Bedienungsanleitung Slant/Fin BOILERS

20 Seiten 0.6 mb
Download

Zur Seite of 20

Summary
  • Slant/Fin BOILERS - page 1

    CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .P A GE Ratings and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Installation Requirements: Boiler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 C ...

  • Slant/Fin BOILERS - page 2

    2 LIBERTY II Standard working pressure 30 psi water , 15 psi steam. All boilers hydrostatically tested — A.S .M.E. * For f orced hot water heating systems where the boiler and all piping are located within the area to be heated, the boiler ma y be selected on the basis of g ross D .O .E. capacity output. The net I=B=R output ratings shown are bas ...

  • Slant/Fin BOILERS - page 3

    L IBERTY II 3 BOILER LOCA TION Provide a le v el, solid f oundation f or the boiler . Location should be near the chimney so that the Flue Pipe Connector or Breeching to the chim- ney is short and direct. A. The foundation m ust be capable of supporting the weight of the boiler when filled with water: B. The Liber ty II Boiler has full wet base sec ...

  • Slant/Fin BOILERS - page 4

    4 LIBERTY II Any oil-fired boiler must ha v e a steady draft* and an ample supply of combustion air at all times during firing. If air supply or chimney dr aft* is unreliable , CO 2 and ov erfire draft* will change unpredictab ly . DO NO T v ent this boiler to the same chimney flue used b y a fireplace or coal or wood burning furnace or boiler. The ...

  • Slant/Fin BOILERS - page 5

    L IBERTY II 5 Figure 3a. Appliances located in confined spaces. Air from inside the building. See T able 2 (2.3). Figure 3b. Appliances located in confined spaces. Air from out- doors. See T able 2 (2.4). Figure 3c. Appliances located in confined spaces. Air from out- doors through ventilated attic. See T able 2 (2.4). Figure 3d. Appliances located ...

  • Slant/Fin BOILERS - page 6

    6 LIBERTY II INST ALLING CONTROLS AND A CCESSORIES ON BOILER UNITS Note : Jac ket m ust be installed on boiler units prior to installation of trim. I. STEAM BOILER TRIM, see page 2 f or tapping locations, and figure 4 for illustr ation of steam boiler . A. Steam pressure gauge and pressure cut-out, install in tapping n o . 4, figure 4. B. Gauge gla ...

  • Slant/Fin BOILERS - page 7

    L IBERTY II 7 C . HO T W A TER RADIA TION VENTING - Manual air v ents should be installed at the top of all "drops"(where piping goes downward). Air must be vented or purged from all z one lines to permit proper system heating. D . PUMP LOCA TION-Locating low-head pump(s) on retur n to boil- er is only acceptable in residences of one or t ...

  • Slant/Fin BOILERS - page 8

    8 LIBERTY II VENT PIPING AND DRAFT REGULA T OR A. V ent pipes must be installed having the same diameter as the boiler outlet. (See page 2) B. V ent pipes and breeching must be pitched upward a minimum of 1/4" per foot. C . Connect vent pipe to the chimney using as f ew elbows as possible . D . Horizontal vent connector into the chimne y shoul ...

  • Slant/Fin BOILERS - page 9

    L IBERTY II 9 CLEANING AND FILLING A NEW STEAM BOILER I. BEFORE USING STEAM BOILER A. Check burner to be cer tain it is ready for firing. DO NOT FIRE into an empty boiler . B. Be prepared to heat raw w ater to at least 180°F . as soon as it is introduced into the boiler . This procedure will remove dissolv ed, corrosive gases . C . Provide drain l ...

  • Slant/Fin BOILERS - page 10

    1 0 LIBERTY II CA UTION: When flushing float type low water cut-off control, hot water and steam will flow out the b low do wn valv e . Blow down v alve is illus- trated below . A. SPECIAL FLUSHING INSTRUCTIONS For ne w boiler installed in old system. Installation of new boiler ma y break loose a hea vy accumulation of sediment and scale from old p ...

  • Slant/Fin BOILERS - page 11

    L IBERTY II 11 ...

  • Slant/Fin BOILERS - page 12

    1 2 LIBERTY II T T 24 VOLT T HERMOSTAT FLAME DETECTOR BLACK RED WHITE 4 2 1 3 NOZZLE LINE HEATER IF EQUIPPED G REEN GROUNDING SCREW QUICK DISCONNECT PLUG 1 3 L2 L1 W HITE OTHER SAFETY CONTROL BLACK RED GREEN HIGH LIMIT 2 1 ELECTRICAL POWER SUPPLY. PROVIDE DIS CONNECT MEANS AND OVERLO AD PROTECTION AS R EQUIRED BY CODES. 2 CONTROL CASE MUST BE CONNE ...

  • Slant/Fin BOILERS - page 13

    L IBERTY II 13 4 2 1 3 1 2 2 H EX NUT LOOSE WHITE WIRE LEAD TO PROBE BLACK WHITE R ED G REEN L 4006A LOW LIMIT FOR TANKLESS OPTIONAL T T F F FLAME DETECTOR WHITE BLACK RED GREEN GROUNDING SCREW L OW WATER ALARM O R WATER FEEDER ( OPTIONAL) NOZZLE LINE HEATER IF EQUIPPED 1 P RESSURE C UT OUT BURNER JUNCTION BOX P ROBE BLUE Q UICK DISCONNEC T PLUG 2 ...

  • Slant/Fin BOILERS - page 14

    1 4 LIBERTY II ...

  • Slant/Fin BOILERS - page 15

    L IBERTY II 15 BURNER D A T A – BECKETT CF-375 BURNERS FOR P A CKA GED BOILERS ONL Y ( For knoc k ed-down & boiler b urner units see publication no . L-42KB) LD-60 CF-375 2.60 2.25 45˚ P HA GO 135 10 3 1 LD-60 CF-375 2.85 2.25 45˚ P HA GO 160 10 2 2 LD-70 CF-375 3.00 2.5 45˚ SS HA GO 145 10 4 3 LD-70 CF-375 3.10 2.5 45˚ SS HA GO 155 10 4 ...

  • Slant/Fin BOILERS - page 16

    1 6 LIBERTY II ...

  • Slant/Fin BOILERS - page 17

    L IBERTY II 17 NO TE: ELECTRODES ARE PRESET A T THE F ACT ORY . REGULA TION OF THE TURBULA TOR AND AIR SHUTTER FOR PROPER COMBUSTION T urbulator Setting 1. Loosen nut, 1, then turn the screw , 2, until the index marker , 3, is aligned with the correct index n umber . 2. Retighten the retaining nut, 1. TURBULA T OR SETTINGS - RIELLO 40 SERIES The nu ...

  • Slant/Fin BOILERS - page 18

    1 8 LIBERTY II ...

  • Slant/Fin BOILERS - page 19

    L IBERTY II 19 ...

  • Slant/Fin BOILERS - page 20

    L IBERTY II 20 I. EXTENDED SHUTDOWN, CLEANING OR REMO V AL OF BOILER FROM SER VICE. D ANGER: Use CA UTION when handling chemicals and draining hot w ater from a boiler . Scalding water and/or chemicals can cause per - manent injur y to the skin, e y es and respir ator y system. A. Shut down burner by disconnecting all electrical power to the burner ...

Produzent Slant/Fin Kategorie Boiler

Dokumente, die wir vom Produzenten des Geräts Slant/Fin BOILERS erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Slant/Fin
- Bedienungsanleitungen BOILERS
- Produktkarten Slant/Fin
- Informationsbroschüren
- oder Energieetiketten Slant/Fin BOILERS
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Slant/Fin BOILERS.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Slant/Fin BOILERS, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Slant/Fin BOILERS. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Slant/Fin BOILERS ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Slant/Fin BOILERS, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Slant/Fin BOILERS hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Slant/Fin BOILERS verständlich ist.

Eine gänzliche Bedienungsanleitung von Slant/Fin sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Slant/Fin BOILERS bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Slant/Fin BOILERS befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Slant/Fin BOILERS, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Slant/Fin BOILERS - die uns die ersten Schritte während der Nutzung von Slant/Fin BOILERS erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Slant/Fin BOILERS hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Slant/Fin BOILERS im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Slant/Fin BOILERS?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Slant/Fin BOILERS nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Slant/Fin BOILERS hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)