  • Carrier 50HCQA - page 1

    1 50HCQA Si ngle Packa ge Rooftop Heat P ump with P uron r (R - - - 410A) Refrig erant S i z e s 0 4 --- 0 6 Installation Instructions NOTE : Read the entire instru ction manual before s tarting the ins tallation T ABLE OF CONTENTS SAFET Y CONSIDE RA TIONS 2 .................... INS T ALLA TION 4 ............................... Jobsite Survey 4 ... ...

  • Carrier 50HCQA - page 2

    2 Return Air E nthalpy Sensor 29 ................. Indoor Air Quality (CO 2 sensor) 30 ............. Outdoor Air Qua lity Sens or 30 ................. Connect ing Discrete Inputs 30 .................. Commun ication W iring - - Pro tocols 31 ............ General 31 ................................. Local Acces s 32 ............................. R T ...

  • Carrier 50HCQA - page 3

    3 Horizontal Connections / Economizer V ertical Connections / Economizer C10230 Fig. 1 - - Unit Dimensional Drawing – 04 — 06 Size Units 50HCQ A ...

  • Carrier 50HCQA - page 4

    4 C10231 Fig. 1 - - Unit Dimensional Drawing – 04 — 06 Size Unit (cont.) INST ALLA TION Jobsite Survey Complete th e follow ing check s bef ore ins tallation. 1. Consult local buildi ng codes a nd the NEC (Nat ional Electrical Code) AN SI/N FP A 70 for special ins talla- tion requ irements . 2. Det ermi ne unit loca tion (from proje ct pla ns) ...

  • Carrier 50HCQA - page 5

    5 Roof Mount — Check bui lding code s for weight distribution requirem ents. Unit operat ing weight i s shown in T a ble 1. Ste p 2 — Plan for Seque nce of Unit Inst allation The support me thod used for thi s uni t will di cta te different sequence s for the steps of unit i nstall ation. For exa mple, on curb- - mounted units, some accessories ...

  • Carrier 50HCQA - page 6

    6 50HCQA04-06 ROOFCURB ACCESSORY CRRFCURB001A02 CRRFCURB002A02 1’ - 2” [356] 2’ - 0” [610] UNIT SIZE C10232 Fig. 3 - - Roof Curb Details 50HCQ A ...

  • Carrier 50HCQA - page 7

    7 A-B 0.5” (13) B-C 1.0” (25) A-C 1.0” (25) MAXIMUM ALL OWABLE DIFFERENCE IN. (MM) C06110 Fig. 4 - - Unit Lev eling T olerances Ste p 5 — Field Fabr icate Duct work Cabinet re turn-ai r static pre ssure (a negative condition) shall not exceed 0.35 in. wg (87 P a) w ith economizer or 0.45 in. wg (1 12 Pa) without econom izer. For verti cal d ...

  • Carrier 50HCQA - page 8

    8 C06005 UNI T MAX W EIG HT DIMENS IONS A B C LB KG IN MM IN MM IN MM 50HCQ A04 725 330 74.5 1890 38.5 980 33.5 850 50HCQ A05 845 384 74.5 1890 37.5 955 41.5 1055 50HCQ A06 900 409 74.5 1890 37.5 955 41.5 1055 NOTES : 1. Dimensions in ( ) are in m illimeters. 2. Hook rig ging sh ackles through h oles in base rail, a s shown in d etail “ A .” H ...

  • Carrier 50HCQA - page 9

    9 Ste p 8 — Install Outside Air Hood Economize r Hood Removal and Setup - - Factory Op tion — 1. T he hood is shipped i n knoc k - - down form and loc ate d in the return air compartmen t. It is attached to the economizer u sing tw o plas tic tie - - wraps . 2. T o gain access t o t he hood, remove the filter access panel. (See Fig. 7. ) 3. Loc ...

  • Carrier 50HCQA - page 10

    10 Economize r Hood and T wo- - P osition Hood — NOTE : If the pow er exhaus t access ory is to be ins talled on the unit , t he hood shipped with t he unit will not be used and mus t be dis carded. S ave the aluminu m filter for use in the powe r exhaust hood assembl y . 1. The indoor co il access panel will be used as the top of the hood. Rem o ...

  • Carrier 50HCQA - page 11

    11 NOTE: T rap should be deep enough to offset maximum unit static difference. A 4” (102) trap is recommended . MINIMUM PITCH 1” (25mm) PER 10’ (3m) OF LINE BASE RAIL OPEN VENT TO ROOF DRAIN DRAIN PLUG ROOF CURB SEE NOTE 2 ˝ (51) MIN C08022 Fi g. 14 - - Co ndensa te Dr ai n P ipi ng De tai l s All unit s mus t have an ex ternal trap f or con ...

  • Carrier 50HCQA - page 12

    12 Un its wit h Factory- - Ins talled D iscon nect — The factory- - installed op tion dis connect sw itch is located in a weathe rproof enclosure loca ted under the m ain control box. The m anual sw itch handle is accessible through an opening in the access panel. Discard the factory tes t leads (see Fig. 16) . Units Without Disconnect Option Uni ...

  • Carrier 50HCQA - page 13

    13 Mount the weatherproof c over to t he backi ng pla te as sho wn in F ig. 18. Remove two s lot fillers in the bottom of the cove r to permit servic e tool cords to exit t he cover . Check f or full clos ing and latchin g. RECEPTACLE NOT INCLUDED COVER – WHILE-IN-USE WEATHERPROOF BASE PLATE FOR GFCI RECEPTACLE C09022 Fig. 18 - - W e atherproof C ...

  • Carrier 50HCQA - page 14

    14 LOW VOL T AGE CONDUIT CONNECTOR HIGH VOL T AGE CONDUIT CONNECTOR C08637 Fig. 20 - - Thru- - Base Con nectio n Fittin gs Field - - supplie d and field - - insta lle d liquid - - t ight conduit connec tors and conduit may be a ttac hed to t he conne ctors on the bas epan. Pu ll correctly rated high voltag e and low voltage t hrough appropriat e co ...

  • Carrier 50HCQA - page 15

    15 RACEW A Y HOLE IN END P ANEL (HIDDEN) C08027 Fig. 22 - - Fie ld Control W iri ng Raceway Electri c Heaters 50HCQ uni ts may be equipped with field - - insta lle d access ory electric heaters. The heaters a re modular in design, wit h heat er frame s holding open c oil re sistance wires s trung through ceramic in sulators, line - - break limit sw ...

  • Carrier 50HCQA - page 16

    16 TRACK FLANGE C08135 Fi g. 2 5 - - T y pic al M odul e Instal l ati on Single Po int Boxe s and Suppleme nta ry Fuse When the unit MOCP device value exceeds 60- - A, unit - - mounted suppl ementary fuses a re required for each heater circu it. These fu ses are inclu ded in access ory Single Point Boxe s, with power distributi on and fuse blocks. ...

  • Carrier 50HCQA - page 17

    17 PremierLin k t (Factory- - Option) C08199 Fig. 28 - - Premier Link Contr olle r The Premier Link contr oller (see F ig. 28 ) is compatib le with Car rier Comf ort Netw ork r ( CCN) dev ices. This contro l is designed to allow users the access and ability to change fact ory- - de fined set tings, t hus expa nding the function of t he standa rd un ...

  • Carrier 50HCQA - page 18

    18 C10227 Fig. 30 - - T ypica l Prem ierLink W iring Schem atic 50HCQ A ...

  • Carrier 50HCQA - page 19

    19 Out door A ir T emp eratu re ( OA T) Sen sor — The OA T i s factory - - mount ed in t he Ec onoMi$er2 (FIOP or acces sor y). It is a nominal 10 k ohm ther mistor attached to an eyelet moun ting ring. EconoMi$e r t 2— The Premi erLi nk control is used with E conoMi$er2 (option or access o ry) for outdoor air management. The damper po sition i ...

  • Carrier 50HCQA - page 20

    20 GJ 4 - 1 2 J4- 1 0 J4-8 Y1 Y2 2 R R 4 6 J4-6 J4-4 W2 C 8 10 C SP ACE THERMOST A T PL CTB THERMOST A T W1 TB1 CTB THERMOST A T C08119 Fig. 35 - - Space Th ermos tat C onn ection s T ab le 3 – PremierL ink S ens or Us age APP LICATION OUTD OOR AIR TEMPERA TURE SEN SOR RETU RN AIR TEMPERA TURE SEN SOR OUTD OOR AIR EN THA LPY SE NSOR RETU RN AIR E ...

  • Carrier 50HCQA - page 21

    21 T abl e 4 – Space Se nsor M ode TB1 TERMINA L FIELD C ONNEC TION INPU T S IGNAL 1 T 5 5 --- S E N / T 5 6 --- S E N An alog (10k th erm istor) 2 RMTOC C Discrete, 24VAC 3 T 5 5 --- S E N / T 5 6 --- S E N An alog (10k th erm istor) 4 CMPS AF E Discrete, 24VAC 5 T56 - - - SET An alog (10k th erm istor) 6 FSD Discrete, 24VAC 7 L OOP - - - PW R A ...

  • Carrier 50HCQA - page 22

    22 If the 5 0HC Q un it has an economizer sy stem and free - - cool ing operat ion is requi red, a sensor represent ing Return A ir T emperature mus t also be connected (field - - suppli ed and insta lle d). Thi s sensor may be a T- - 55 Space Sensor (see Fig. 31) i nstalle d i n the space or in the return du ct, or it may be sens or PNO 33 ZCSEN S ...

  • Carrier 50HCQA - page 23

    23 8 7 6 5 4 32 1 2 1 HG 24 V AC OR 24 VDC NC ALARM RELA Y CONT ACTS COM NO } 0-10VDC SIG COM 4-20mA + + - + - J3 J4 C08635 Fig. 38 - - Ind oor/ Outdoor Air Quality (CO 2 )S e n s o r (33ZCSENC O2) - - T ypical Wiring Diagram T o accurately monitor th e quality o f the air in the conditio ned air sp ace, locate the senso r near a return- - air gril ...

  • Carrier 50HCQA - page 24

    24 On 50HCQ units equipped with fa ctory - - insta lle d Smoke Detector (s) , the smoke detector co ntroller implemen ts the unit shutdown t hrough its NC conta ct set c onnect ed to the unit’ s CTB input. The FSD func tion is initiated via the smoke detec tor ’ s A la rm NO contact set. The Prem ierL ink communi cat es the smoke detector ’ s ...

  • Carrier 50HCQA - page 25

    25 signal pins must be wired to the signal ground pins. W i ring c onnect ions for CCN must be made a t t he 3 - - pin plug. At any baud (9600, 19200, 38400 baud), the numbe r of contro llers is limited to 239 devices maximum. Bus length may not exceed 4000 ft, with no more than 60 total devic es on a ny 1000- - ft secti on. Optic all y i solate d ...

  • Carrier 50HCQA - page 26

    26 R TU - - MP Control Sys tem The R TU- - MP cont rolle r , see Fig. 47, provi des expanded stand - - al one operati on of the HV AC system plus connec tion and c ontrol t hrough communi cat ion with several Bui lding Automa tion System s (BAS) through popular thi rd - - part y network systems. T he availa ble network systems a re BACnet MP/TP , M ...

  • Carrier 50HCQA - page 27

    27 C10229 Fig. 49 - - T ypic al R TU - - MP System Contr ol Wiring Diagram 50HCQ A ...

  • Carrier 50HCQA - page 28

    28 T abl e 8 – RTU- - M P Cont roll er Inputs and O utputs POI NT N AME BA Cnet O BJ ECT NAME TYPE OF I/O CON NE CTI ON PI N NUMB ERS INPU TS Space T em peratu re Sensor sptsens AI (10K T hermistor) J 2 0 --- 1 , 2 Supply Air T emperature sat AI (10K Thermistor) J2 - - - 1, 2 Loca l Outside Air T emper ature Sens or oatsens A I (10K Th ermistor) ...

  • Carrier 50HCQA - page 29

    29 Field Conne ct ions Field connections for accesso ry s ensors and input devices are made t he R T U- - MP , at plugs J1, J2, J4, J5, J1 1 and J20. All field c ontrol wiring that c onnect s to the R TU - - MP must be routed through the r aceway built into the corner pos t as sho wn in F ig. 22. The raceway pr ovides the UL required cl eara nce be ...

  • Carrier 50HCQA - page 30

    30 T o wire the r eturn ai r entha lpy sensor , perform the follow ing: 1. Use a 2 - - conduc tor , 18 or 20 A WG, twisted pai r cable to conne ct the return a ir enthalpy sensor to the enthal- py controll er . 2. Conne ct the fie ld - - suppli ed RED wire to (+) spade connec tor on the re turn ai r entha lpy s ensor and the (+) term inal on the en ...

  • Carrier 50HCQA - page 31

    31 Input 8 or 9 is rec ommende d for easy of insta llat ion. Refer to Fig . 47 and Fig. 49 fo r wire terminatio ns at J5 . Rem ote O c cupa ncy : The remote occupancy access ory is a field- - installed acces sor y . This access ory overrides th e unoccupi ed mode a nd puts the uni t in occ upied m ode. When ins talling this acces sory , the unit mu ...

  • Carrier 50HCQA - page 32

    32 Loca l A ccess — BACvi ew 6 H andhe l d: The BA Cview 6 is a ke ypad/displa y interface used to connect to the R TU- - MP to access th e control i nformat ion, re ad sensor value s, and te st the R TU, see Fig. 57. This is an accessor y interface that does not come w ith the MP co ntroller and can on ly be u sed at th e unit. Conne ct the BACv ...

  • Carrier 50HCQA - page 33

    33 T able 9 – LEDs The LEDs on the R TU- - MP s how th e status of certain fu nctions If th is LE D is on ... Statu s is... Power The R TU MP has power Rx The RTU MP is receiving data from the network segment Tx The R TU MP is tran smitting d ata over th e network segm ent DO# The digital output is active The Run and Error LEDs indicate contr ol ...

  • Carrier 50HCQA - page 34

    34 Duct smoke sensor control ler Fast ener (2X) Cont rol ler co ver Conduit nuts (sup pli ed by instal ler ) Cond uit sup port pl ate Cover ga sket (ordering option) Cond uit cou plin gs (sup pli ed by install er) T erminal block cov er Contr oll er hous ing and e lectronics Alarm Po wer Te s t / r e s e t switch Tro u b le C08208 Fig. 58 - - Con t ...

  • Carrier 50HCQA - page 35

    35 loca tion and t he tubing to the sampli ng tube be connected. See “ Completing In stallation of Return Air Smoke Senso r :” for details.) Return Air Detector Sampling T ube Controller module Return Air Detector module (shipping position shown)* *RA detector must be moved from shipping position to operating position by installer C07307 Fig. 6 ...

  • Carrier 50HCQA - page 36

    36 T ab le 10 – U nit W ire/Fu se or HA CR Br eaker Sizin g Da ta UNI T N O M . V --- P h --- H Z IFM TY PE ELEC. HTR P .E. NO C .O. o r UNP WR C .O. CRHEA TER*** NOM (K W) FL A FLA NO P .E. w/P .E. ( pwrd fr/unit) MCA FUSE or HACR BRKR DISC. SIZE MCA FUSE or HACR BRKR DISC. SIZE FLA LRA FL A LRA 50HCQA04 208/230 - - - 1 - - - 60 D D --- S T D NO ...

  • Carrier 50HCQA - page 37

    37 T abl e 10 — Uni t Wire/ F use or HACR Bre ake r Si zi ng Dat a (co nt) UNI T N O M . V --- P h --- H Z IFM TY PE ELEC. HTR P .E. w/ PWR D C.O. CRHEA TER*** NOM (K W) FL A FLA NO P .E. w/P .E. ( pwrd fr/unit) MCA FUSE or HACR BRKR DISC. SIZE MCA FUSE or HACR BRKR DISC. SIZE FLA LRA FL A LRA 50HCQA04 208/230 - - - 1 - - - 60 D D --- S T D NONE ...

  • Carrier 50HCQA - page 38

    38 T abl e 10 — Uni t Wire/ F use or HACR Bre ake r Si zi ng Dat a (co nt) UNI T N O M . V --- P h --- H Z IFM TY PE ELEC. HTR P .E. NO C .O. or U NPWR C.O. CRHEA TER*** NOM (K W) FL A FLA NO P .E. w/P .E. (pwrd fr/unit) MCA FUSE or HACR BRKR DISC. SIZE MCA FUSE or HACR BRKR DISC. SIZE FLA LRA FL A LRA 50HCQA05 208/230 - - - 1 - - - 60 D D --- S ...

  • Carrier 50HCQA - page 39

    39 T abl e 10 — Uni t Wire/ F use or HACR Bre ake r Si zi ng Dat a (co nt) UNI T N O M . V --- P h --- H Z IFM TY PE ELEC. HTR P .E. w/ PWRD C .O. CRHEA TER*** NOM (K W) FL A FLA NO P .E. w/P .E. (pwrd fr/unit) MCA FUSE or HACR BRKR DISC. SIZE MCA FUSE or HACR BRKR DISC. SIZE FLA LRA FL A LRA 50HCQA05 208/230 - - - 1 - - - 60 D D --- S T D NONE - ...

  • Carrier 50HCQA - page 40

    40 T abl e 10 — Uni t Wire/ F use or HACR Bre ake r Si zi ng Dat a (co nt) UNI T N O M . V --- P h --- H Z IFM TY PE ELEC. HTR P .E. NO C .O. or U NPWR C.O. CRHEA TER*** NOM (K W) FL A FLA NO P .E. w/P .E. (pwrd fr/unit) MCA FUSE or HACR BRKR DISC. SIZE MCA FUSE or HACR BRKR DISC. SIZE FLA LRA FL A LRA 50HCQA06 208/230 - - - 1 - - - 60 D D --- S ...

  • Carrier 50HCQA - page 41

    41 T abl e 10 — Uni t Wire/ F use or HACR Bre ake r Si zi ng Dat a (co nt) UNI T N O M . V --- P h --- H Z IFM TY PE ELEC. HTR P .E. w/ PWRD C .O. CRHEA TER**** NOM (K W) FL A FLA NO P .E. w/P .E. (pwrd fr/unit) MCA FUSE or HACR BRKR DISC. SIZE MCA FUSE or HACR BRKR DISC. SIZE FLA LRA FL A LRA 50HCQA06 208/230 - - - 1 - - - 60 D D --- S T D NONE ...

  • Carrier 50HCQA - page 42

    42 Legend and Notes for T able 10 LEG END: BRKR - - - C ircuit breaker CO - - - Conve nie nt out let DD - - - Direct dr ive ind oor fan motor DISC - - - Disconnect FLA - - - Full loa d a mp s IFM - - - Ind oor fan motor LRA - - - Locke d roto r amps MCA - - - Minimum cir cuit a mps P E --- P o w e r e x h a u s t PWRD CO - - - Powe red convenie nt ...

  • Carrier 50HCQA - page 43

    43 Step 12 — I n stal l Access ori es A vailable access ories includ e: Roof Curb Thru - - base c onnect ion kit (m ust be insta lle d before unit is set on c urb) Manual outside air da mper T wo- - Pos ition motorized out side air damper EconoMi$er IV (with control and inte grate d barometric relie f) EconoMi$e r2 (without control/ for externa l ...

  • Carrier 50HCQA - page 44

    44 Copyright 2010 Carrier Corp. D 7310 W . Morris St. D I ndianapolis, I N 46231 Print ed in U.S.A. Ed ition Date: 04/10 Manufacturer reser ves the right to change , at any time, specifications and d esigns without notice and without ob ligations. Catal og No : 50HCQ - - - 01SI Replaces : NEW 50HCQ A ...

Produzent Carrier Kategorie Heat Pump

Dokumente, die wir vom Produzenten des Geräts Carrier 50HCQA erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Carrier
- Bedienungsanleitungen 50HCQA
- Produktkarten Carrier
- Informationsbroschüren
- oder Energieetiketten Carrier 50HCQA
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Carrier 50HCQA.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Carrier 50HCQA, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Carrier 50HCQA. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Carrier 50HCQA ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Carrier 50HCQA, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Carrier 50HCQA hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Carrier 50HCQA verständlich ist.

Eine gänzliche Bedienungsanleitung von Carrier sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Carrier 50HCQA bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Carrier 50HCQA befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Carrier 50HCQA, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Carrier 50HCQA - die uns die ersten Schritte während der Nutzung von Carrier 50HCQA erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Carrier 50HCQA hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Carrier 50HCQA im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Carrier 50HCQA?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Carrier 50HCQA nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Carrier 50HCQA hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)