    Part No. 312755-G Rev 00 May 2006 4655 Great America Parkway Santa Clara, CA 95054 Installing the Breaker Interface P anel f or the Ethernet Routing Switc h 8010co Chassis ...

  • Nortel 8010co - page 2

    2 312755-G Rev 00 Copyright © 2006 Nortel Netw orks. All Rights Reserved. The information in this document is subj ect to change without notice. The statements, config urations, technical data, and recommendations in this docume nt are believ ed to be accura te and reliable, but are presen ted without e xpress or implied warranty . Users must take ...

  • Nortel 8010co - page 3

    3 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis Règlement sur le br ouillage radioélect rique du ministère des Comm unications Cet appareil numérique (8000 Series cha ssis) respecte les limites de bruits r adioé lectriques visant les appareils numériques de classe A prescr ites dans le Règlement sur l ...

  • Nortel 8010co - page 4

    4 312755-G Rev 00 Denan statement (Japan/Nippon only) National safety stat ements of compliance CE marking statement (Europe onl y) EN 60 950 statemen t This is to certify that the Nortel 8000 Se ries chassis and components installed within the chassi s are in compliance with the requirements of EN 60 950 in accordance with the Low V oltage Directi ...

  • Nortel 8010co - page 5

    5 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis re verse engineer or otherwise translat e the Softwa re; c) crea te deri vati ve works or modif ications unless expressly authorized; or d) sublicense, rent or le ase the Software. Licensors of intellectual property to No rtel are beneficiaries of this provisio ...

  • Nortel 8010co - page 6

    6 312755-G Rev 00 ...

  • Nortel 8010co - page 7

    7 Installing th e Breaker Interface P ane l f o r the Ether n et Routing Sw itch 8010c o Chassis Contents Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Bef ore you begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 ...

  • Nortel 8010co - page 8

    8 Contents 312755-G Re v 00 Mounting h ardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 DC input elec trica l requiremen ts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Installing the breaker interf ace panel . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Nortel 8010co - page 9

    Contents 9 Installing th e Breaker Interface P ane l f o r the Ether n et Routing Sw itch 8010c o Chassis Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 ...

  • Nortel 8010co - page 10

    10 Contents 312755-G Re v 00 ...

  • Nortel 8010co - page 11

    11 Installing th e Breaker Interface P ane l f o r the Ether n et Routing Sw itch 8010c o Chassis Figures Figure 1 Breaker interface panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Figure 2 F ront p anel comp onents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Figure 3 Shelf c ...

  • Nortel 8010co - page 12

    12 Figures 312755-G Re v 00 Figure 30 La beling cables for the BIP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Figure 31 Ra ck g rounding strip example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Figure 32 Att aching power supp ly cable leads to the BIP . . . . . . . . . . . . . . . . . . . . ...

  • Nortel 8010co - page 13

    13 Installing th e Breaker Interface P ane l f o r the Ether n et Routing Sw itch 8010c o Chassis Ta b l e s T able 1 Alar m modu le display LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 T able 2 DC power requirem ents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 T able 3 Single chas ...

  • Nortel 8010co - page 14

    14 Tables 312755-G Re v 00 ...

  • Nortel 8010co - page 15

    15 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis Preface The breaker interf ace panel (BIP) provid es po we r distribu tion and alarm status indications for one or two 8010co cha ssis in an equipment rack. The status indications can be link ed to ot her BIPs to provide total sy st em stat us to the central o ...

  • Nortel 8010co - page 16

    16 Preface 312755-G Rev 00 T ext con ventions This guide uses the follo wing text con ventions: Ho w to get Help This section explains ho w to get help for Nortel products and services. Getting Help from the Nortel W eb site The best way to get techni cal support for Nortel products is from the Nortel T echnical Support W eb site: http://www .norte ...

  • Nortel 8010co - page 17

    Preface 17 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis • sign up for automatic notif ication of ne w software and documentation for Nortel equipment • open and manage technical suppo rt cases Getting Help o ver the phone fr om a Nortel Solutions Center If you don’ t f ind the information you requir ...

  • Nortel 8010co - page 18

    18 Preface 312755-G Rev 00 ...

  • Nortel 8010co - page 19

    19 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis Chapter 1 Overview This chapter provides an o vervie w of th e BIP and co vers the follo wing topics: • Physical description • “ Accessing the alarm module” on page 30 • “Conf iguration e xample” on page 32 Ph ysical description The BIP pro vides ...

  • Nortel 8010co - page 20

    20 Chapter 1 Overview 312755-G Rev 00 Fr ont panel Figure 2 sho ws the BIP front panel components. Figure 2 F ront panel components Shelf cir cuit breakers (upper and lo wer shelves) T wo groups of three circuit break ers pro v ide input power to the po wer supplies for the upper and lo wer shelf 8010 co chassis ( Figure 3 on page 21 ): • The f i ...

  • Nortel 8010co - page 21

    Chapter 1 Ove rview 21 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis Figure 3 Shelf circuit br eak ers 10372EA 1 1 = Upper shelf LEDs 2 = Lower shelf LEDs Front of rack Upper Shelf 123 123 Lower Shelf 2 Upper shelf power supplies PS 1 + DC – DC PS 2 + DC – DC PS 3 + DC – DC Lower shelf power supplies ...

  • Nortel 8010co - page 22

    22 Chapter 1 Overview 312755-G Rev 00 Alarm module displa y panel The alarm module disp lay panel ( Figure 4 ), located on the BIP front panel, provides visual status indications for one or tw o 8010co chassis in a single rack. Figure 4 Alar m modu le display panel See Ta b l e 1 for a description of the LEDs. T able 1 Alar m mo dule display LEDs I ...

  • Nortel 8010co - page 23

    Chapter 1 Ove rview 23 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis The alarm module can also be link ed to other BIPs, an d can pro vide visual and audible alarms to aisle alarms and to the central of fice (see “Central of fice alarms” on page 26 ). Alarm support for the BIP is provided by the 8691SF ...

  • Nortel 8010co - page 24

    24 Chapter 1 Overview 312755-G Rev 00 Front panel lo c king screws The front panel locking scre ws allo w yo u to open the front panel to access the alarm module. The alarm modu le contains jumpers that you use to conf igure your system alarm parameters. For information about conf iguring yo ur system alarm parameters, see “ Accessing the alarm m ...

  • Nortel 8010co - page 25

    Chapter 1 Ove rview 25 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis Figure 6 sho ws the loca tion of the shelf alar m connectors on the BIP and on two 8010co chassis (upper and lo wer shelves). Figure 6 Shelf alar m co nnections (uppe r and lower shelv es) 1 = J1 (BIP upper shelf alarm connector) 2 = J2 ( ...

  • Nortel 8010co - page 26

    26 Chapter 1 Overview 312755-G Rev 00 Central office alarms The central of fice alarm connectors allo w you to aggregate alarms from multiple BIPs and route them to an aisle alarm and to the central off ice. Figure 7 shows three BIPs configured to aggregate alarms from three racks. Y ou c an conf igure up to ten BIPs in a series configuration to ag ...

  • Nortel 8010co - page 27

    Chapter 1 Ove rview 27 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis This type of configuration allows you to independ en tly monitor and control the external audible and visual alarm status in dications of the BIP at the central off ice. Figure 8 Configuring standalone BIPs to report alar m status P ower ...

  • Nortel 8010co - page 28

    28 Chapter 1 Overview 312755-G Rev 00 Figure 9 P ower term inal bloc k Figure 10 on page 29 shows an e xample of the BIP po wer terminal block ca bling including grou nd connections for two 8010co chassis and in stalled po wer supplies. As shown in this example, both upper an d lower chassis are each fully conf igured with three po wer supplies (on ...

  • Nortel 8010co - page 29

    Chapter 1 Ove rview 29 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis Figure 10 P ow er and g rounding e xample 32 PS (+) Lower Shelf PS (+) Upper Shelf PS (-) Lower Shelf PS (-) Upper Shelf A/B Input Feed Returns – 48 VDC A/B Input Feeds 1321 321321 A 2 A 1 B 1 B 2 Power terminal block (BIP) Return Secon ...

  • Nortel 8010co - page 30

    30 Chapter 1 Overview 312755-G Rev 00 Accessing the alarm module The alarm module contains jumpers that you can configure to allo w the BIP to monitor the shelf alarm cables for a single or dual chassis installation. The BIP ships from the factory with def ault jumper configurations set for a single chassis in the lo wer shelf of the rack. If you i ...

  • Nortel 8010co - page 31

    Chapter 1 Ove rview 31 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis 2 Gently lo wer the front panel to e xpose the alarm modu le ( Figure 12 ). Figure 12 Accessing the al ar m module Figure 13 shows a close-up vie w of the alar m module with jumpers J8 and J9 configured to monitor the shelf alarm cabl e f ...

  • Nortel 8010co - page 32

    32 Chapter 1 Overview 312755-G Rev 00 Configuration e xample Figure 14 shows a typical conf iguration using the optional breaker interface panel. Figure 14 8010co chassis configuration with BIP option 10420EB 1 = Breaker interf ace panel 2 = 8010co Chassis (upper shelf position) 3 = 8010co Chassis (lower shelf position) 2 1 3 ...

  • Nortel 8010co - page 33

    33 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis Chapter 2 Installation This chapter describes how to install th e breaker interface panel and co vers the follo wing topics: • “Preparing to install the breaker interface panel ” ne xt • “Installing the breaker interface panel” on page 36 • “V ...

  • Nortel 8010co - page 34

    34 Chapter 2 In stallation 312755-G Rev 00 Shipment content s Inspect all items for shipping d amage. If yo u detect any damage, d o not install the BIP . Call the Nortel T echnical Solutions Center in your area (see “Ho w to get Help” on page 16 ). Y our BIP shipment contains the follo wing items ( Figure 15 ): Figure 15 Contents of the BIP sh ...

  • Nortel 8010co - page 35

    Chapter 2 Inst allation 35 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis Additional equipme nt T o install the BIP , you might need items that are not part of the BIP installation kit. Before installing the BIP hardw are, ensure that you ob tain all the cables, tools, and other equipmen t that you need. Fo ...

  • Nortel 8010co - page 36

    36 Chapter 2 In stallation 312755-G Rev 00 Installing the breaker interface panel This section cov ers the following topics: • “Installing the hardware ” next • “Connect ing cabl es to the ch assis po wer supplies” on pag e 38 • “Routing po wer supply cables to the BIP” on page 47 • “Connecting the gr ound cables to the rack g ...

  • Nortel 8010co - page 37

    Chapter 2 Inst allation 37 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis T o install the BIP: 1 Remov e the plastic back cov er from the BIP terminal block ( Figure 16 ). Figure 16 Remo ving the plastic bac k cov er from the BIP 2 Position the BIP in the uppermost position in the rack and align the holes i ...

  • Nortel 8010co - page 38

    38 Chapter 2 In stallation 312755-G Rev 00 Connecting cables to the chassis po wer supplies This section describes how to connect th e BIP power cables to the 8010co chassis 8004DC po wer supplies. These procedur es assume that all requi red po wer supplies were pre viously installed du ring the 8010co chassis installation. Before begi nning the pr ...

  • Nortel 8010co - page 39

    Chapter 2 Inst allation 39 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis T o connect cables to the chassis po wer supplies: 1 Remov e the 8010co chassis bottom bezels (if required). a Using a Phillips scre wdriv er , loosen the 2 captiv e screws securing the bezel to the chassis ( Figure 18 ). b Pull the t ...

  • Nortel 8010co - page 40

    40 Chapter 2 In stallation 312755-G Rev 00 2 Locate the po wer supplies ( Figure 19 ). W ith the bezel removed, you can see the power supplies. The chassis can contain up to three power supplies. (Po wer supplies reside in ba y 1, bay 2, and bay 3, vie wed left to right from the front of the chassis.) Figure 19 Location of po wer supplies Fail Pass ...

  • Nortel 8010co - page 41

    Chapter 2 Inst allation 41 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis 3 Loosen the 2 retaining scre ws on the power supply located in bay 1 i n the lo wer chassis ( Figure 20 ). Figure 20 Loosening the po wer supply retaining scre ws 4 Lift the e xtractor le ver to disconnect the po wer supply from the ...

  • Nortel 8010co - page 42

    42 Chapter 2 In stallation 312755-G Rev 00 5 Remov e the Phillips screw securing the plastic safety co ver to the power supply , and then remov e the co ver ( Figure 22 ). Sa ve the Phillips scre w and the co ve r for replacement later . Figure 22 Remo ving the plastic saf ety cov er from the po wer supply 6 Note the position of the ground stud and ...

  • Nortel 8010co - page 43

    Chapter 2 Inst allation 43 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis 7 Locate the follo wing items in the shipping container ( Figure 24 ). • 125-inch po wer cables—for po wer supplies located in the lower chassis • 90-inch po wer cables—for po wer suppl ies located in the upper chassis • 90- ...

  • Nortel 8010co - page 44

    44 Chapter 2 In stallation 312755-G Rev 00 9 Attach the lug end of a 125-inch po wer supply ca ble to th e positi ve terminal on the power supply ( Figure 26 ). Use a 7/16-inch hex wrench to fasten the hardware in the correct order . Figure 26 Attaching the posit iv e lead +DC 4 1 = T wo-hole cr imp lug 2 = Lock w asher (x 2) 3 = He x nut (x 2) 4 = ...

  • Nortel 8010co - page 45

    Chapter 2 Inst allation 45 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis 10 Attach the lug end of a 125-inch po wer supply cable to the negati ve terminal on the power supply ( Figure 27 ). Use a 7/16-inch hex wrench to fasten the hardware in the correct order . Figure 27 Attaching the negat iv e lead 11 R ...

  • Nortel 8010co - page 46

    46 Chapter 2 In stallation 312755-G Rev 00 12 Secure the po wer supply in bay 1 of the lower chassis ( Figure 29 ). a Use the po wer supply hand le to push the po wer supply firmly into bay 1. b Push the ex tractor le ver do wn to lock the po wer supply in place. c T ighten the two po wer supply retaining scre ws. Figure 29 Replacing the po wer sup ...

  • Nortel 8010co - page 47

    Chapter 2 Inst allation 47 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis Routing power suppl y cables to the BIP After you connect all cables to the cha ssis po wer supplies, you must route the po wer supply cable leads from each chassis to the BIP . If you installed an upper and lo wer shelf chassis, and ...

  • Nortel 8010co - page 48

    48 Chapter 2 In stallation 312755-G Rev 00 5 Route the remaining (black ) po wer supply cables from the back of the lo wer and upper shelf chassis to the back pane l of the BIP , loosely fastening them with tie-wraps along the path. 6 Loosely support the po wer supply cabl es with tie-wraps abo ve the BIP po wer terminal block. 7 Proceed to, “Con ...

  • Nortel 8010co - page 49

    Chapter 2 Inst allation 49 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis Connecting the power suppl y cables to the BIP T o connect the po wer supp ly cables to the BIP: 1 Locate one of the po wer supply cables. 2 Match the labeled tag on the po wer supp ly cable with the correct location on the po wer ter ...

  • Nortel 8010co - page 50

    50 Chapter 2 In stallation 312755-G Rev 00 4 Repeat steps 1 through 3 for each remaining po wer supply in your conf iguration ( Figu re 33 ). Figure 33 Upper and lo wer shelf po wer cab les connected to the BIP 5 Locate the BIP ground cable (see Figure 30 on page 47 ). 10394FA 32 PS (+) Lower Shelf PS (+) Upper Shelf PS (-) Lower Shelf PS (-) Upper ...

  • Nortel 8010co - page 51

    Chapter 2 Inst allation 51 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis 6 Attach one end of the BIP ground cable to the po wer terminal block ( Figure 34 ). a Loosen the po wer terminal block screw ju st enough to i nsert the ground cable lead (item 1 in Figure 34 ). b Insert the lead and tighten the scre ...

  • Nortel 8010co - page 52

    52 Chapter 2 In stallation 312755-G Rev 00 Connecting DC input power f eeds to the BIP Nortel does not supply the cables for c onn ecting the breake r interface panel to the DC input po wer source. Y ou must select ca bles that comply with the electrical code of the country where you inten d to use the DC-DC p o wer supply . Y ou can connect up to ...

  • Nortel 8010co - page 53

    Chapter 2 Inst allation 53 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis Figure 35 A and B f eed exa mple Ta b l e 3 lists input power options for sing le and dual chassis installations. T able 3 Single chassis and dual chassis input options Single chassis input * * F or a single chassis installation, alwa ...

  • Nortel 8010co - page 54

    54 Chapter 2 In stallation 312755-G Rev 00 T o connect the DC input feeds to the BIP: 1 Locate the DC po wer sour ce for the DC input feed. 2 Determine the po wer requirements for your conf iguration (see Fi gure 35 on page 53 ). 3 Locate the A and B - 48 VDC input feeds ( Figure 36 ). The -48 VDC input feed cables should be tagged with source labe ...

  • Nortel 8010co - page 55

    Chapter 2 Inst allation 55 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis 4 Connect the -48 VDC input feeds according to your conf iguration requirements. a Match the tagged -48 VDC input feed cabl e lead wi th the correct po wer terminal block on the back o f the BIP ( Figure 37 ). a Loosen the po wer term ...

  • Nortel 8010co - page 56

    56 Chapter 2 In stallation 312755-G Rev 00 5 Connect the remainin g -48 VDC input feeds and returns as required ( Figure 38 ). Figure 38 Connecting th e A and B -48 VDC input f eeds to the BIP (2 of 2 ) Note: Figure 38 sho ws the attachment of two “ A” feeds and tw o “B” feeds to the BIP . Note that there is a primary and a secondary A feed ...

  • Nortel 8010co - page 57

    Chapter 2 Inst allation 57 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis 6 Connect the A/B input feed returns. a Locate the A/B Input Feed Returns se ction of the po wer terminal block. b Loosen one of the four a v ailable A/B input feed return connection s cre ws just enough to insert the cable lead (item ...

  • Nortel 8010co - page 58

    58 Chapter 2 In stallation 312755-G Rev 00 7 Connect the remaining -48 VDC input returns as required ( Figure 4 0 ). Figure 40 shows the BIP with all po we r cables and returns installed. Figure 40 Connecting th e A/B input f eed returns (2 of 2) 8 Go to the ne xt section, “Replacin g co v ers” on pag e 59 . Note: Be sure to properly support th ...

  • Nortel 8010co - page 59

    Chapter 2 Inst allation 59 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis Replacing co vers After you complete all of th e cabling requirements as described in the pre vious sections, you must replace the plastic ba ck cov er on the BIP and the 8010co chassis bezel(s) that were remov ed earlier in these pro ...

  • Nortel 8010co - page 60

    60 Chapter 2 In stallation 312755-G Rev 00 2 Replace the 8010co chassis bezel. a Set the notch (on both ends of the 312096-A bezel) into the tabs on the chassis ( Figure 42 ). b Lift the top of the bezel up, and t hen align the capti ve scre ws with the holes in the chassis. c Using a Phillips scre wdriv er , tighten the 2 capti ve scr e ws to secu ...

  • Nortel 8010co - page 61

    Chapter 2 Inst allation 61 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis Installing shelf alarm cables 1 T o install the shelf alarm cable for a single chassis in the lo wer shelf: a Locate the shelf alarm cables in the shipping container . b Connect one end of the shelf alarm cable to the J2 connec tor on ...

  • Nortel 8010co - page 62

    62 Chapter 2 In stallation 312755-G Rev 00 2 T o install the shelf alarm cable for a second chassis in the upper shelf: a Conf igure the jumpers on the alarm modu le to support a se cond chassis in the upper shelf as described in “ Accessing the alarm module” on pa ge 30 . b Connect one end of the shelf alarm cable to the J1 connec tor on the b ...

  • Nortel 8010co - page 63

    Chapter 2 Inst allation 63 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis Initial power -up T o power up the 8010co chassis: 1 Set the six circuit breakers on the BIP front panel to the of f position (O = Of f). 2 Set the switches for all po wer supplies in the upper and lo wer chassis to the of f position ...

  • Nortel 8010co - page 64

    64 Chapter 2 In stallation 312755-G Rev 00 4 V erify the following LEDs on the 8010co chassis: — The (green) po wer supply LEDs for each po wer supply in both the upper and lo wer chassis are on. (If any of the po wer supply LEDs are not on, replace the po wer supply .) — The chassis f ans are po wering up. If any of the pre vious steps indicat ...

  • Nortel 8010co - page 65

    Chapter 2 Inst allation 65 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis 4 Continue with the insta llation of the 8010co cha ssis as described in the appropriate product chassis installation manual. Note: When you po wer of f the 8010co chassis, wait at least 30 seconds before turning the po wer su pplies ...

  • Nortel 8010co - page 66

    66 Chapter 2 In stallation 312755-G Rev 00 ...

  • Nortel 8010co - page 67

    67 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis Chapter 3 Pr oblem solving This chapter describes ho w to isolate an d diagnose problems with your b reaker interface panel and associated 8010co chassis. This chapter cov ers the follo wing topics: • “Interpreting the LEDs ” (next) • “Diagnosing and ...

  • Nortel 8010co - page 68

    68 Chapter 3 Problem solving 312755-G Rev 00 Interpreting the LEDs All BIP LEDs and i ndicators are located on the front pa nel ( Figure 44 ). Figure 44 BIP LEDs and indicators Ta b l e 4 describes the BIP LEDs and indicators. T able 4 BIP LEDs and indicators Item Labe l/Icon T ype Color/St ate Descrip tion 1 Upper Shelf/ Lower Shelf LED Red/On ste ...

  • Nortel 8010co - page 69

    Chapter 3 Problem solving 69 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis If you need more help, go to t he next section, “Diagnosing and correcting t he problem” on page 7 0 . 4 POWER Indicator White/On ste ady P ower indicator—The external DC p ower is av ailable to the BIP . 5 CRITICAL Indicator ...

  • Nortel 8010co - page 70

    70 Chapter 3 Problem solving 312755-G Rev 00 Diagnosing and correcting the pr oblem Before you perform the prob lem-solving steps in this section, complete the follo wing steps: 1 Set the switches for all po wer supplies in the upper and lo wer chassis to the of f position (O = Of f). 2 Set the six circuit breakers on the BIP front panel to the of ...

  • Nortel 8010co - page 71

    Chapter 3 Problem solving 71 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis Corrective actions T o resolve problems with the BIP or th e 8010co chassis and components, follo w the correcti ve act ions sugges ted in Ta b l e 5 . T able 5 Correc tiv e actions Symptom Probable cause Corrective action The (red) ...

  • Nortel 8010co - page 72

    72 Chapter 3 Problem solving 312755-G Rev 00 The (red) CRITICAL indicator is on steady . F ailov er from Master CPU to the second (redundant) CPU . This action is preceded by the CRITICAL indicator blinking two times and then tur ning off after the redundant CPU becomes operational. After the Redundant CPU becomes op erational, the (red) MAJOR indi ...

  • Nortel 8010co - page 73

    73 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis Appendix A T ec hnical specifications This appendix lists the technical specif ications for the break er interface panel . This appendix cov ers the follo wing topics: • “En vironme ntal ” (next) • “Electrical” on page 74 • “Physical dimensions ...

  • Nortel 8010co - page 74

    74 Appendix A Technical specifications 312755-G Rev 00 Electrical Ph ysical dimensions Electr omagnetic emissions Safety a gency cer tification P arameter Specifica tions Input V oltage (Nominal) -48 VDC Input Current Feed Rating 60 A per DC input f eed Output Current Feed Rating 30 A per DC output feed P arameter Specifica tions Height 12.6 cm (4. ...

  • Nortel 8010co - page 75

    75 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis Appendix B BIP e xternal cab le pin assignments This appendix describes the br eaker interface panel connectors. This appendix cov ers the follo wing topics: • “Shelf alarm connectors (J1 and J2) , ” next • “Of f ice alarm connectors (J3 and J4)” o ...

  • Nortel 8010co - page 76

    76 Appendix B BIP external cable pin assignments 312755-G Rev 00 Figure 46 J1 and J2 shelf alar m connector pinouts Ta b l e 6 lists the pin assignments for the J1 and J2 shelf alarm connectors. T able 6 J1 and J2 shelf alarm connector pin assignment s Pin Signal Description 1 L+ABS Alar m battery supply retur n. 2 VCRIT Visual critical alarm. 3 A ...

  • Nortel 8010co - page 77

    Appendix B BIP exte rnal cable pin assign ments 77 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis Office alarm connector s (J3 and J4) The BIP of f ice alarm connectors (J3 and J4 ) use high-density , 26-pin D-su b connectors ( Figure 47 ). Figure 47 J3 and J4 high-density 26- pin D-sub connector Figure 48 ...

  • Nortel 8010co - page 78

    78 Appendix B BIP external cable pin assignments 312755-G Rev 00 Ta b l e 7 lists the pin assignments for the J3 and J4 off ice alarm connec tors. T able 7 J3 and J4 office alarm connector pin assignments Pin Signal Description 1 TT A V oice communications from teleph one jacks . 2 TRB V oice communications from teleph one jacks . 3 D2A Data commun ...

  • Nortel 8010co - page 79

    Appendix B BIP exte rnal cable pin assign ments 79 Installing t he Breaker Inte rface Panel for the Ethernet Routi ng Switch 8010co Chassis Standalone office alarm connector (J5) The standalon e of fice alarm connectors (J5) uses a high-densi ty , 26-pin D-sub connector ( Figure 49 ). Figure 49 J5 high-den sity 26-pin D- sub connecto r Figure 50 sh ...

  • Nortel 8010co - page 80

    80 Appendix B BIP external cable pin assignments 312755-G Rev 00 Ta b l e 8 lists the pin assignments for the J5 standalone of fice alarm connector . T able 8 J5 standalone office al ar m connector pin assign ments Pin Signal Description 1 Critical a lar m—Visual (NC) Visual alar m contact 2 Major alar m—Visual (NC) Visual alar m contact 3 Mino ...

  • Nortel 8010co - page 81

    Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis 81 Inde x Number s 8691omSF central processing uni t (CPU) 23 8691SF central processing unit (CPU) 23 A alarm module alarm conditions 23 configuring jumpers 30 display panel 22 LEDs 22 alarms aisle 26 central of f ice 26 B back panel 24 breaker interf ace panel ( ...

  • Nortel 8010co - page 82

    82 Index 312755-G Rev 00 alarm module 22 BIP front panel 68 description 68 location 68 P pin assignments, cables 75 po wer DC input requirements 35 initial power -up 63 po wering off t he system 64 po wer supplies cable routing 47 connecting cables 38 , 49 po wer terminal block 28 problem solving correcti ve actions 71 interpreting LED s 67 R requi ...

Produzent Nortel Kategorie Switch

Dokumente, die wir vom Produzenten des Geräts Nortel 8010co erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Nortel
- Bedienungsanleitungen 8010co
- Produktkarten Nortel
- Informationsbroschüren
- oder Energieetiketten Nortel 8010co
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Nortel 8010co.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Nortel 8010co, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Nortel 8010co. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Nortel 8010co ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Nortel 8010co, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Nortel 8010co hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Nortel 8010co verständlich ist.

Eine gänzliche Bedienungsanleitung von Nortel sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Nortel 8010co bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Nortel 8010co befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Nortel 8010co, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Nortel 8010co - die uns die ersten Schritte während der Nutzung von Nortel 8010co erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Nortel 8010co hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Nortel 8010co im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Nortel 8010co?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Nortel 8010co nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Nortel 8010co hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)