    Ser vice Manual W allMaster ® Thru-the-W all WM-ServMan (04-09) Wa i t th r e e m i n u tes be for e r es t a rt in g Wa r m e r Coo l e r F an O n ly Low H e a t Me d H e a t Hi g h H eat Lo w C oo l M e d C oo l H i g h C oo l M O DE TE M P E R A T U R E 72 Models 2009 2008 M o n ey F a n T im e r O p e r a ti o n S e tH r . S t o p S t a r t Te ...

  • Friedrich 2008 - page 2

    FRIEDRICH AIR CONDITIONING CO . Post Ofce Box 1540 · San Antonio, T exas 78295-1540 4200 N. Pan Am Expressway · San Antonio, T exas 78218-5212 (210) 357-4400 · F AX (210) 357-4490 www .friedrich.com Printed in the U.S.A. TECHNICAL SUPPORT CONT ACT INFORMA TION ...

  • Friedrich 2008 - page 3

    T able Of Contents Important Safety Information ....................................................................................................................2-4 Introduction ..................................................................................................................................................4 WallMaster Model Numb ...

  • Friedrich 2008 - page 4

    IMPORT ANT SAFETY INFORMA TION The information contained in this manual is intended for use by a qualied service technician who is familiar with the safety procedures required for installation and repair , and who is equipped with the proper tools and test instruments required to service this product. Installation or repairs made by unqualied ...

  • Friedrich 2008 - page 5

    Do not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel, • and sleeve on the room side of the air conditioning unit while cleaning. Electrical component malfunction caused by water could result in electric shock or other electrically • unsafe conditions when the power is restored and the u ...

  • Friedrich 2008 - page 6

    PROPERTY DAMAGE HAZARDS FIRE DAMAGE HAZARDS: Read the Installation/Operation Manual for this air conditioning unit prior to operating. • Use air conditioner on a single dedicated circuit within the specied amperage rating. • Connect to a properly grounded outlet only . • Do not remove ground prong of plug. • Do not cut or mod ...

  • Friedrich 2008 - page 7

    5 FRIEDRICH WALLMASTER MODE L NUMB ER CODE W S 08 B 1 0 B 1st DIGIT - FUNCTION W = Thru-The-W all, W allMaster Series 2nd DIGIT - TYPE S = Straight Cool E = Electric Heat Y = Heat Pump 3rd & 4th DIGITS - APPROXIMA TE BTU/HR (Cooling) Heating BTU/HR capacity listed in Specications/Performance Data Section 5th DIGIT - ALPHABETICAL MODIFIER 6th ...

  • Friedrich 2008 - page 8

    6 20 08 / 20 0 9 PERFORMA NCE DA T A * Rati ng C on diti on s: 80 d egr ees F , room ai r tem p. & 50% r elat ive hu midi t y , wit h 95 d eg ree F , outsi de air t emp & 4 0% re lat ive hum idi ty Model Hei ght Wi dt h Depth De pth wit h Fro nt Mi nim um Ex te ns io n Int o Roo m Mi nim um Ex te ns io n Outside Th ru -t he - wa ll Fin is h ...

  • Friedrich 2008 - page 9

    7 Wire Size Use O NL Y wir ing size rec ommende d for single out let branch c ircuit. F use/Circuit B reaker Use ON L Y the cor rec t HACR type and size fuse/circuit breaker . Read elec tr ical ratings on unit ’ s r ating plate. Proper circ uit protecti on is the re sponsibiit y of the h omeowne r . Grounding Unit M UST be grounde d from bra nch ...

  • Friedrich 2008 - page 10

    F U N C TI O NA L CO MP O NE NT S A . Me c ha ni ca l c o m p onen ts Drain pan valve T em p er atur e- sensi tiv e v a lv e t hat o p ens u p to dr ain o ff co nden s a te w a ter wh en t he ou tsi de te m p er at ur e f all s below 40 °F and c lo se s wh en th e ou ts id e tem p e r ature rea ch e s 60 ° F Pl e num a s sem bl y y D i ffus e r w ...

  • Friedrich 2008 - page 11

    Ho w to o p e ra te t h e Fr iedric h W allMaster Figure 1: WS Model cool-only control panel Figure 2: WY/WE Model heat-cool control panel 1 Power 2 3 4 8 Cool Fan Smart 9 Fan Only 6 Mode Speed Fan Heat 7 Clock 5 Timer Set Money Start Time 14 On/Off Saver Stop Time 13 T emp/Hour 10 1 1 12 To s ta rt uni t , e l c a t p e c e r r e p o r p a o t n i ...

  • Friedrich 2008 - page 12

    To s e t t h e t i m e r NOTE : Se t the HOUR C LO CK ( S et Hour ) before a tt emp ting to s et timer f uncti ons. Yo u ca n set the Star t Time and Stop T im e a m inimum o f one hour apa rt , and a m ax imu m of 23 h ou rs apa rt . 11 Af ter se tt ing the time , press the Set Hour b ut ton on ce ( Star t ligh t on ). Use t he and e h t t a h t e ...

  • Friedrich 2008 - page 13

    Fi gure 3 : WY /W E heat -c oo l mo del r em ot e con tr o l Additional R C1 w irele ss re mote c on trol s ca n be p ur cha sed f rom yo ur F ried ri ch d eale r. Fi gure 4 : WS M o de l s O n l y Additional R C1 w irele ss re mote c on trol s ca n be p ur cha sed f rom yo ur F ried ri ch d eale r. Usin g th e r em ot e c o n tr ol To s ta rt u n ...

  • Friedrich 2008 - page 14

    ELECTR ONIC CONTROL P ANEL CHECKING ROOM TEMPERA TURE 1. C h ec k th e ro om te m pe r at u r e a t the el ec tr o ni c con t ro l pad by pressing at the same time, the F an S pe ed button and t he T emp /Hour b u tt o n o n the WS/ WE / W Y m odels (see gures 5 and 6) . 2. Th e ind o or te m pe r at u r e wi l l d is p la y fo r 1 0 sec on d s. ...

  • Friedrich 2008 - page 15

    ERR OR CODES LISTING FOR “WS” MODELS E 1 SHOR T CY CLE S ITUA TI ON: De n e d as a co mp r es so r th a t st arts an d st o ps mor e fr eq u en t l y th a n i t s h ou l d . E2 K E YBOARD STUCK ERROR: If an y ke y bu tt on is st u ck or pr e ss ed fo r 20 se con d s or mor e , the u ni t con s id e rs it st u ck . If a k e y is st u ck it wi ...

  • Friedrich 2008 - page 16

    Figure 8: System Control Switch (Heat Pump & Electric Heat Models) Fan Only Off Low Cool Low Heat Med Cool Med Heat High Heat High Cool MAX HEAT MAX COOL ! Allow 3 min. between restarts SYSTEM CONTROL SWITCH - TEST Disconnect leads from control switch. T urn control to position being tested (see Figure 8). There must be continuity as follows: 1 ...

  • Friedrich 2008 - page 17

    15 ELECTR ONIC CONTROL OPERA TION Heat Pump w/back up Electric Heat If t he in door ambient air themi ster re ads 5 5 degrees, turn of f t he co mpress or and tur n on the ele ctr ic heat and continu e fan operati on until temp s ettin g is satis ed. The n rev er t to st andard heat pump ope ration. If the c ompres sor is ti me delayed : 1 . T u ...

  • Friedrich 2008 - page 18

    16 CAP ACIT ORS ELECTRIC SHOCK HAZARD W ARNING T urn off electric power before servicing. Discharge capacitor with a 20,000 Ohm 2 W att resistor before handling. Failure to do so may result in personal injury , or death. Many motor capacitors are internally fused. Shorting the terminals will blow the fuse, ruining the capacitor . A 20,000 ohm 2 wat ...

  • Friedrich 2008 - page 19

    17 DRAIN P AN V AL VE During the cooling mode of operation, condensate which collects in the drain pan is picked up by the condenser fan blade and sprayed onto the condenser coil. This as - sists in cooling the refrigerant plus evaporating the water . During the heating mode of operation, it is necessary that water be removed to prevent it from fre ...

  • Friedrich 2008 - page 20

    Suction Line Evaporator Coil Metering Device Refrigerant Strainer Discharge Line Condenser Coil Compressor Refrigerant Drier Liquid Line A good understanding of the basic operation of the refrigeration system is essential for the service technician. Without this understanding, accurate troubleshooting of refrigeration system problems will be more d ...

  • Friedrich 2008 - page 21

    R efrigerant Char ging NOTE: Because The W allMaster System Is A Sealed System, Service Process T ubes Will Have T o Be Installed. First Install A Line T ap And Remove Refrigerant From System. Make Necessary Sealed System Repairs And V acuum System. Crimp Process T ube Line And Solder End Shut. Do Not Leave A Service V alve In The Sealed System. Pr ...

  • Friedrich 2008 - page 22

    3. Install a process tube to sealed system. 4. Make necessary repairs to system. 5. Evacuate system to 300 microns or less. 6. Weigh in refrigerant with the property quantity of R-22 refrigerant. 7. Start unit, and verify performance. 8. Crimp the process tube and solder the end shut. Proper safety procedures must be followed, and proper protective ...

  • Friedrich 2008 - page 23

    Underchar ged R efriger ant Systems An undercharged system will result in poor performance (low pressures, etc.) in both the heating and cooling cycle. Whenever you service a unit with an undercharge of refrigerant, always suspect a leak. The leak must be repaired before charging the unit. T o check for an undercharged system, turn the unit on, all ...

  • Friedrich 2008 - page 24

    R estricted Refrigerant System T roubleshooting a restricted refrigerant system can be difcult. The following procedures are the more common problems and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions. A partial restriction allows some of the refrigerant to circulate t ...

  • Friedrich 2008 - page 25

    METERING DEVICE Capillar y T ube Systems All units are equipped with capillary tube metering devices. Checking for restricted capillary tubes. 1. Connect pressure gauges to unit. 2. Start the unit in the cooling mode. If after a few minutes of operation the pressures are normal, the check valve and the cooling capillary are not restricted. 3. Switc ...

  • Friedrich 2008 - page 26

    NOTE: System operating pressures must be near normal before valve can shift . REVERSING V AL VE DESCRIPTION/OPERA TION The Reversing V alve controls the direction of refrigerant ow to the indoor and outdoor coils. It consists of a pressure-operated, main valve and a pilot valve actuated by a solenoid plunger . The solenoid is energized during th ...

  • Friedrich 2008 - page 27

    Reversing V alve in Heating Mode TESTING THE COIL The solenoid coil is an electromagnetic type coil mounted on the reversing valve and is energized during the operation of the compressor in the heating cycle. 1. T urn of f high voltage electrical power to unit. 2. Unplug line voltage lead from reversing valve coil. 3. Check for electrical continuit ...

  • Friedrich 2008 - page 28

    8. Pressurize sealed system with a combination of R-22 and nitrogen and check for leaks, using a suitable leak detector . Recover refrigerant per EP A guidelines. 9. Once the sealed system is leak free, install solenoid coil on new valve and charge the sealed system by weighing in the proper amount and type of refrigerant as shown on rating plate. ...

  • Friedrich 2008 - page 29

    Lock ed Rotor V olta ge (L.R.V .) T est Locked rotor voltage (L.R.V .) is the actual voltage available at the compressor under a stalled condition. Single Phase Connections Disconnect power from unit. Using a voltmeter , attach one lead of the meter to the run “R” terminal on the compressor and the other lead to the common “C” terminal of t ...

  • Friedrich 2008 - page 30

    Single Phase Resistance T est Remove the leads from the compressor terminals and set the ohmmeter on the lowest scale (R x 1). T ouch the leads of the ohmmeter from terminals common to start (“C” to “S”). Next, touch the leads of the ohmmeter from terminals common to run (“C” to “R”). Add values “C” to “S” and “C” to “ ...

  • Friedrich 2008 - page 31

    R ecommended procedur e for compr essor replacement 1. Be certain to perform all necessary electrical and refrigeration tests to be sure the compressor is actually defective before replacing. 2. Recover all refrigerant from the system though the process tubes. PROPER HANDLING OF RECOVERED REFRIGERANT ACCORDING TO EP A REGULA TIONS IS REQUIRED. Do n ...

  • Friedrich 2008 - page 32

    1. 2. 3. 4. 5. ELECTRIC SHOCK HAZARD W ARNING T urn off electric power before service or installation. Failure to do so may result in personal injury , or death. S e a l e d R e f r i ge r a ti o n Sy s te m c o n t a i n s r e f r i g e r an t and oil under high pressure. Proper safety procedures must be followed, and proper protective clothing mu ...

  • Friedrich 2008 - page 33

    R OUTINE MAINTENANCE AIR FIL TER Clean the unit air intake lter at least every 300 to 350 hours of operation. Clean the lters with a mild detergent in warm water and allow to dry thoroughly before reinstalling. Units are to be inspected and serviced by qualied service personnel only . Use proper protection on surrounding property . Failure ...

  • Friedrich 2008 - page 34

    Return Air Grille Decorative Front WSC Sleeve AB123456C3567 MODEL# WS07A10B Airflow Rotate D ischarge G rille 1" Diam eter Pl ug 1” Diameter Plug SLEEVE / DRAIN Inspect the sleeve and drain system periodically (at least yearly or bi-yearly) and clean of all obstructions and debris. Clean both areas with an antibacterial and antifungal cleane ...

  • Friedrich 2008 - page 35

    33 COOLING ONL Y ROOM AIR CONDITIONERS: TR OUBLESHOO TING TIPS n o i t c A e s u a C e l b i s s o P m e l b o r P Compressor does not run Low voltage Check voltage at compressor . 1 15V & 230V units will operate at 10% voltage variance T -stat not set cold enough or inoperative Set t-stat to coldest position. T est t-stat & re- place if in ...

  • Friedrich 2008 - page 36

    n o i t c A e s u a C e l b i s s o P m e l b o r P Unit does not run Fuse blown or circuit tripped Replace fuse, reset breaker . If repeats, check fuse or breaker size. Check for shorts in unit wiring & components Power cord not plugged in Plug it in System switch in “OFF” position Set switch correctly Inoperative system switch or open con ...

  • Friedrich 2008 - page 37

    35 n o i t c A e s u a C e l b i s s o P m e l b o r P Compressor runs for short periods only . Cycles on overload Overload inoperative. Opens too soon Check operation of unit. Replace overload if system operation is satisfactory Compressor restarted before system pressures equalized Allow a minimum of 2 minutes to allow pressures to equalize befor ...

  • Friedrich 2008 - page 38

    Problem Possible Cause Action W ater “spitting” into room Sublimation: When unconditioned saturated, outside air mixes with conditioned air , condensation forms on the cooler surfaces Ensure that foam gaskets are installed in between window panes & in between the unit & the sleeve. Also, ensure that fresh air/exhaust vents (on applicabl ...

  • Friedrich 2008 - page 39

    37 Problem Possible Cause Action Room temperature uneven (Heating cycle) Heat anticipator (resistor) shorted (on applicable models) Disconnect power to unit. Remove resistor from t-stat bulb block. Plus in unit & allow to operate. Feel resistor for heat. If not heat, replace resistor Wide differential - partial loss of t-stat bulb charge Replac ...

  • Friedrich 2008 - page 40

    38 n o i t c A e s u a C e l b i s s o P m e l b o r P Unit cools when heat is called for Incorrect wiring Refer to applicable wiring diagram Defective solenoid coil Check for continuity of coil Reversing valve fails to shift Block condenser coil & switch unit to cooling. Allow pressure to build up in system, then switch to heating. If valve fa ...

  • Friedrich 2008 - page 41

    DISCHARGE TUBE SUCTION TUBE to T ube to OUTSIDE from Compressor T ube to INSIDE Capillary T ube Capillary T ube Compressor RIGHT Pilot LEFT Pilot COIL COIL 14 NORMAL FUNCTION OF V AL VE V AL VE OPERA TING DISCHARGE TUBE from Compressor SUCTION TUBE to Compressor Tube to INSIDE COIL Tube to OUTSIDE COIL LEFT Pilot Capillary Tube RIGHT Pilot Capillar ...

  • Friedrich 2008 - page 42

    WALLMASTER WIRING DIA GRAM ELECTR ONIC CONTROL COOL ONL Y MODELS: WS08B10A-D,A-F WS10BIO A-D WS14B10A-D WS14B10A-E WS10B30A-D WS13B30B-E,B-F WS16B30A-D,A-E 40 ...

  • Friedrich 2008 - page 43

    WALLMASTER WIRING DIA GRAM ELECTR ONIC CONTROL COOL WITH ELECTRIC HEA T MODELS: WE10B33C-A WE13B33C-A WE16B33C-A 41 ...

  • Friedrich 2008 - page 44

    WALLMASTER WIRING DIA GRAM ELECTR ONIC CONTROL HEA T PUMP WITH ELECTRIC HEA T MODELS: WY10B33C-A WY13B33C-A 42 ...

  • Friedrich 2008 - page 45

    43 WALLMASTER WIRING DIA GRAM ELECTR OMECHANICAL CONTROL COOL WITH ELECTRIC HEA T MODELS: WE10B33A-C WE13B33B-D,B-E WE16B33A-C ,A-D ...

  • Friedrich 2008 - page 46

    44 WALLMASTER WIRING DIA GRAM ELECTR OMECHANICAL CONTROL HEA T PUMP WITH ELECTRIC HEA T MODELS: WY10B33A-C ,A-D WY13B33A-C ,A-D ...

  • Friedrich 2008 - page 47

    DK / Drain Ki t In st alle d at the ba ck of the unit and allows for at tachme nt to pe rmanen t co ndensa te disp os al sy st em, if disp osal is ne ce ssar y or desi re d. SB / Sub Base Us ed as a base for the unit when it is desi re d to plac e the co rd and re ce ptacle within the in st allation, or simp ly as a ba se for the unit when moun te ...

  • Friedrich 2008 - page 48

    FIGURE 1 MINIMUM OF 24” REQUIRED FROM TOP OF UNIT TO CEILING. INSIDE W ALL MINIMUM OF 1” SP ACING REQUIRED ON ALL SIDES OF LINTELS WSC SLEEVE DRAIN EXTENSION THE UNIT . 7/8” MINIMUM 1” MINIMUM 3 1/2” FOR SUBBASE 9/16” MINIMUM OUTSIDE W ALL INST ALLA TION INSTRUCTIONS FOR “WSC” SLEEVE MOUNTING HARDW ARE PROVIDED W ALL PREP ARA TION: ...

  • Friedrich 2008 - page 49

    FIGURE 2 BACK UNIT REST LEVEL FRONT UNIT REST RAISED LEDGE INST ALLA TION REQUIREMENTS: STEP 1 The “WSC” SLEEVE should be positioned so that the DRAIN EXTENSION extends a minimum of 9/16” beyond the OUTSIDE W ALL (See Figure 1). STEP 2 The “WSC” SLEEVE must extend a minimum of 7/8” beyond the INSIDE W ALL. STEP 3 The “WSC” SLEEVE mu ...

  • Friedrich 2008 - page 50

    48 MECHANICAL HAZARD W ARNING Be careful with the sharp edges and corners. Wear protective clothing and gloves, etc. Failure to do so could result in serious injury . CUT/SEVER HAZARD ...

  • Friedrich 2008 - page 51

    49 FIGURE A AIR DISCHARGE PLENUM FIGURE B SIDE PROFILE OF W ALL SLEEVE RAISED LEDGE GASKET FRONT UNIT REST Remove the black rubber gasket from the air discharge plenum of the air conditioner (see fi g. A). Look inside the wall sleeve and check to see if a black rubber gasket is already in place along the bottom front (see fi g. B). If one is not ...

  • Friedrich 2008 - page 52

    50 INST ALLA TION INSTRUCTIONS FOR INTERNAL DRAIN KIT (IDK) Apply Sealer to the bottom of the Drain Plate Drill a .625” diameter hole here Dimple W all Sleeve Sleeve Base 0.5” In from edge 4.75” From back of basepan Drill a .625” diameter hole in the bottom of the basepan 1. DRILL A .625” DIAMETER HOLE IN THE BOTTOM OF THE SLEEVE BASE TO ...

  • Friedrich 2008 - page 53

    51 51 MECHANICAL HAZARD W ARNING Be careful with the sharp edges and corners. Wear protective clothing and gloves, etc. Failure to do so could result in serious injury . CUT/SEVER HAZARD EXCESSIVE WEIGHT HAZARD W ARNING Use two people to lift or carry the unit, and wear proper protective clothing. Failure to do so may result in serious personal inj ...

  • Friedrich 2008 - page 54

    52 52 MECHANICAL HAZARD W ARNING Be careful with the sharp edges and corners. Wear protective clothing and gloves, etc. Failure to do so could result in serious injury . CUT/SEVER HAZARD ...

  • Friedrich 2008 - page 55

    53 53 MECHANICAL HAZARD W ARNING Be careful with the sharp edges and corners. Wear protective clothing and gloves, etc. Failure to do so could result in serious injury . CUT/SEVER HAZARD ...

  • Friedrich 2008 - page 56

    54 54 MECHANICAL HAZARD W ARNING Be careful with the sharp edges and corners. Wear protective clothing and gloves, etc. Failure to do so could result in serious injury . CUT/SEVER HAZARD ...

  • Friedrich 2008 - page 57

    55 Friedrich Air Conditioning Company P.O. Box 1540 San Antonio, TX 78295 210.357.4400 www .friedrich.com WALLMASTER ® THRU-THE-WALL AIR CONDITIONERS LIMITED WARRANTY FIRST YEAR A NY PART: If any part supplied by FRIEDRICH fails because of a defect in workmanship or material within twelve months from date of original purchase, FRIEDRICH will repai ...

  • Friedrich 2008 - page 58

    ...

  • Friedrich 2008 - page 59

    FRIEDRICH AIR CONDITIONING CO . Post Ofce Box 1540 · San Antonio, T exas 78295-1540 4200 N. Pan Am Expressway · San Antonio, T exas 78218-5212 (210) 357-4400 · F AX (210) 357-4490 www .friedrich.com Printed in the U.S.A. TECHNICAL SUPPORT CONT ACT INFORMA TION ...

  • Friedrich 2008 - page 60

    FRIEDRICH AIR CONDITIONING CO . Post Ofce Box 1540 · San Antonio, T exas 78295-1540 4200 N. Pan Am Expressway · San Antonio, T exas 78218-5212 (210) 357-4400 · F AX (210) 357-4490 www .friedrich.com Printed in the U.S.A. WM-ServMan (04-09) ...

Produzent Friedrich Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts Friedrich 2008 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Friedrich
- Bedienungsanleitungen 2008
- Produktkarten Friedrich
- Informationsbroschüren
- oder Energieetiketten Friedrich 2008
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Friedrich 2008.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Friedrich 2008, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Friedrich 2008. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Friedrich 2008 ansehen.

Die komplette Bedienungsanleitung des Geräts Friedrich 2008, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Friedrich 2008 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Friedrich 2008 verständlich ist.

Eine gänzliche Bedienungsanleitung von Friedrich sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Friedrich 2008 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Friedrich 2008 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Friedrich 2008, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Friedrich 2008 - die uns die ersten Schritte während der Nutzung von Friedrich 2008 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Friedrich 2008 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Friedrich 2008 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Friedrich 2008?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Friedrich 2008 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Friedrich 2008 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)