0.17 mb

of 16

Summary
  • Liebert SL-14050 - page 1

    SGH Steam Generating Humidifier Installation and Operation Guide IMPORTANT: Read and save this guide for future reference. This guide to be left with equipment owner. SL-14050 Form # 99-428 Rev. 1 / 150-1633 Rev. A ...

  • Liebert SL-14050 - page 2

    Table Of Contents INSTALLATION 1 RECEIVING & UNPACKING EQUIPMENT ................................1 PRE-INSTALLATION CHECKPOINT ...................................1 BASIC HUMIDIFIER CONFIGURATION ..................................1 LOCATION & MOUNTING .........................................1 HUMIDIFIERS .................................... ...

  • Liebert SL-14050 - page 3

    INSTALLATION RECEIVING & UNPACKING EQUIPMENT 1. Check packing slip to ensure ALL material has been delivered. 2. All material shortages are to be reported to Liebert within 48 hours from receipt of goods. Liebert assumes no responsibility for any material shortages beyond this period. 3. Inspect shipping boxes for damage and note on shipping wa ...

  • Liebert SL-14050 - page 4

    to clearances required for plumbing, electrical, and control entrances. The clearance dimensions shown in this manual are for reference only and are the minimum required for maintenance of the humidifier. Local and National Codes should be consulted prior to final location and installation of the humidifier. Liebert can not accept responsibility fo ...

  • Liebert SL-14050 - page 5

    FRONT WALL SIDE STEAM CONDENSATE A 005-030 3.2" (8.0cm) 050-100 3.2" (8.0cm) A POWER AND CONTROL WIRING FROM HUMIDIFIER 10-20 050-100 3.2” (8 cm) 3. All SGH blower packs consist of a steel cabinet containing: blower/motor powered by voltage directly from the humidifier, fuse, relay, speed select switch, stainless steel steam distributor ...

  • Liebert SL-14050 - page 6

    5. Exercise extreme caution when installing in fiber glass or internally lined ducts. 6. High positive or negative static pressure ducts or plenums have special requirements. High positive static pressure ducts may require the unit to be fitted with a fill cup extension kit. High negative static pressure ducts will likely require the drain rate of ...

  • Liebert SL-14050 - page 7

    10. Any distributor longer than 3 feet (1 meter) should be supported at its end with a threaded rod through top or bottom of duct. See Figure #10. 11. It is recommended that single distributors are mounted near the bottom of the duct to ensure the steam is dispersed into the majority of the air flow. See Figure #12. 12. Using duct mounting template ...

  • Liebert SL-14050 - page 8

    5. ALWAYS supply and install a shut off valve in the water supply line dedicated to the humidifier to facilitate servicing. Use ½ "O D copper to within 4 feet of the humidifier. Reduce copper to 3/8" OD and connect to the factory-supplied 3/8" olive compression fitting under the humidifier. DRAIN LINE 1. Humidifier is equipped with ...

  • Liebert SL-14050 - page 9

    3. Liebert steam supply hose or field-supplied piping should be sloped downwards from the steam distributors to the humidifier. Slope should be at least 2" in 12" to promote condensate runback. See Figure #18. If this slope is not possible, condensate must be removed before the distributor. See Figure #19. 4. Minimize the length of steam ...

  • Liebert SL-14050 - page 10

    ACCESSORIES - FILL CUP EXTENSION KIT(S) 1. The SGH humidifier is an electrode humidifier. It produces steam at atmospheric pressure. Pressure head must develop to push steam through supply line and into air duct. 2. Combined resistance of duct positive static pressure and steam line resistance creates a small pressure head in steam cylinder. Total ...

  • Liebert SL-14050 - page 11

    impeding condensate flow when duct pressures are below atmosphere. 6. The condensate line can go to either of two large holes in the fill cup cover on top of humidifier. 7. It is not necessary to return the condensate to the humidifier. 8. Long condensate runs (more than twenty feet) should be sloped well and be constructed out of ½ " nominal ...

  • Liebert SL-14050 - page 12

    information is relevant to all controls, factory supplied or otherwise. A, B and C (described below) are to be wired in series (only one path for current) across terminals 8 and 10 on the low voltage control terminal strip, or replaced with a jumper wire for constant operation (see Figure #27). Caution: If any control field wiring touches ground me ...

  • Liebert SL-14050 - page 13

    4. The modulation signal must increase from minimum toward maximum as sensed RH (actual RH) drops below desired RH (%RH setpoint). In response, humidifier ’ s steam output will increase from minimum toward maximum. When humidifier ’ s steam output (lbs/hr) matches humidification load (lbs/hr), modulation signal will stabilize. 5. Field-wiring c ...

  • Liebert SL-14050 - page 14

    satisfied and stops again. The resultant short-cycling is easily overcome. A manual capacity adjustment potentiometer ( “ pot ” ) is provided on the SGH main pc board for that purpose. It is marked “ CAPACITY ADJUST ” and is adjustable from 25 to 100% of rating. Modulation Control The SGH humidifier, utilizing modulation control, does not h ...

  • Liebert SL-14050 - page 15

    LIMITED WARRANTY Liebert Corporation (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years from date of shipment, that THE COMPANY ’ s manufactured and assembled products, not otherwise expressly warranted (with the exception of the cylinder) are free from defects in material and workmanship. No warranty is made ...

  • Liebert SL-14050 - page 16

    Model # :_________________________ Serial # :__________________________ Cylinder # :_________________________ Cylinder Last Replaced: _________________________ MTH/DAY/YR _________________________ MTH/DAY/YR _________________________ MTH/DAY/YR PRINTED IN CANADA LIEBERT CORPORATION 1050 Dearborn Drive, P.O. Box 29186 Columbus, Ohio 43229 Tel: (614) ...

Liebert Blowtorch

:
-
-
-
-
-






1.
2.
3.
4.
5.
6.

Captcha

(0)