Bedienungsanleitung Carrier 50TCQA

48 Seiten 5.46 mb
Download

Zur Seite of 48

Summary
  • Carrier 50TCQA - page 1

    50TCQA Si ngle Packa ge Rooftop Heat P ump with P uron r (R - - - 410A) Refrig erant S i z e s 0 4 --- 0 7 Installation Instructions NOTE : Read the entire instru ction manual before s tarting the ins tallation T ABLE OF CONTENTS SAFET Y CONSIDE RA TIONS 1 .................... INS T ALLA TION 4 ............................... Step 1 - - Plan fo r U ...

  • Carrier 50TCQA - page 2

    2 ELECTRIC AL SHOCK HAZARD Failure t o follow thi s warning could c ause personal injury or dea th. Before performi ng service or m ainte nance ope rati ons on unit, always turn off main power switc h to unit a nd install l ockout ta g. Unit may have more than one power switch. ! W ARNING UNIT OP ERA TIO N AND SAFE TY H AZARD Failure t o follow thi ...

  • Carrier 50TCQA - page 3

    3 Horizontal Connections / Economizer V ertical Connections / Economizer C09001 Fig. 1 - - Unit Dimensional Drawing – 04 — 07 Size Units 50TCQA ...

  • Carrier 50TCQA - page 4

    4 C09002 Fig. 1 - - Unit Dimensional Drawing – 04 — 07 Size Unit (cont.) INST ALLA TION Jobsite Survey Complete th e follow ing check s bef ore ins tallation. 1. Consult local buildi ng codes a nd the NEC (Nat ional Electrical Code) AN SI/N FP A 70 for special ins talla- tion requ irements . 2. Det ermine uni t loca tion (from proje ct plans) o ...

  • Carrier 50TCQA - page 5

    5 Roof moun t — Check bui lding code s for weight distribution requirem ents. Unit operat ing weight i s shown in T a ble 1. Ste p 2 — Plan for Seque nce of Unit Ins tallat ion The support me thod used for thi s uni t will di cta te different sequence s for the steps of unit i nstall ation. For exa mple, on curb- - mounted units, some accessori ...

  • Carrier 50TCQA - page 6

    6 50TCQA04-07 ROOFCURB ACCESSORY CRRFCURB001A02 CRRFCURB002A02 1’ - 2” [356] 2’ - 0” [610] UNIT SIZE C08548 Fig. 3 - - Roof Curb Details 50TCQA ...

  • Carrier 50TCQA - page 7

    7 A-B 0.5” (13) B-C 1.0” (25) A-C 1.0” (25) MAXIMUM ALL OWABLE DIFFERENCE IN. (MM) C06110 Fig. 4 - - Unit Lev eling T olerances Ste p 5 — Field Fabr icate Duct work Cabinet re turn-ai r static pre ssure (a negative condition) shall not exceed 0.35 in. wg (87 P a) w ith economizer or 0.45 in. wg (1 12 Pa) without e conomi zer . For verti cal ...

  • Carrier 50TCQA - page 8

    8 P o s i t i o n i n go nC u r b— Po sition unit on roof curb s o that the follow ing clearances are maintained : 1 / 4 in. (6.4 mm) clearance between the roof curb and the base rail inside the front and rear , 0.0 in. clearance betw een the roof cu rb and th e base r ail insid e on the duct en d of th e unit. This w ill r esult in the dis tance ...

  • Carrier 50TCQA - page 9

    9 T wo P osition Damper H ood Removal and Setup - - Factor y Option 1. T he hood is shipped i n knock - - down form a nd assembled t o a me tal support tray using plastic stretch w rap. Located in the return air compartmen t, the assembly ’ s metal tray is attached to the basep an and also attached to the damper usin g two plas tic tie - - wraps ...

  • Carrier 50TCQA - page 10

    10 Economize r Hood and T wo- - Position Hood — NOTE : If the pow er exhaus t access ory is to be ins talled on the unit , t he hood shipped with t he unit will not be used and mus t be dis carded. S ave the aluminu m filter for use in the powe r exhaust hood assembl y . 1. The i ndoor co il access panel will be used as the top of the hood. Rem o ...

  • Carrier 50TCQA - page 11

    11 NOTE: T rap should be deep enough to offset maximum unit static difference. A 4” (102) trap is recommended . MINIMUM PITCH 1” (25mm) PER 10’ (3m) OF LINE BASE RAIL OPEN VENT TO ROOF DRAIN DRAIN PLUG ROOF CURB SEE NOTE 2 ˝ (51) MIN C08022 Fi g. 14 - - Condensate Dr ain P i ping De ta il s All unit s mus t have an ex ternal trap f or conden ...

  • Carrier 50TCQA - page 12

    12 Un its wit h Factory- - Ins talled D iscon nect — The factory- - installed op tion dis connect sw itch is located in a weathe rproof enclosure loca ted under the m ain control box. The m anual sw itch handle is accessible through an opening in the access panel. Discard the factory tes t leads (see Fig. 16) . Units Without Disconnect Option Uni ...

  • Carrier 50TCQA - page 13

    13 Mount the weatherproof c over to t he backi ng pla te as sho wn in F ig. 18. Remove two s lot fillers in the bottom of the cove r to permit servic e tool cords to exit t he cover . Check f or full clos ing and latchin g. RECEPTACLE NOT INCLUDED COVER – WHILE-IN-USE WEATHERPROOF BASE PLATE FOR GFCI RECEPTACLE C09022 Fig. 18 - - W eatherproof Co ...

  • Carrier 50TCQA - page 14

    14 LOW VOL T AGE CONDUIT CONNECTOR HIGH VOL T AGE CONDUIT CONNECTOR C08637 Fig. 20 - - Thru- - Base Con nectio n Fittin gs Field - - suppli ed and fie ld - - i nstalle d liqui dtight conduit connec tors and conduit may be at tac hed to t he conne ctors on the bas epan. Pu ll correctly rated high voltag e and low voltage t hrough appropriat e condui ...

  • Carrier 50TCQA - page 15

    15 RACEW A Y HOLE IN END P ANEL (HIDDEN) C08027 Fig. 22 - - Fi eld Control Wiring Raceway El ectric H eaters 50TCQ units may be equippe d with fie ld - - insta lle d access ory electric heaters. The heaters a re modular in design, wit h heat er frame s holding open c oil re sistance wires s trung through ceramic in sulators, line - - break limit sw ...

  • Carrier 50TCQA - page 16

    16 TRACK FLANGE C08135 Fi g. 2 5 - - T y pic al M odul e Insta ll ati on Sing le Poi nt B oxe s and Suppl e me ntar y F uses — When the unit MO CP device value exceeds 60 - - A, unit- - mounted supplementary fuse s are required for each heater circuit. Thes e fuses ar e included in acces sory S ingle Point Boxes , with power distribut ion and fus ...

  • Carrier 50TCQA - page 17

    17 PremierLi nk t (Facto ry - - O pti on ) — C08199 Fig. 28 - - Premie rLink Controller The Premier Link contr oller (see F ig. 28 ) is compatib le with Car rier Comf ort Netw ork r ( CCN) dev ices. This contro l is designed to allow users the access and ability to change fact ory- - define d set tings, thus e xpanding t he function of t he stand ...

  • Carrier 50TCQA - page 18

    18 C09014 Fig. 30 - - PremierLin k W iring Sch ematic 50TCQA ...

  • Carrier 50TCQA - page 19

    19 Outdoor Air T e mpera ture (OA T) Sensor — T he OA T is fact ory- - mounte d in the EconoMi$er2 (FIOP or access ory) . It is a no minal 10k ohm ther mistor attached to an eyelet moun ting ring. EconoMi$er2 — T he PremierLi nk control is used w ith EconoMi$er2 (option or accessory) for outdoor air management. The damper position is contr olle ...

  • Carrier 50TCQA - page 20

    20 GJ 4 - 1 2 J4- 1 0 J4-8 Y1 Y2 2 R R 4 6 J4-6 J4-4 W2 C 8 10 C SP ACE THERMOST A T PL CTB THERMOST A T W1 TB1 CTB THERMOST A T C08119 Fig. 35 - - Space Th ermostat C onnect ions T ab le 3 – PremierL ink S ensor U sage APP LICATION OUTD OOR AIR TEMPERA TURE SEN SOR RETU RN AIR TEMPERA TURE SEN SOR OUTD OOR AIR EN THA LPY SE NSOR RETU RN AIR EN T ...

  • Carrier 50TCQA - page 21

    21 T abl e 4 – Space Se nsor M ode TB1 TERMINA L FIELD C ONNEC TION INPU T S IGNAL 1 T 5 5 --- S E N / T 5 6 --- S E N An alog (10k th erm istor) 2 RMTOC C Discrete, 24VAC 3 T 5 5 --- S E N / T 5 6 --- S E N An alog (10k th erm istor) 4 CMPS AF E Discrete, 24VAC 5 T56 - - - SET An alog (10k th erm istor) 6 FSD Discrete, 24VAC 7 L OOP - - - PW R A ...

  • Carrier 50TCQA - page 22

    22 If the 50 TCQ unit has an eco nomizer s ystem and free - - c ooling opera tion i s required, a sensor repre senting Return A ir T emperature mus t also be connected (field - - supplied and i nstall ed). T his s ensor may be a T - - 55 Space Sensor (see Fig. 31) insta lle d i n the space or in the return du ct, or it may be sens or PNO 33 ZCSEN S ...

  • Carrier 50TCQA - page 23

    23 8 7 6 5 4 32 1 2 1 HG 24 V AC OR 24 VDC NC ALARM RELA Y CONT ACTS COM NO } 0-10VDC SIG COM 4-20mA + + - + - J3 J4 C08635 Fig. 38 - - Indoor/Outdoor Air Quality (CO 2 )S e n s o r (33ZCSENC O2) - - T ypical Wiring Diagram T o accurately monitor th e quality o f the air in the conditio ned air sp ace, locate the senso r near a return- - air grille ...

  • Carrier 50TCQA - page 24

    24 On 50TCQ units equippe d with fact ory - - insta lled Smoke Detector (s) , the smoke detector co ntroller implemen ts the unit shutdown t hrough its NC conta ct set c onnect ed to the unit’ s CTB input. The FSD func tion is initiated via the smoke detec tor ’ s Alarm NO contact set . The Premie rLink communi cat es the smoke detector ’ s t ...

  • Carrier 50TCQA - page 25

    25 At any baud (9600, 19200, 38400 baud), the numbe r of contro llers is limited to 23 9 devices max imum. Bus leng th may not exceed 4000 ft, with no more than 60 total devic es on a ny 1000- - ft sect ion. Opti cal ly isolat ed RS- - 485 repea ters are re quired e very 1000 ft. NOTE : Ca rrier de vice de fault i s 9600 band. COMMU NICA TION BUS W ...

  • Carrier 50TCQA - page 26

    26 R TU - - MP contr ol system The R TU- - MP c ontrolle r , see Fig. 47, provides expanded stand - - al one operati on of the HV AC system plus connec tion and c ontrol t hrough communi cat ion with several Bui lding Automa tion System s (BAS) through popular thi rd - - part y network systems. T he availa ble network systems a re BACnet MP/TP , Mo ...

  • Carrier 50TCQA - page 27

    27 C09015 Fig. 49 - - RTU- - MP System Control W iri ng Diagram 50TCQA ...

  • Carrier 50TCQA - page 28

    28 T abl e 8 – RTU- - M P Cont roll e r Inputs and O utputs POI NT N AME BA Cnet O BJE CT NAME TYPE OF I/O CON NECTI ON PIN NUMB ERS INPU TS Space T em peratu re Sensor sptsens AI (10K T hermistor) J 2 0 --- 1 , 2 Supply Air T emperature sat AI (10K Thermistor) J2 - - - 1, 2 Loca l Outside Air T emper ature Sens or oatsens A I (10K Th ermistor) J ...

  • Carrier 50TCQA - page 29

    29 The raceway p rovid es the UL r equired clear ance betw een high - - and low- - volta ge wiring. Pass the control wires through the hol e provide d in the c orner post, t hen fee d the wires thorough the raceway to the R TU- - MP . Connect to the wire s to the rem ovable Phoenix c onnectors and t hen reconne ct the conne ctors to the board. Sp a ...

  • Carrier 50TCQA - page 30

    30 entha lpy sensor and the (SR) te rmina l on the e nthal py controll er . NOTE : The ent halpy control must be set t o the “ D” setting f or dif ferential enthalpy co ntrol to w ork pro perly . Indoor Air Quality (CO 2 sensor) — The indoor air quality sens or accesso ry monito rs sp ace carbon dio xide (CO 2 ) levels. This information is us ...

  • Carrier 50TCQA - page 31

    31 Remote Occ upancy The remote occup ancy access ory is a field- - installed access ory . This access ory ove rrides t he uno ccupied mode and put s the unit in occupied mode. When in stalling th is access ory , the unit mu st be configur ed for remote occupan cy by settin g MENU → Config → Inputs → input 3, 5, 8, or 9 to Rem ote Occupancy a ...

  • Carrier 50TCQA - page 32

    32 Loc al Access BACvie w 6 Handhel d The BA Cview 6 is a keypad/di splay inte rface used to connect to th e R TU- - MP to acces s the control inf ormation, read sensor values, and t est the R TU, see F ig. 57. This is an access ory inter face that does no t come with the MP controll er and c an only be used at the unit. Connect the BACview 6 to th ...

  • Carrier 50TCQA - page 33

    33 T able 9 – LEDs The LEDs on the R TU- - MP s how the s tatus of cer tain functio ns If th is LE D is on ... Statu s is... Power The R TU MP has power Rx The RTU MP is receiving data from the network segment Tx The R TU MP is tran smitting d ata over the n etwork segm ent DO# The digital output is active The Run and Error LEDs indicate contr ol ...

  • Carrier 50TCQA - page 34

    34 termi nal for c onnect ing to t he cont rolle r . Ea ch sensor has four LEDs (for Power , Trouble, Alarm and Dirty) and a manua l test/re set button (on the le ft - - side of the housing). Duct smoke sensor control ler Fast ener (2X) Cont rol ler co ver Conduit nuts (sup pli ed by instal ler ) Cond uit sup port pl ate Cover ga sket (ordering opt ...

  • Carrier 50TCQA - page 35

    35 dow nwar d, into the r eturn air s tream. The sampling tube is connec ted via t ubing to t he ret urn a ir sensor t hat i s mounted on a bracket high on the partition bet ween return filter and con troller locatio n. (This s enso r is ship ped in a flat - - mounting locat ion. Installat ion requi res t hat t his sensor be reloc ated to its opera ...

  • Carrier 50TCQA - page 36

    36 T abl e 10 – Uni t Wire/ M OCP Si z ing Da ta UNIT N O M . V --- P H --- H Z IFM TYPE ELECT RIC HEATER NO C.O. o r UNPWR D C.O . Nom (kW) FLA NO P .E. w/ P .E. (p wrd fr/u nit) MCA MO C P DISC. SIZ E MCA MO C P DISC. SIZ E FLA LRA FLA LRA 50TCQ *04 208/230 - - - 1 - - - 60 STD --- --- 30.7 45 30 121 32.6 50 32 123 3.3/4.4 15.9/18.3 50.6/53.6 6 ...

  • Carrier 50TCQA - page 37

    37 T abl e 10 — Uni t Wire/ M OCP Si z ing Da ta (c ont ) UNIT N O M . V --- P H --- H Z IFM TYPE ELECT RIC HEATER w/ PWRD C .O. Nom (kW) FLA NO P .E. w/ P .E. (p wrd fr/u nit) MCA MO C P DISC. SIZ E MCA MO C P DISC. SIZ E FLA LRA FLA LRA 50TCQ *04 208/230 - - - 1 - - - 60 STD --- --- 35.5 50 36 126 37.4 50 38 128 3.3/4.4 15.9/18.3 55.4/58.4 60/6 ...

  • Carrier 50TCQA - page 38

    38 T abl e 10 — Uni t Wire/ M OCP Si z ing Da ta (c ont ) UNIT N O M . V --- P H --- H Z IFM TYPE ELECT RIC HEATER NO C.O. o r UNPWR D C.O . Nom (kW) FLA NO P .E. w/ P .E. (p wrd fr/u nit) MCA MO C P DISC. SIZ E MCA MO C P DISC. SIZ E FLA LRA FLA LRA 50TCQ *05 208/230 - - - 1 - - - 60 STD --- --- 36.2 50 35 128 38.1 50 37 130 3.3/4.4 15.9/18.3 56 ...

  • Carrier 50TCQA - page 39

    39 T abl e 10 — Uni t Wire/ M OCP Si z ing Da ta (c ont ) UNIT N O M . V --- P H --- H Z IFM TYPE ELECT RIC HEATER w/ PWRD C .O. Nom (kW) FLA NO P .E. w/ P .E. (p wrd fr/u nit) MCA MO C P DISC. SIZ E MCA MO C P DISC. SIZ E FLA LRA FLA LRA 50TCQ *05 208/230 - - - 1 - - - 60 STD --- --- 41.0 60 41 133 42.9 60 43 135 3.3/4.4 15.9/18.3 60.8/63.8 70/8 ...

  • Carrier 50TCQA - page 40

    40 T abl e 10 — Uni t Wire/ M OCP Si z ing Da ta (c ont ) UNIT N O M . V --- P H --- H Z IFM TYPE ELECT RIC HEATER NO C.O. o r UNPWR D C.O . Nom (kW) FLA NO P .E. w/ P .E. (p wrd fr/u nit) MCA MO C P DISC. SIZ E MCA MO C P DISC. SIZ E FLA LRA FLA LRA 50TCQ *06 208/230 - - - 1 - - - 60 STD --- --- 41.7 60 40 145 43.6 60 43 147 4.9/6.5 23.5/27.1 71 ...

  • Carrier 50TCQA - page 41

    41 T abl e 10 — Uni t Wire/ M OCP Si z ing Da ta (c ont ) UNIT N O M . V --- P H --- H Z IFM TYPE ELECT RIC HEATER w/ PWRD C .O. Nom (kW) FLA NO P .E. w/ P .E. (p wrd fr/u nit) MCA MO C P DISC. SIZ E MCA MO C P DISC. SIZ E FLA LRA FLA LRA 50TCQ *06 208/230 - - - 1 - - - 60 STD --- --- 46.5 60 46 150 48.4 60 48 152 4.9/6.5 23.5/27.1 75.8/80.3 80/9 ...

  • Carrier 50TCQA - page 42

    42 T abl e 10 — Uni t Wire/ M OCP Si z ing Da ta (c ont ) UNIT N O M . V --- P H --- H Z IFM TYPE ELECT RIC HEATER NO C.O. o r UNPWR D C.O . Nom (kW) FLA NO P .E. w/ P .E. (p wrd fr/u nit) MCA MO C P DISC. SIZ E MCA MO C P DISC. SIZ E FLA LRA FLA LRA 50TCQ *07 208/230 - - - 3 - - - 60 STD --- --- 30.5 45 30 146 32.4 50 32 148 4.9/6.5 13.6/15.6 47 ...

  • Carrier 50TCQA - page 43

    43 T abl e 10 — Uni t Wire/ M OCP Si z ing Da ta (c ont ) UNIT N O M . V --- P H --- H Z IFM TYPE ELECT RIC HEATER w/ PWRD C .O. Nom (kW) FLA NO P .E. w/ P .E. (p wrd fr/u nit) MCA MO C P DISC. SIZ E MCA MO C P DISC. SIZ E FLA LRA FLA LRA 50TCQ *07 208/230 - - - 3 - - - 60 STD --- --- 35.3 50 35 151 37.2 50 37 153 4.9/6.5 13.6/15.6 52.3/54.8 60/6 ...

  • Carrier 50TCQA - page 44

    44 Legend and Notes for T able 10 LEG END: CO - - - Conve nie nt ou tl et DISC - - - Disconn ect FLA - - - Full load amp s IFM - - - Ind oor fan motor LRA - - - Locke d roto r amps MCA - - - Minimum cir cuit a mps MOC P - - - Maximu m over curr ent p ro tection P E --- P o w e r e x h a u s t UNP WR CO - - - Un p ower ed conv en ien t ou tlet NOT E ...

  • Carrier 50TCQA - page 45

    45 Step 12 — I n stal l Access ori es A vailable access ories includ e: Roof Curb Thru - - base c onnect ion kit (m ust be insta lle d before unit is set on c urb) Manual outside air da mper T wo- - Pos ition motor ized outsid e air damper EconoMi$er IV (with control and inte grate d barometric relie f) EconoMi$e r2 (without control/ for externa ...

  • Carrier 50TCQA - page 46

    46 50TCQA ...

  • Carrier 50TCQA - page 47

    47 50TCQA ...

  • Carrier 50TCQA - page 48

    48 Copyright 2009 Carrier Corp. D 7310 W . Morr i s St. D In dianapolis, IN 46231 Print ed in U.S.A. Edition Date: 02/10/09 Manufacturer reser ves the right to change , at any time, specifications and d esigns without notice and without ob ligations. Catal og No : 50TCQ - - - 01SI Replaces : NEW 50TCQA ...

Produzent Carrier Kategorie Heat Pump

Dokumente, die wir vom Produzenten des Geräts Carrier 50TCQA erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Carrier
- Bedienungsanleitungen 50TCQA
- Produktkarten Carrier
- Informationsbroschüren
- oder Energieetiketten Carrier 50TCQA
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Carrier 50TCQA.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Carrier 50TCQA, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Carrier 50TCQA. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Carrier 50TCQA ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Carrier 50TCQA, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Carrier 50TCQA hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Carrier 50TCQA verständlich ist.

Eine gänzliche Bedienungsanleitung von Carrier sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Carrier 50TCQA bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Carrier 50TCQA befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Carrier 50TCQA, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Carrier 50TCQA - die uns die ersten Schritte während der Nutzung von Carrier 50TCQA erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Carrier 50TCQA hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Carrier 50TCQA im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Carrier 50TCQA?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Carrier 50TCQA nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Carrier 50TCQA hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)