

  • GE Monogram GFK-1115 - page 123

    GFK- 1115 Chapter 6 Demo Project 6 - 27 6 The top four keys of the left-hand Keyblock module are defined as function keys F1 to F4 (see “Defining Key Assignments”). ● Move the cursor to the upper left-most key of Keyblock module (left-most module). Press F2 LED Function . All LED functions are offered in the next window. ● Select the functi ...

  • GE Monogram GFK-1115 - page 124

    6 - 28 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 7. If you want to call up the same picture again for further editing, follow these steps: ● While the main menu is on the screen, press key combination Ctrl + B or select the Picture function from the Edit pulldown menu. The picture editor is called. ● ...

  • GE Monogram GFK-1115 - page 125

    GFK- 1115 Chapter 6 Demo Project 6 - 29 6 3. Insert an input field that increments/decrements using keys F1 and F2, respectively. Follow these steps: ● Position the cursor at (11,2). ● Press F2 Field . ● Select Input Field from the Field Class selection window and press the ↵ ↵ key. ● Select the input field Input Word (unsigned) from th ...

  • GE Monogram GFK-1115 - page 126

    6 - 30 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 Tip If the field ends up in the wrong position in your picture, you can easily move it. First, move the cursor into the field. With key combination Ctrl + Cursor key, the field can be moved to the desired position. 4. Now, insert an input field into the pic ...

  • GE Monogram GFK-1115 - page 127

    GFK- 1115 Chapter 6 Demo Project 6 - 31 6 5. Insert an output field that will display the value that is entered in the first input field, into the picture. This is done as follows: ● Position the cursor at (11,6). ● Press F2 Field . ● Select the Output Field from the Field Class window and press the ↵ ↵ key. ● Select the Output Word (un ...

  • GE Monogram GFK-1115 - page 128

    6 - 32 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 6. Insert an output field into the picture. The value that is entered in the second input field will be displayed in this output field. This is done as follows: ● Position the cursor at (10,7). ● Press F2 Field . ● Select the Output Field entry from t ...

  • GE Monogram GFK-1115 - page 129

    GFK- 1115 Chapter 6 Demo Project 6 - 33 6 7. Next, the LED functions must be defined. ● Function keys F1 and F2 should be assigned LED function Key LED blinking slow. The value in the first input field (see step 3) can be changed in steps with these keys. ● Function keys F3 and F4 should be assigned LED function Key LED switched on . These keys ...

  • GE Monogram GFK-1115 - page 130

    6 - 34 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 Follow these steps to create this picture: 1. Open the picture editor from the main menu with key combination Ctrl + B . 2. Insert all lines and text so that your picture looks like this: 3. Insert a scaled input field for the Hours (HH) entry in the pictur ...

  • GE Monogram GFK-1115 - page 131

    GFK- 1115 Chapter 6 Demo Project 6 - 35 6 ● To achieve a limit on the entry between 0 and 23, the scaling parameters are changed as follows: 0% Value in the PLC: ................ 0 100% Value in the PLC: ............ 23 Minimum Value on Panel: ......... 0 Maximum Value on Panel: ........ 2 3 Setting the scaling parameters to these values stops an ...

  • GE Monogram GFK-1115 - page 132

    6 - 36 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 4. Insert the input fields for minutes (MM:), seconds (SS:), month (MM:), Day (DD:), and Year (YYYY:) into the picture. Use the input field Input Bit/Byte , for all but the Year field, which must be Input Word Unsigned. Basically these fields are inserted t ...

  • GE Monogram GFK-1115 - page 133

    GFK- 1115 Chapter 6 Demo Project 6 - 37 6 After all fields have been entered, the screen will look as follows (the field numbers in the picture correspond to the numbers in the table on page 6-36): When the project is running, you can switch to the previous picture or the next picture by pressing the +p+ key or the +n+ key respectively (see “Defi ...

  • GE Monogram GFK-1115 - page 134

    6 - 38 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 ● Press F4 to confirm the field parameters and to close the Input Word (unsigned) . The input field for the Year (YYYY) is displayed in the picture: 6. Next, the key functions must be defined. By pressing F1 or F2 , the internal variable TIME_SET or DATE_ ...

  • GE Monogram GFK-1115 - page 135

    GFK- 1115 Chapter 6 Demo Project 6 - 39 6 ● Confirm your entry with F4 Accept . The key function is inserted and indicated by the character T : ● Move the cursor to key F2 now. Perform those steps described again. Enter DATE_SET/DI for the Tagname and a 1 again for the Value 1 . ● Press F4 Accept to confirm and save this entry and then press ...

  • GE Monogram GFK-1115 - page 136

    6 - 40 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 PASSWORD Picture (Password Entry) A password can be entered in this picture. The input will be compared with three valid passwords, each of which each corresponds to a different level of access. The current password level is also displayed. If an invalid pa ...

  • GE Monogram GFK-1115 - page 137

    GFK- 1115 Chapter 6 Demo Project 6 - 41 6 ● Enter the following parameters for the password input field: Character Size:................................... 2 Number of Digits: .............................. 6 Destination Tagname: ........................ PASSWORD Tagname for Completion: .................. COMPLETE Value for Completion: .......... ...

  • GE Monogram GFK-1115 - page 138

    6 - 42 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 INPLOCK Picture (password protected entry of values) This picture is a demonstration of password protected value entries. The picture contains two input fields: ● The first input field is locked (i.e., no entry is possible), if the entered password is inv ...

  • GE Monogram GFK-1115 - page 139

    GFK- 1115 Chapter 6 Demo Project 6 - 43 6 ● Change the field parameters as follows: Position: ............................................. 10,3 Number of Digits: .............................. 5 Places after the dec. point: .................. 0 Character Size:................................... 1 Field Width: ................................ ... ...

  • GE Monogram GFK-1115 - page 140

    6 - 44 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 4. Insert the second input field into the picture. ● Insert the input field Input Word (unsigned) into the picture (at cursor position 10,5) with the following parameters: Field parameters Position: ............................................. 10,5 Numbe ...

  • GE Monogram GFK-1115 - page 141

    GFK- 1115 Chapter 6 Demo Project 6 - 45 6 KEYFUNCT Picture (Key Functions) This picture demonstrates key function possibilities. Function keys F1 to F3 on the PANELWARE Panel will be assigned certain key functions: ● By pressing F1, a value of 10 000 should be written to a word in the PLC. ● By pressing F2 the contents of a memory location in t ...

  • GE Monogram GFK-1115 - page 142

    6 - 46 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 3. Insert the first output field and the respective key functions into the picture: ● Insert an output field type, Output Word (unsigned) , with the following parameters: Position: ............................................. 24,3 Number of Digits: ..... ...

  • GE Monogram GFK-1115 - page 143

    GFK- 1115 Chapter 6 Demo Project 6 - 47 6 5. Insert the third output field and its key functions into the picture: ● Insert an output field of type Output Bit/Byte with the following parameters: Position: ............................................. 24,5 Number of Digits: .............................. 1 Places after the dec. point: ............ ...

  • GE Monogram GFK-1115 - page 144

    6 - 48 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 ALARM Picture (Alarm List) This picture shows a list of active alarms. The alarm bit field (16 bits in the demo project) is read from the PLC. Every bit represents an alarm. If an alarm occurs (bit changes from 0 to 1), it will appear in the alarm list. Thi ...

  • GE Monogram GFK-1115 - page 145

    GFK- 1115 Chapter 6 Demo Project 6 - 49 6 5. Assign function keys F1 to F4 with LED function Key LED switched on . Step 5 in “Main Picture” explains how to assign LED functions to individual keys (see page 6-26). 6. Save this picture now under the name ALARM . ...

  • GE Monogram GFK-1115 - page 146

    6 - 50 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 ERR_PIC Picture (Error Picture) The error picture is displayed if an error occurs in the communication with the PLC. Three internal variables containing notes on the cause of the error are displayed in the picture (for more information on these variables se ...

  • GE Monogram GFK-1115 - page 147

    GFK- 1115 Chapter 6 Demo Project 6 - 51 6 Defining the Text Groups A text group named GLOBAL exists for every project. This text group cannot be deleted. Text #0 of this text group contains commands for clearing the display and the key LEDs. These commands are always executed after every picture change. In the demo project, no text is used from a t ...

  • GE Monogram GFK-1115 - page 148

    6 - 52 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 Binding Pictures to the Project Every picture used must be bound into the project. Binding the pictures is done in the project editor (see Chapter 4, “Project Editor” in the PANELWARE™ Configuration Software Reference Manual — GFK-0849). Error Pictu ...

  • GE Monogram GFK-1115 - page 149

    GFK- 1115 Chapter 6 Demo Project 6 - 53 6 Binding Process Pictures The pictures that will be used to display process information or to enter process data (commands) with the Keyblocks must be bound into the project. Press F2 Bind Picture in the project editor. The screen appears: The name of the picture to be bound into the project (the Base pictur ...

  • GE Monogram GFK-1115 - page 150

    6 - 54 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 3. In step 2, only those branches that affect the MAIN picture are defined. To define the complete branching structure (so that it corresponds with the description in “Preparing a Concept Before Beginning”), all pictures must be bound into the project i ...

  • GE Monogram GFK-1115 - page 151

    GFK- 1115 Chapter 6 Demo Project 6 - 55 6 CLOCK Picture: INPLOCK Picture: ERR_PIC Picture: ...

  • GE Monogram GFK-1115 - page 152

    6 - 56 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 Picture Directory/Startup Picture Pressing F3 Picture List , causes a list of all pictures that are bound to be displayed. Pictures that are not bound are also listed, and are indicated as unbound. The picture directory shown below should be displayed if yo ...

  • GE Monogram GFK-1115 - page 153

    GFK- 1115 Chapter 6 Demo Project 6 - 57 6 3. Move the cursor to the rectangle with the misspelled word MANI and change the name to MAIN. Press the F4 Accept key to confirm the change. 4. The corrected picture directory should now be displayed. 5. The Startup picture is the picture that is displayed on the screen as soon as the Panel is switched on ...

  • GE Monogram GFK-1115 - page 154

    6 - 58 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 Editing the Alarm System The alarm system can be accessed via the Alarm System option in the Edit menu, or by pressing the key combination Ctrl + A . The alarm system basic configuration screen appears: For the demo project, no printer will be supported. To ...

  • GE Monogram GFK-1115 - page 155

    GFK- 1115 Chapter 6 Demo Project 6 - 59 6 B . Enter the symbolic name ALARM for the parameter Tagname for Alarm Bit Field . Press F4 Accept to confirm the entry. The newly defined alarm groups are displayed in the alarm group list: C . Move the cursor to the line with the new alarm group. D . Sixteen alarms should be put into this alarm group: ● ...

  • GE Monogram GFK-1115 - page 156

    6 - 60 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 E . Now you can display a list of all alarms in this group by pressing the F5 Alarm List key while in the Alarm Group List window. (Press PgeDn to view the remainder of the Alarm List window.) F . You can change the sequence of the alarms and the definition ...

  • GE Monogram GFK-1115 - page 157

    GFK- 1115 Chapter 6 Demo Project 6 - 61 6 Editing the Connections All of the variables used in the project must be assigned to a certain PLC address in the connection editor. General information on operating the connection editor can be found in the PANELWARE™ Configuration Software Reference Manual (GFK-0849). Access the connection list from the ...

  • GE Monogram GFK-1115 - page 158

    6 - 62 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 Genius Internal Connection To display the Genius Internal variables used in your project, move the cursor in the connection list to the connection GI — GENIUS — Genius Internal and press F5 VAT or ↵ ↵ : If you have made all entries correctly If you ...

  • GE Monogram GFK-1115 - page 159

    GFK- 1115 Chapter 6 Demo Project 6 - 63 6 Genius GBC Series 90-70 Connection All variables used in your project and having the connection DD Genius can be displayed. To do this move the cursor to the GENIUS connection in the connection editor and press the function key F5 VAT or the ↵ ↵ key: If you have made all entries correctly, your screen s ...

  • GE Monogram GFK-1115 - page 160

    6 - 64 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK -1115 6 Compiling the Project To download a project to the Panel, it must first be compiled. Only a project that is loaded (project name in the title bar) can be compiled. Start the compilation by accessing the project compiler, either via the Compile menu option i ...

  • GE Monogram GFK-1115 - page 161

    GFK- 1115 Appendix A Cabling Information A - 1 Appe ndix Cabling Information This appendix describes the required PCS to PLC/PC interface cabling. It includes the following information: ■ Genius Communications ............................................................................................ A-2 ❏ Selecting a Cable Type .............. ...

  • GE Monogram GFK-1115 - page 162

    A - 2 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GF K-1115 A Genius Communications Selecting a Cable Type The Genius bus is a shielded twisted-pair wire, daisy-chained from block to block and terminated at both ends. Proper cable selection is critical to successful operation of the system. Each bus in the system can b ...

  • GE Monogram GFK-1115 - page 163

    GFK- 1115 Appendix A Cabling Information A - 3 Table A - 1. Recommended Cable Types Cable # Terminating Resistor* -10% to +20% Number of Dielectric Voltage Ambient Temp. Maximum Length Cable Run feet/meters at baud rate and Make Outer Dia. 1/2 Watt Conductors/AWG Rating Rating 153.6s 153.6e 76.8 38.4• (A)9823 (B)9182 (C)4596 (M)M39240 350in 8.89m ...

  • GE Monogram GFK-1115 - page 164

    A - 4 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GF K-1115 A Bus Length The maximum bus length for shielded, twisted-pair cable is 7500 feet. Some cable types are restricted to shorter bus lengths. For example, for buses with a total cable length of 100 feet to 2000 feet Belden 9182 or Alpha 9823 or Belden 89182 can b ...

  • GE Monogram GFK-1115 - page 165

    GFK- 1115 Appendix A Cabling Information A - 5 A Connecting Devices to the Bus Devices can be placed in any physical sequence on the bus, however, communications will be most efficient if devices are placed in the same sequence as their Device Numbers (Block Numbers).Each device has four terminals for the serial bus cable (Serial 1, Serial 2, Shiel ...

  • GE Monogram GFK-1115 - page 166

    A - 6 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GF K-1115 A Cable Diagrams Table A-2 provides an overview of the cabling possibilities for connecting PANELWARE Panels, PLCs, printers and PCs (with PCS installed and running). Table A-3 lists the locations of pin-out diagrams in the PANELWARE documentation. Table A - 2 ...

  • GE Monogram GFK-1115 - page 167

    GFK- 1115 B - 1 Appe ndix Errors/Troubleshooting This appendix provides an overview of possible system errors, their causes, and how to handle them. Actual error messages are displayed, followed by possible causes and corrective actions. The following sections of information are included: ■ Errors During Installation.............................. ...

  • GE Monogram GFK-1115 - page 168

    B - 2 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GF K-1115 B Errors During Installation Installation could not be ended properly! Setup program cannot be called! Check that the following conditions are met: ■ PC must contain an 80286 or higher type processor. ■ To install the PCS, the PC must have at least 2 MB ha ...

  • GE Monogram GFK-1115 - page 169

    GFK- 1115 Appendix B Errors/Troubleshooting B - 3 B Errors During Program Start PCS cannot be started! Check that the following conditions are met: ■ PC must contain an 80286 or higher type processor. ■ PC must have at least 640 KB RAM (500 KB must be available). If enough RAM is not available, remove the necessary memory-resident programs. PCS ...

  • GE Monogram GFK-1115 - page 170

    B - 4 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GF K-1115 B Errors While Working in PCS When the PCS is running, error messages are either displayed in the bottom line of the screen (the function key line) or in the current window. Faults running PCS! Check that the following condition is met: ■ FILES and BUFFERS i ...

  • GE Monogram GFK-1115 - page 171

    GFK- 1115 Appendix B Errors/Troubleshooting B - 5 B Error! Error picture and first picture cannot be the same! The compilation of a project is interrupted with this error message if the error picture is defined in the first position of the picture directory. The start-up picture must be listed in the first position of the directory (see the Chapter ...

  • GE Monogram GFK-1115 - page 172

    B - 6 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GF K-1115 B Error Numbers in Internal USER Variable The name of an internal user variable can be defined in the PLC Node Parameter Definition window (see chapter 4). These variables are assigned the following error numbers: Error Number Definition 24100 ... GENI Board O ...

  • GE Monogram GFK-1115 - page 173

    Index GFK-1115 Index-1 A Accessing the Connection List, 5-2 Alarm field, 6-48 Alarm group definition, 6-58 Alarm list, 6-48 Alarm system activation, 6-60 editing, 6-58 B Base picture, 6-53 Baud Rate, 4-7 Baud rate selection, A-4 Binding pictures error picture, 3-35 overview, 3-32 Pict_1 picture, 3-37 picture for a communications error, 3-33 picture ...

  • GE Monogram GFK-1115 - page 174

    Index Index-2 GFK-1115 F Firmware revision, 4-4 Flash memory, 3-39 FlashPROM, 2-9, 6-64 Function keys of the VAT, 5-7 G General information connection editor, 5-2 Controllers, 2-2 General operation PCS, 3-6 PCS screen elements, 3-8 Genius (Definition in PCS), 4-2 Genius bus connector, 2-7 Genius communications, A-2 baud rate, A-4 bus length, A-4 co ...

  • GE Monogram GFK-1115 - page 175

    Index GFK-1115 Index-3 Password, 6-40, 6-42, 6-44 PCS configuration, 3-9 General operation, 3-6 installation, 3-2 Overview, 1-2 starting, 3-5 Phase A devices bus length and baud rate, A-4 Picture 1, 3-21 Picture 2, 3-25 Picture 3, 3-27 Picture Directory, 1-2, 6-56 Picture for communication error, 6-50, 6-52 Picture list directory organization, 3-38 ...

Производитель GE Monogram Категория Appliance Trim Kit

Документы, которые мы получаем от производителя устройства GE Monogram GFK-1115 мы можем разделить на несколько групп. Это в частности:
- технические чертежи GE Monogram
- инструкции обслуживания GFK-1115
- паспорта изделия GE Monogram
- информационные брошюры
- энергетические этикетки GE Monogram GFK-1115
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания GE Monogram GFK-1115.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа GE Monogram GFK-1115, инструкции обслуживания, короткие инструкции или инструкции пользователя GE Monogram GFK-1115. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия GE Monogram GFK-1115.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства GE Monogram GFK-1115, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании GE Monogram GFK-1115 пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей GE Monogram GFK-1115.

Полная инструкция обслуживания GE Monogram, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией GE Monogram GFK-1115 - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания GE Monogram GFK-1115, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся GE Monogram GFK-1115, которое найдем в данном документе
3. Советы по использованию основных функций устройства GE Monogram GFK-1115 - которые должны облегчить нам первые шаги во время использования GE Monogram GFK-1115
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем GE Monogram GFK-1115
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра GE Monogram GFK-1115 в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся GE Monogram GFK-1115?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с GE Monogram GFK-1115, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с GE Monogram GFK-1115 со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)