SR/SC Series "A" W oodburning Fireplace For Models: SC36A, SR36A SC42A, SR42A For use in U.S./Canada Underwriter's Laboratories Report No. MH6018 DO NOT DISCARD THIS MANUAL: Retain for future use. 948 SR cover 1 1/18/97 948 SC cover 1 1/18/97 7412948 7/08 Rev . 19 Homeowner's Installation and Operating Manual ...
-
Majestic SR42A - page 2
2 SR/SC Series "A" W oodb ur ning Fireplace 7412948 Safety Information PLEASE READ THIS MANUAL BEFORE INST ALLING AND USING FIREPLACE. IMPORT ANT : Read all instructions and warnings carefully before starting installation. Failure to follow these instructions may result in a possible fire hazard and will void the warranty . Description T ...
-
Majestic SR42A - page 3
3 SR/SC Series "A" W oodb ur ning Fireplace 7412948 5/8" (16mm) 1/2" (13mm) 1/2" 36" (914mm) 38 " (971mm) 40" (1016mm) 5/8" (16mm) 22 " (578mm) 1 " (45mm) 35 " (902mm) 24" (610mm) 7 " (197mm) 7 " (191mm) Recessed Na ...
-
Majestic SR42A - page 4
4 SR/SC Series "A" W oodb ur ning Fireplace 7412948 5/8" (16mm) 1/2" (13mm) 1/2" 42" (1067mm) 38 " (971mm) 46" (1 168mm) 5/8" (16mm) 22 " (578mm) 1 " (45mm) 38" (965mm) 24" (610mm) 7 " (197mm) 7 " (191mm) Recessed Nailing Fla ...
-
Majestic SR42A - page 5
5 SR/SC Series "A" W oodb ur ning Fireplace 7412948 Chase Installation Insulation methods shown are optional for cold climate, not a requirement for unit operation. FP554 Fig. 5 Fireplace and chase parts identification. FP554 BR/BC Combo of IWF261 AND IWF265 11/10/97 T ermination Cap Storm Collar Pan Flashing Draftstop Batt Insulation (c ...
-
Majestic SR42A - page 6
6 SR/SC Series "A" W oodb ur ning Fireplace 7412948 Chimney Requirements - Offset Installations 0 0 0 0 0 3" 1 1" 1 0 0 0 0 8 ¹⁄₄ " 20" 0 1 0 0 0 1 1 ¹⁄₄ " 25 ¹⁄₄ " 2 0 0 0 0 13 ¹⁄₂ " 29 ¹⁄₄ " 1 1 0 0 0 16 ¹⁄₂ " 34 ¹⁄₄ " 0 0 1 0 0 20 ¹⁄₄ " 40 ³ ...
-
Majestic SR42A - page 7
7 SR/SC Series "A" W oodb ur ning Fireplace 7412948 L 1 L 1 L T MODEL SK 2 W ALL CHIMNEY TOT AL LENGTH (L T ) INST ALLED LENGTH (L 1 ) SK81 SK818 SK83 SK84 1 1 " 17 " 35 " 47 " 10 " 16 " 34 " 46 " FP288 MBUF-INST ALLED L ...
-
Majestic SR42A - page 8
8 SR/SC Series "A" W oodb ur ning Fireplace 7412948 Insulating Fireplace Enclosure for Cold Climates If you live in a cold climate, it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible. Insulate base of fireplace with a noncombustible in - sulation rated fo ...
-
Majestic SR42A - page 9
9 SR/SC Series "A" W oodb ur ning Fireplace 7412948 Framing Framing can be constructed before or after the fireplace is set in place, however , most installers build the frame before setting the fireplace. Frame fireplace with 2 x 4 lumber or heavier materials. Refer to framing dimensions in Figures 1, 2, 3 or 4 for basic fireplace sp ...
-
Majestic SR42A - page 10
10 SR/SC Series "A" W oodb ur ning Fireplace 7412948 Straight-Up Chimney Installation T o mark the centerline of the flue, put the fireplace in final position and measure out from the wall: 9 ¹⁄₄ " (235mm). Mark a spot on the ceiling directly above the fireplace. Draw a line parallel to the back wall through this mark. (Fig. ...
-
Majestic SR42A - page 11
1 1 SR/SC Series "A" W oodb ur ning Fireplace 7412948 NOTE: Safety strips are not required over noncom- bustible floors where all supports at the base of the fireplace are noncombustible. Four (4) nailing flanges are incorporated on each cor- ner of the surround. Bend the nailing flanges out, level the box, then secure it firmly in p ...
-
Majestic SR42A - page 12
12 SR/SC Series "A" W oodb ur ning Fireplace 7412948 Continue installing the pipe as required until pipe is installed up through the ceiling. At this point, you must install a firestop spacer . Installing the Firestop Spacer in the Ceiling Hole A firestop spacer is used to keep pipe spaced properly and required for safety . Nail the fi ...
-
Majestic SR42A - page 13
13 SR/SC Series "A" W oodb ur ning Fireplace 7412948 NOTE: In the U.S., it is a good idea, although not al- ways required, to install an attic insulation shield where blown-in insulation is planned to be used in the attic. Install the attic insulation shield with the flanges on its base extending down into the framing hole. Nail each cor ...
-
Majestic SR42A - page 14
14 SR/SC Series "A" W oodb ur ning Fireplace 7412948 Installing T op Housing or T ermination Follow the installation instructions provided with the chimney termination you have selected. Installing Chimney In a Chase Refer to Page 5, Figure 5 for an illustration of a typical chase installation. CAUTION: T reatment of firestop spacers and ...
-
Majestic SR42A - page 15
15 SR/SC Series "A" W oodb ur ning Fireplace 7412948 MA81 rev . 8/5/97 1 " Ref. Combustible materials are permitted within a shaded area shown in Figure 23 titled Minimum W all Clearances. * ** MA81 Fig. 22 Combustible mantle clearances. *12" from top of fireplace opening for radiant models 12" from top of grille ...
-
Majestic SR42A - page 16
16 SR/SC Series "A" W oodb ur ning Fireplace 7412948 Hearth Installation A hearth extension is required to protect a combustible floor in front of the fireplace. Refer to Figure 23 for mini- mum dimensions and mounting detail. NOTE: Hearth Extension must not cover the air inlet opening of a fireplace. The hearth extension described in ...
-
Majestic SR42A - page 17
17 SR/SC Series "A" W oodb ur ning Fireplace 7412948 COMMON MA TERIALS AND F ACTORS MA TERIAL K* R MINIMUM THICKNESS EH2416 Common Brick 0.458 5.0 1.09 0.50 in.** 0.10 5.46 in.** (MHSC) R V alue is for 1/2 inch. * Units of K = BTU/SQ FT/HR/˚F/IN ** Thickness of Listed Material FP533ADD Addendum 6/1/99 djt 8/4/99 changed .2 to .1 one inch ...
-
Majestic SR42A - page 18
18 SR/SC Series "A" W oodb ur ning Fireplace 7412948 Installing Line for Gas Logs MHSC fireplaces are designed to accept a 1/2" (13 mm) gas line for installation of an approved gas appliance. (MHSC manufactures a wide variety of gas logs for use in MHSC fireplaces.) Be sure to have the appliance installed in accordance with buildin ...
-
Majestic SR42A - page 19
19 SR/SC Series "A" W oodb ur ning Fireplace 7412948 1 2 3 4 5 6 a b c 7 8 9 10 1 1 12 948 SR/SC parts 5/16/00 djt d 14 13 e MHSC reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, without notice. SR36A/42A, SC36A/42A SERIES Ref. Description SR/SC36A SR/SC42A 1 ...
-
Majestic SR42A - page 20
20 SR/SC Series "A" W oodb ur ning Fireplace 7412948 The following accessories for this appliance are available from your local Majestic Fireplaces distributor . Should you need additional information beyond what your distributor can furnish, contact: MHSC, 149 Cleveland Drive, Paris, KY 40361, Attn: T echnical Services. CAUTION: This fi ...
-
Majestic SR42A - page 21
21 SR/SC Series "A" W oodb ur ning Fireplace 7412948 Chimney Components Round T op T ermination T op used to terminate chimney at roof. RL TSK8 (Flashing not included.) Round T op T ermination - T op used to terminate chimney at chase. RL TSK8L Extended (Flashing not included.) Flashing Metal finishing required around Contemporary 8-6-12 ...
-
Majestic SR42A - page 22
22 SR/SC Series "A" W oodb ur ning Fireplace 7412948 Chimney Collar Enclosure Installs on the "over the chimney collar" of the CCE-SK fireplace; provides outside air to assist in cooling the chimney system. Attic Insulation Shield Used to prevent insulation from coming in AIS-SK contact with the chimney system. SK8 Chimney Sect ...
-
Majestic SR42A - page 23
23 SR/SC Series "A" W oodb ur ning Fireplace 7412948 LIMITED W ARRANTY Factory-Build Fireplace and Components (Except Blowers) What is Covered and For How Long Five-Y ear Coverage: For five years from the date this fireplace and components are first purchased for use, MHSC will, at its option, repair or replace any defective part of th ...
-
Majestic SR42A - page 24
MHSC 149 Cleveland Drive • Paris, Kentucky 40361 www .mhsc.com ...