Bedienungsanleitung Mitsubishi MSZ-GF60VE-E1

42 Seiten Betrifft nicht
Download

Zur Seite of 42

Summary
  • Mitsubishi MSZ-GF60VE-E1 - page 1

    SER VICE MANUAL CONTENTS 1. TECHNICAL CHANGES ··································· 3 2. P ART NAMES AND FUNCTIONS ····················· 4 3. SPECIFICA TION ················································ 5 4. NOISE CRITERIA CURVES ·······? ...

  • Mitsubishi MSZ-GF60VE-E1 - page 2

    2 Use the speci fi ed refrigerant only Never use any refrigerant other than that specified. Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failur ...

  • Mitsubishi MSZ-GF60VE-E1 - page 3

    3 MUZ-GF60VE - E1 MUZ-GF71VE - E1 1. New model TECHNICAL CHANGES 1 OBH635 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 4

    4 P ART NAMES AND FUNCTIONS 2 ACCESSORIES Model MUZ-GF60/71VE Drain socket 1 MUZ-GF60VE MUZ-GF71VE Piping Air outlet Drain outlet Air inlet (back and side) Drain hose OBH635 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 5

    5 SPECIFICA TION 3 Outdoor model MUZ-GF60VE MUZ-GF71VE Power supply Single phase, 230 V , 50 Hz Capacity Rated frequency (Min. - Max.) Cooling kW 6.1 (1.4 - 7.5) 7.1 (2.0 - 8.7) Heating 6.8 (2.0 - 9.3) 8.1 (2.2 - 9.9) Breaker Capacity A 20 Electrical data Power input 1 (T otal) Cooling W 1,790 2,130 Heating 1,810 2,230 Running current 1 (T otal) Co ...

  • Mitsubishi MSZ-GF60VE-E1 - page 6

    6 Speci fi cations and rated conditions of main electric parts Model Item MUZ-GF60VE MUZ-GF71VE Smoothing capacitor (CB1, CB2, CB3) 560 μ F 450 V Fuse (F601, F880, F901) T3.15AL250 V IGBT module (IC932) 5 A 600 V (IC700) 20 A 600 V Expansion valve coil (LEV) 12 V DC Reactor (L) 340 μ H Diode module (IC820) 20 A 600 V Circuit protection (PTC64, P ...

  • Mitsubishi MSZ-GF60VE-E1 - page 7

    7 NOISE CRITERIA CUR VES 4 MUZ-GF60VE MUZ-GF71VE T est conditions Cooling: Dry-bulb temperature 35°C Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C OUTDOOR UNIT MICROPHONE 1 m 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 NC-60 NC-50 NC-40 NC-30 NC-20 NC-70 OCT A VE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR B ...

  • Mitsubishi MSZ-GF60VE-E1 - page 8

    8 Unit: mm OUTLINES AND DIMENSIONS 5 MUZ-GF60VE MUZ-GF71VE 417.5 40 42 Drain hole 175 500 330 50 Air in Air out 2-holes 10 21 360 840 109 81 880 452 Service panel 99.5 164.5 195 35 44 Liquid refrigerant pipe joint Refrigerant pipe (flared) Ø 6.35 ( MUZ-GF60VE ) Ø 9.52 ( MUZ-GF71VE ) Gas refrigerant pipe joint Refrigerant pipe (flared) Ø 15.88 35 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 9

    9 WIRING DIAGRAM 6 MUZ-GF60VE MUZ-GF71VE OBH635 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 10

    10 REFRIGERANT SYSTEM DIAGRAM 7 MUZ-GF60VE Unit: mm Outdoor heat exchanger Flared connection Defrost thermistor RT6 1 Discharge temperature thermistor RT6 2 Flared connection Stop valve Stop valve (with service port) Capillary tube ø 4.0 × ø 2.4 × 100 Refrigerant flow in cooling Compressor 4-way valve Refrigerant flow in heating Refrigerant pip ...

  • Mitsubishi MSZ-GF60VE-E1 - page 11

    11 Max. Length A Max. Height difference B Indoor unit Outdoor unit MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE Refrigerant piping: m Piping size O.D: mm Max. Length A Max. Height difference B Gas Liquid MUZ-GF60 30 15 15.88 6.35 MUZ-GF71 9.52 ADDITIONAL REFRIGERANT CHARGE (R410A: g) Model Outdoor unit precharged Refrigerant piping len ...

  • Mitsubishi MSZ-GF60VE-E1 - page 12

    12 The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi- tions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the perform ...

  • Mitsubishi MSZ-GF60VE-E1 - page 13

    13 NOTE: The above broken lines are for the heating operation without any frost and defrost operation. 0.8 0.9 1.0 1.1 1.2 1.3 - 1 0 - 5 0 5 1 01 52 02 53 03 54 04 5 Outdoor intake air Dry-bulb temperature (°C) Input correction factors 26 24 22 20 18 Indoor intake air Wet-bulb temperature( ) Indoor air Wet-bulb temperature difference (°C) 7.9 7.2 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 14

    14 8-2. CAP ACITY AND INPUT CORRECTION BY OPERA TIONAL FREQUENCY OF COMPRESSOR Correction of Cooling capacity Capacity correction factors Correction of Cooling input Input correction factors Correction of Heating capacity Capacity correction factors MUZ-GF60VE Correction of Heating input Capacity correction factors Correction of Cooling capacity Ca ...

  • Mitsubishi MSZ-GF60VE-E1 - page 15

    15 15 20 50 25 60 30 70 35 4.0 5.0 6.0 7.0 8.0 9.0 15 20 50 25 60 30 70 35 4.0 5.0 6.0 7.0 8.0 9.0 MUZ-GF60VE MUZ-GF71VE Ambient temperature(°C) Ambient humidity(%) Am bient temperature ( °C) Amb ien t h umid it y(% ) O ut door current ( A) O ut door current ( A) Outdoor unit current 0 5 10 15 20 25 3.0 3.5 4.0 4.5 5.0 5.5 0 5 10 15 20 25 6 8 10 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 16

    16 PERFORMANCE DA T A COOL operation a t Rated frequency MUZ-GF60VE CAP ACITY : 6.1 kW SHF: 0.79 INPUT : 1790 W INDOOR DB (°C) INDOOR WB (°C) OUTDOOR DB (°C) 21 25 27 30 Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 7.17 4.37 0.61 1432 6.86 4.19 0.61 1504 6.59 4.02 0.61 1575 6.34 3.87 0.61 1647 21 20 7.47 3.66 0.49 1504 7 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 17

    17 PERFORMANCE DA T A COOL operation a t Rated frequency MUZ-GF60VE CAP ACITY : 6.1 kW SHF: 0.79 INPUT : 1790 W INDOOR DB (°C) INDOOR WB (°C) OUTDOOR DB (°C) 35 40 46 Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 5.98 3.65 0.61 1754 5.49 3.35 0.61 1862 5.06 3.09 0.61 1933 21 20 6.28 3.08 0.49 1826 5.86 2.87 0.49 1915 5.43 2.66 0.49 2023 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 18

    18 PERFORMANCE DA T A COOL operation a t Rated frequency MUZ-GF71VE CAP ACITY : 7.1 kW SHF: 0.78 INPUT : 2130 W INDOOR DB (°C) INDOOR WB (°C) OUTDOOR DB (°C) 21 25 27 30 Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 8.34 5.01 0.60 1704 7.99 4.79 0.60 1789 7.67 4.60 0.60 1874 7.38 4.43 0.60 1960 21 20 8.70 4.17 0.48 1789 8 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 19

    19 PERFORMANCE DA T A COOL operation a t Rated frequency MUZ-GF71VE CAP ACITY : 7.1 kW SHF: 0.78 INPUT : 2130 W INDOOR DB (°C) INDOOR WB (°C) OUTDOOR DB (°C) 35 40 46 Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 6.96 4.17 0.60 2087 6.39 3.83 0.60 2215 5.89 3.54 0.60 2300 21 20 7.31 3.51 0.48 2173 6.82 3.27 0.48 2279 6.32 3.03 0.48 2407 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 20

    20 PERFORMANCE DA T A HEA T operation at Rated frequency MUZ-GF60VE CAP ACITY : 6.8 kW INPUT : 1810 W INDOOR DB (°C) OUTDOOR WB (°C) -10 -5 0 5 10 15 20 Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 4.28 1 177 5.17 1412 6.05 1593 6.94 1720 7.82 1828 8.64 1882 9.52 1919 21 4.08 1267 4.90 1502 5.78 1665 6.60 1792 7.48 1882 8.30 1937 9. ...

  • Mitsubishi MSZ-GF60VE-E1 - page 21

    21 MUZ-GF60VE MUZ-GF71VE 9-2. R.V . COIL CONTROL Heating . . . . . . . . . . . . . . . . . ON Cooling . . . . . . . . . . . . . . . . . OFF Dry . . . . . . . . . . . . . . . . . . . . OFF NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor . ON OFF ON OFF Outdoor fan motor Compressor 5 seconds 15 seconds ON OFF Comp ...

  • Mitsubishi MSZ-GF60VE-E1 - page 22

    22 10-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature <JS> T o change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P .C. board. (Refer to 1 1-6-1.) Jumper wire Defrost fi nish temperature ( °C ) MUZ-GF 60VE 71VE JS Soldered (Initial setting) 10 10 None (Cut) 18 18 10-2. PRE-HEA T CONTROL SE ...

  • Mitsubishi MSZ-GF60VE-E1 - page 23

    23 Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (1 1-3.) disappears, the memorized failure details can be r ecalled. 1 1-2. F AILURE MODE RECALL FUNCTION 1. Flow chart of failure mode recall function for the indoor/outdo ...

  • Mitsubishi MSZ-GF60VE-E1 - page 24

    24 2. Flow chart of the detailed outdoor unit failure mode recall function 2.Blinking pattern when outdoor unit is abnormal: ON OFF No beep Beeps Repeated cycle 2.5-second OFF 3-second ON Blinking at 0.5- second interval No beep Beeps Repeated cycle 2.5-second OFF 3-second ON Blinking at 0.5- second interval Repeated cycle Does the upper lamp of OP ...

  • Mitsubishi MSZ-GF60VE-E1 - page 25

    25 3. Outdoor unit failure mode table The upper lamp of OPERA TION INDICA TOR lamp (Indoor unit) Abnormal point (Failure mode / protection) LED indication (Outdoor P .C. board) Condition Remedy Indoor/outdoor unit failure mode recall function Outdoor unit failure mode recall function OFF None (Normal) —— — — — 1-time fl ash 2.5 seconds O ...

  • Mitsubishi MSZ-GF60VE-E1 - page 26

    1 1-3. TROUBLESHOOTING CHECK T ABLE No. Symptom LED indication Abnormal point/ Condition Condition Remedy 1 Outdoor unit does not op- erate. 1-time fl ash every 2.5 seconds Outdoor power sys- tem Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started. Reconnect connector of compres- sor . Refe ...

  • Mitsubishi MSZ-GF60VE-E1 - page 27

    No. Symptom LED indication Abnormal point/ Condition Condition Remedy 19 Outdoor unit operates. 8-time fl ash 2.5 seconds OFF Zero cross detecting circuit Zero cross signal cannot be detected. It occurs with following cases. 1 Instantaneous power voltage drop. (Short time power failure) 2 Distortion of primary voltage Refer to 1 1-5. "Check o ...

  • Mitsubishi MSZ-GF60VE-E1 - page 28

    28 1 1-5. TROUBLESHOOTING FLOW Are the voltages balanced? Disconnect the connector between compressor and the IGBT module (IC700). Replace the inverter P .C. board. Check the voltage between terminals. Check the compressor . See 1 1-5. “Check of compressor”. No Ye s See 1 1-5. “Check of open phase”. A How to check inverter/compressor Refer ...

  • Mitsubishi MSZ-GF60VE-E1 - page 29

    29 F Check of compressor start failure D Check of compressor winding E Check of compressor operation time ● Disconnect the connector between the compressor and the IGBT module (IC700), and measure the resistance between the compressor terminals. <<Measurement point>> At 3 points BLK-WHT BLK-RED WHT -RED <<Judgement>> Refer ...

  • Mitsubishi MSZ-GF60VE-E1 - page 30

    30 G Check of outdoor thermistors H Check of R.V . coil Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P .C. board. Replace the inverter P .C. board. No No Is the resistance of thermistor normal? (Refer to 1 1-6.1.) Reconnect the connector of thermistor . T urn ON the power supply and press EMERGENCY OPERA TION swit ...

  • Mitsubishi MSZ-GF60VE-E1 - page 31

    31 I Check of outdoor fan motor Is the resistance between each ter- minal of outdoor fan motor normal? (Refer to 1 1-4.) Disconnect CN932 from the inverter P .C. board, and turn on the power supply . Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-) Does the vol ...

  • Mitsubishi MSZ-GF60VE-E1 - page 32

    32 J Check of power supply Is there voltage 230 V AC between the indoor terminal block S1 and S2? No Ye s Replace the indoor electronic control P .C. board. Rectify indoor/outdoor connecting wire. Ye s If light up, OK. If fl ash, refer to 1 1-3. Does the upper lamp of OPERA TION INDICA TOR on the indoor unit light up? Does LED on the inverter P .C ...

  • Mitsubishi MSZ-GF60VE-E1 - page 33

    33 Press OPERA TE/ST OP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1 Expansion valve operates in full-opening direction. OK NOTE : After check of LEV , do the undermentioned operations. 1. T urn OFF the power supply and turn it ON again. 2. Press RESET butto ...

  • Mitsubishi MSZ-GF60VE-E1 - page 34

    34 Check the outdoor fan motor . (Refer to 1 1-5. .) Is the fuse (F901) blown on the in- verter P .C. board? Check the connection of the connectors (CN931, CN932) of the outdoor fan motor . If the connection is poor , make it correct. Operate the outdoor unit by starting EMERGENCY OPERA TION. Check the LED indication on the inverter P .C. board. Do ...

  • Mitsubishi MSZ-GF60VE-E1 - page 35

    35 M How to check miswiring and serial signal error T urn the power supply OFF . Is there rated voltage in the power supply? Ye s No Check for incorrect indoor-outdoor connecting wiring. Check the power supply . A Is there rated voltage between outdoor terminal block S1 and S2? Check for miswiring, broken wires, and loose wire connection between th ...

  • Mitsubishi MSZ-GF60VE-E1 - page 36

    36 N Electromagnetic noise enters into TV sets or radios Ye s Is the unit earthed? No Earth the unit. Ye s Is the distance between the antennas and the indoor unit within 3 m, or is the distance between the antennas and the outdoor unit within 3 m? No Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor ...

  • Mitsubishi MSZ-GF60VE-E1 - page 37

    37 1. Inverter P .C. board 1 1-6. TEST POINT DIAGRAM AND VOL T AGE MUZ-GF60VE MUZ-GF71VE -20 -10 0 10 20 30 40 0 10 20 30 40 50 60 70 80 90 100 T emperature( ) Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68) T emperature( ) Discharge temperature thermistor(RT62) 0 1 02 03 04 05 06 07 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 38

    38 2. Relay P .C. board MUZ-GF60VE MUZ-GF71VE T o inverter P .C. board CN681 (CN680) CN60 L68B(-) L68A(+) 10 VDC OBH635 ...

  • Mitsubishi MSZ-GF60VE-E1 - page 39

    39 12-1. MUZ-GF60VE MUZ-GF71VE NOTE: T urn OFF power supply before disassembly . OPERA TING PROCEDURE PHOTOS 1. Removing the cabinet (1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover . (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover . (7) Di ...

  • Mitsubishi MSZ-GF60VE-E1 - page 40

    OPERA TING PROCEDURE PHOTOS 2. Removing the inverter assembly , inverter P .C. board and relay P .C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con- nectors: <Inverter P .C. board> CN602 (R.V . coil) CN931, CN932 (Fan motor) CN671 (Defrost thermistor , discharge tempera ...

  • Mitsubishi MSZ-GF60VE-E1 - page 41

    OPERA TING PROCEDURE PHOTOS 4. Removing the discharge temperature thermistor , defrost thermistor , outdoor heat exchanger tempera- ture thermistor and ambient temperature thermistor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P .C. board> CN671 (Defrost ...

  • Mitsubishi MSZ-GF60VE-E1 - page 42

    © Copyright 2013 MITSUBISHI ELECTRIC CORPORA TION Distributed in Mar . 2013. No. OBH635 Made in Japan New publication, effective Mar . 2013 Specifications are subject to change without notice. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAP AN ...

Produzent Mitsubishi Kategorie Air-conditioning

Dokumente, die wir vom Produzenten des Geräts Mitsubishi MSZ-GF60VE-E1 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Mitsubishi
- Bedienungsanleitungen MSZ-GF60VE-E1
- Produktkarten Mitsubishi
- Informationsbroschüren
- oder Energieetiketten Mitsubishi MSZ-GF60VE-E1
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Mitsubishi MSZ-GF60VE-E1.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Mitsubishi MSZ-GF60VE-E1, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Mitsubishi MSZ-GF60VE-E1. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Mitsubishi MSZ-GF60VE-E1 ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Mitsubishi MSZ-GF60VE-E1, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Mitsubishi MSZ-GF60VE-E1 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Mitsubishi MSZ-GF60VE-E1 verständlich ist.

Eine gänzliche Bedienungsanleitung von Mitsubishi sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Mitsubishi MSZ-GF60VE-E1 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Mitsubishi MSZ-GF60VE-E1 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Mitsubishi MSZ-GF60VE-E1, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Mitsubishi MSZ-GF60VE-E1 - die uns die ersten Schritte während der Nutzung von Mitsubishi MSZ-GF60VE-E1 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Mitsubishi MSZ-GF60VE-E1 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Mitsubishi MSZ-GF60VE-E1 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Mitsubishi MSZ-GF60VE-E1?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Mitsubishi MSZ-GF60VE-E1 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Mitsubishi MSZ-GF60VE-E1 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)