    Commer cial Electric W ater Heaters 9kW – 900kW Input Models CHP-I&S-01 INST ALLA TION AND SER VICE MANUAL 1 If the inf ormation in this manual is not f ollo w ed exactl y , a f ir e or explosion ma y r esult causing property damage, personal injury or loss of life . Do not stor e or use gasoline or other flammable v apors and liquids in the ...

  • Bradford-White Corp 9kW - page 2

    2 CONTENTS Star t-Up Pr ocedur e Filling the W ater Heater . . . . . . . . .22 Start-Up Checks . . . . . . . . . . . . . . .23 Shutdo wn Procedure . . . . . . . . . . . .24 Maintenance T&P Relief V alve . . . . . . . . . . . . . .24 W ater Chemistr y . . . . . . . . . . . . . . .25 Flushing the T ank . . . . . . . . . . . . . .25 Sediment Remo ...

  • Bradford-White Corp 9kW - page 3

    3 FIG. 2 F ront Vie w V ertical Squar e Models FIG. 1 Fr ont V iew V er tical Round Models FIG. 3 F ront Vie w Horizontal Models ...

  • Bradford-White Corp 9kW - page 4

    T o minimize the possibility of serious personal injury , f ir e or damag e to y our appliance , ne v er violate the follo wing safety rules. 1. Alw a ys keep the ar ea around y our appliance fr ee of combustib le materials, gasoline, and other flammable liquids and v apors. 2. Ne ver co ver y our appliance, lean an ything against it, stor e trash ...

  • Bradford-White Corp 9kW - page 5

    3. The appliance must be installed so that the electrical components are protected from w ater (dripping, spraying, etc.) during appliance operation and service (replacing of fuses, elements, etc.) 4. Appliances located in a garage or parking structure shall be installed so that the jacket and all piping shall be located or protected so that it is ...

  • Bradford-White Corp 9kW - page 6

    Right Side - 6" (15cm) (24" (0.61m) for high kW vertical square models with an additional control panel on right side) Rear - 0" Left Side - 0" F r ont - 36" (0.91m) for service access to controls and heating elements To p - 12" (30cm) for service access to electrical ser vice, w ater connections and piping W ater Pipe ...

  • Bradford-White Corp 9kW - page 7

    7 Maintain minimum specif ied clearances for adequate operation. All installations must allo w suf f icient space for servicing the electrical components, w ater pipe connections, piping and other auxiliary equipment, as well as the appliance. Multiple appliances ma y be installed in a modular w ater heater installation. Multiple appliances ma y be ...

  • Bradford-White Corp 9kW - page 8

    Before making an y connections to the cold w ater inlet or hot w ater outlet, insure that all piping is clean and free of material or scale. This can usually be accomplished b y “ blo wing out the pipe. ” Any foreign material or scale entering the w ater heater can adversel y af fect operation and performance. Inlet and Outlet Connections F or ...

  • Bradford-White Corp 9kW - page 9

    discharg e! Hydro gen gas can be produced in a hot water system that has not been used for a long period of time (generall y tw o weeks or more). Hydro gen gas is extremel y flammable. T o prev ent the possibility of injury under these conditions, we recommend the hot w ater f aucet be open for se veral minutes at a sink close to the w ater heater ...

  • Bradford-White Corp 9kW - page 10

    initial operation. Operation of a w ater heater without a completel y f illed tank ma y result in serious damage to the appliance and heating element burn out. 5. The w ater heater should be connected with a separate grounded branch circuit with o ver cur rent protection and disconnect s witch. The w ater heater should be g rounded in accordance wi ...

  • Bradford-White Corp 9kW - page 11

    The follo wing items are a vailab le as extra cost options. • Electronic lo w w ater cut-off pre vents energizing of the heater w hen it is not f illed with w ater . • Pilot lights – Monitor on-of f cycle of contactors. • Manual limiting switches with indicating lights to permit heater kW input to be manuall y limited as desired. • T empe ...

  • Bradford-White Corp 9kW - page 12

    Each internal pow er circuit is fused for safety . Each po w er circuit to an immersion element is fused at a maximum of 48 amps. P o w er circuits ma y be fused at lo w er cur rent lev els as needed to balance cur rent on three phase units. The po w er circuit fuses are held b y a spring loaded fuse block rated for the v oltage specif ied to opera ...

  • Bradford-White Corp 9kW - page 13

    This w ater heater uses an immersion thermostat(s) to activ ate magnetic contactors allo wing cur rent to flo w to the immersion heating elements. The standard control system uses one immersion thermostat for each 54kW of electric heating po w er in a water heater . As an option, additional immersion thermostats may be pro vided to add additional s ...

  • Bradford-White Corp 9kW - page 14

    The maxim um temperatur e setpoint that should be set f or the Immersion Thermostats or pr ogrammed into the Electr onic T emperatur e Contr ol Sequencer is 190 ° F ( 88 ° C) Al wa ys close the electrical control panel door after making a temperature adjustment. T ur n on electricity . 1. T ur n “ OFF ” the electrical po w er to the water hea ...

  • Bradford-White Corp 9kW - page 15

    The w ater heater uses an optional adjustable electronic temperature control to pro vide staged ON/OFF control of the electric heating elements. Operation is based on temperature input from an immersion temperature sensor . The sensor is a positi ve coef f icient platinum thermistor . The sensor is placed in a w ell located abo ve the heating eleme ...

  • Bradford-White Corp 9kW - page 16

    Once po w er is applied to the temperature controller the displa y will countdo wn from 210 until the displa y reads zero. All outputs are de-energized at this time. This countdo wn process will repeat each time main po w er is inter rupted. T o av oid vie wing this entire countdo wn, press the Select ke y . The displa y will no w sho w nor mal rea ...

  • Bradford-White Corp 9kW - page 17

    Stag e Set P oint Differ ential 1 12 5 ˚ F 2 ˚ F 2 12 3 ˚ F 2 ˚ F 3 12 1 ˚ F 2 ˚ F 4 12 0 ˚ F 2 ˚ F Re-pro g ram the set points and dif ferentials to meet your system hot w ater requirements. The operating control uses a Liquid Crystal Displa y for interactiv e prompting during pro g ramming and displa y of sensed and assigned set point and ...

  • Bradford-White Corp 9kW - page 18

    FIG. 21 High W ater T emperatur e Limit Contr ol - Fixed Setting ERROR MESSAGES DISPLA YED BY THE ELECTRONIC TEMPERA TURE CONTROL There are se ven er ror messages that can be displa yed in response to softw are or hardware problems with the boiler ’ s inter nal electronic temperature control. The er ror codes that ma y be seen flashing on the dis ...

  • Bradford-White Corp 9kW - page 19

    The high limit contr ol will not r eset until the water temper ature has dr opped belo w the set point of the high limit. r eset multiple times. The source of the problem must be found and cor rected to insure proper operation. The limit control is co vered with an insulation blank et which must be remo ved to push the red reset button. The blanket ...

  • Bradford-White Corp 9kW - page 20

    This w ater heater may be equipped with an optional electronic lo w w ater cut-off installed at the factor y . This lo w water cut-of f device uses a w ater lev el sensing probe located abo ve the heating element installed in the highest point in the storage tank. If the internal water le vel drops belo w this point, the lo w water cut-of f will sh ...

  • Bradford-White Corp 9kW - page 21

    electrical input of the w ater heater in the summer months when ground w ater temperatures are w ar mer and full electrical input from the immersion heating elements is not required. The w ater heater may be restored to full input b y mo ving the s witches to the “ ON ” position. The w ater heater may be pro vided with an optional time clock. T ...

  • Bradford-White Corp 9kW - page 22

    The cold w ater supply m ust be left in the open position when the w ater heater is in use. An alarm bell with silencing switch is a vailab le as an option on this w ater heater . The alarm bell can be used to pro vide an audib le indication of a control sensed malfunction. The user must specify the safety function or multiple safety functions that ...

  • Bradford-White Corp 9kW - page 23

    6. While the tank is f illing, open the electrical control panel and set the thermostat(s) to the desired w ater temperature. If equipped with multiple thermostats, all individual thermostats may be adjusted to the same temperature set point or they ma y be set a 2 ° F to 4 ° F (1 ˚ C to 2 ˚ C) apart to step the elements on in stages. 7. Insure ...

  • Bradford-White Corp 9kW - page 24

    4. Close and lock the electrical control panel door . 5. T urn on the main electrical pow er to the w ater heater . 6. T emperature control and contactor operation should be checked b y allo wing the water heater to come up to temperature and shut of f automaticall y . 7. The w ater heater is no w ready continuous normal operation. Draining the W a ...

  • Bradford-White Corp 9kW - page 25

    should be metallic pipe or a high temperature plastic pipe (CPVC, etc.) to insure that hot w ater flo w will not damage the discharge piping from the relief v alve. In hard w ater areas, water treatment should be used to reduce the introduction of minerals to the system. Minerals in the w ater can collect in the storage tank and on the immersion he ...

  • Bradford-White Corp 9kW - page 26

    All gask ets on disassembled clean-out openings m ust be r eplaced with new g askets on r e-assembl y . Gaskets ar e a v ailab le from y our distributor . Scale accumulation in the bottom of the storage tank ma y be remo ved b y tur ning of f main po w er and draining the tank. Once all w ater is remo ved , the hand hole access can be remo ved. Thi ...

  • Bradford-White Corp 9kW - page 27

    27 TROUBLE SHOOTING Checklist Before calling for service, check the following points to see if the cause of trouble can be identif ied and cor rected. Revie wing this checklist ma y eliminate the need of a ser vice call and quickl y restore hot water service. Not enough or no hot w ater 1. Ensure that the electrical disconnect s witch serving the w ...

  • Bradford-White Corp 9kW - page 28

    CP-5M-5/02-Reprinted in U .S.A. Excessi ve w ater pressure is not the most common cause of relief v alve leakage. It is often caused b y a “ closed system. ” A check valve, back flo w pre venter or pressure reducing v alve, in the inlet system will not permit the expanded hot water volume to equalize pressure with the main. A relief v alve must ...

Produzent Bradford-White Corp Kategorie Water Heater

Dokumente, die wir vom Produzenten des Geräts Bradford-White Corp 9kW erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Bradford-White Corp
- Bedienungsanleitungen 9kW
- Produktkarten Bradford-White Corp
- Informationsbroschüren
- oder Energieetiketten Bradford-White Corp 9kW
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Bradford-White Corp 9kW.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Bradford-White Corp 9kW, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Bradford-White Corp 9kW. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Bradford-White Corp 9kW ansehen.

Die komplette Bedienungsanleitung des Geräts Bradford-White Corp 9kW, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Bradford-White Corp 9kW hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Bradford-White Corp 9kW verständlich ist.

Eine gänzliche Bedienungsanleitung von Bradford-White Corp sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Bradford-White Corp 9kW bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Bradford-White Corp 9kW befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Bradford-White Corp 9kW, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Bradford-White Corp 9kW - die uns die ersten Schritte während der Nutzung von Bradford-White Corp 9kW erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Bradford-White Corp 9kW hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Bradford-White Corp 9kW im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Bradford-White Corp 9kW?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Bradford-White Corp 9kW nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Bradford-White Corp 9kW hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)