    TABLE 1—INTERMITTENT PILOT IGNITION MODULES. IGNITER- 100 SENSOR TYPE PREPURGE PERCENT LOCKOUT IGNITION MODEL TYPE OF GAS TIMING SHUTOFF TIMING SEQUENCE a S8600A, Separate Natural None No No Spark on until pilot S8610A lightoff or manual S8600F, Combination shutoff; pilot valve S8610F open until manual shutdown. S8600B, Separate Natural None Yes, ...

  • Honeywell S8670 - page 2

    2 CORROSIVE CHEMICALS Corrosive chemicals can also attack the module and gas control and eventually cause a failure. Where chemicals may be used routinely for cleaning, make sure the cleaning solution cannot reach the controls. Where chemicals are likely to be suspended in air, as in some industrial and agricultural applications, protect the igniti ...

  • Honeywell S8670 - page 3

    We recommend mounting the module with the terminals down to protect them from dripping water and dust. It can also be mounted with the terminals on either side. DO NOT MOUNT with terminals pointing up. Fasten securely with four No. 6-32 machine or No. 8 sheetmetal screws. MOUNT THE SYSTEM CONTROLS Mount any required controls, such as the gas contro ...

  • Honeywell S8670 - page 4

    4 Ground Control System The igniter, flame sensor and ignition module must share a common ground with the main burner. Use thermo- plastic insulated wire with a minimum rating of 105 ° C [221 ° F] for the ground wire; asbestos insulation is not accept- able. If necessary, use a shield to protect the wire from radiant heat generated by the burner. ...

  • Honeywell S8670 - page 5

    5 69-0463 Fig. 3 — S8600A,B; S8610A,B connections in a heating system with an atmospheric burner. Fig. 2 — S8600F,H,M; S8610F,H with a vent damper plug in a heating system with an atmospheric burner and a D80D vent damper. Q345, Q346, Q348, Q362, Q381 PILOT BURNER/ IGNITER-SENSOR L1 (HOT) L2 THERMO- STAT 1 LIMIT CONTROLLER 2 4 MV MV/PV PV GND ( ...

  • Honeywell S8670 - page 6

    Fig. 5 — S8600F,H,M; S8610F,H; S8660D; S8670D connections in a heating system with power-assisted combustion. Fig. 4 — S8600A,B; S8610A,B with vent damper pl u g in an atmospheric burner heating system with a D80D vent damper. 6 MV MV/PV PV GND (BURNER) 24V GND 24V TH-W VENT DAMPER PLUG SPARK 5 S8600A,B; S8610A,B POWER SUPPLY. PROVIDE DISCONNEC ...

  • Honeywell S8670 - page 7

    Fig. 6 — S8600F,H,M; S8610F,H; S8660D; S8670D connections in a heating system with a two-stage gas control and power-assisted combustion. 7 69-0463 5 MV MV/PV PV GND (BURNER) 24V GND 24V TH-W (OPT) VENT DAMPER PLUG (OPT) SPARK 5 S8600F,H,M; S8610F,H; S8660D; S8670D PILOT BURNER GROUND PILOT GAS SUPPLY Q345, Q346, Q348, Q362, Q381PILOT BURNER/ IGN ...

  • Honeywell S8670 - page 8

    Fig. 7 — S8600F,H,M; S8610F,H; S8660D; S8670D in a heating system with an atmospheric burner and a D80B vent damper. 8 LIMIT CONTROLLER 5 MV MV/PV PV GND (BURNER) 24V GND 24V TH-W (OPT) VENT DAMPER PLUG (OPT) SPARK 5 S8600F,H,M; S8610F,H; S8660D; S8670D 3 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. ALTERNATE LIMIT ...

  • Honeywell S8670 - page 9

    Fig. 8 — S8600F,H,M; S8610F,H; S8660D; S8670D connections in a heating-cooling system with power-assisted combustion. 9 69-0463 MV MV/PV PV GND (BURNER) 24V GND 24V TH-W (OPT) VENT DAMPER PLUG (OPT) SPARK 5 S8600F,H,M; S8610F,H; S8660D; S8670D POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. ALTERNATE LIMIT CONTROLLER L ...

  • Honeywell S8670 - page 10

    Fig. 9 — S8600F,H,M; S8610F, H; S8660D; S8670D connections in a hydronic heating sytem with a D80D vent damper. 10 2 MV MV/PV PV GND (BURNER) 24V GND 24V TH-W (OPT) VENT DAMPER PLUG (OPT) SPARK 4 S8600F,H,M; S8610F,H; S8660D; S8670D POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. CUT PLUG OFF MODULE END OF D80D WIRE HA ...

  • Honeywell S8670 - page 11

    Fig. 10 — S8600F,H,M; S8610F,H; S8660D; S8670D connections in a commercial water heater control system. 11 69-0463 CHECKOUT Check out the gas control system: • At initial installation of the appliance. • As part of regular maintenance procedures. Mainte- nance intervals are determined by the application. See PLANNING THE INSTALLATION, page 1, ...

  • Honeywell S8670 - page 12

    call for heat. ❏ Make sure pilot lights smoothly when gas reaches the pilot burner. ❏ Make sure main burner lights smoothly without flash- back. ❏ Make sure burner operates smoothly without floating, lifting, or flame rollout to the furnace vestibule or heat buildup in the vestibule. ❏ If gas line has been disturbed, complete gas leak test. ...

  • Honeywell S8670 - page 13

    13 69-0463 TRIAL FOR IGNITION Pilot Ignition Following prepurge timing (S8660, S8670), or on the call for heat (S8600, S8610), the module energizes the first main valve operator. The first main valve opens, which allows gas to flow to the pilot burner. At the same time, the electronic spark generator in the module produces an over 10,000 volt spark ...

  • Honeywell S8670 - page 14

    14 WARNING When performing the following steps, do not touch stripped end of jumper or SPARK terminal. The ignition circuit generates over 10,000 volts and electrical shock can result. ❏ Energize the module and immediately touch one end of the jumper firmly to the GND terminal on the module. Move the free end of the jumper slowly toward the SPARK ...

  • Honeywell S8670 - page 15

    15 69-0463 • Make sure electrical connections are clean and tight. Replace damaged wire with moisture-resistant No. 18 wire rated for continuous duty up to 105 ° C [221 ° F]. • Check for cracked ceramic insulator, which can cause short to ground, and replace igniter-sensor if neces- sary. • At the gas control, disconnect main valve wire fro ...

  • Honeywell S8670 - page 16

    Fig. 15 — S8660, S8670 troubleshooting guide. 16 Check continuity of ignition cable and ground wire. NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though operation is normal at the time of checkout. If checks are okay, replace module. M1173C START Check line voltage power, low voltage transformer, limit controller, the ...

  • Honeywell S8670 - page 17

    17 69-0463 Fig. 16 — Representative schematic for S8600F,H, M; S8610F,H. See Fig. 1 for hookup. S8660 and S8670 are similar except the timing circuit includes a purge timer. See Fig. 6 for hookup. L1 (HOT) L2 1 24V TRANSFORMER LIMIT CONTROLLER ON-OFF SWITCH 24V 2 THERMOSTAT OR CONTROLLER 24V (GND) SPARK DRIVE CIRCUIT 2K1 FLAME DETECTOR CIRCUIT RE ...

  • Honeywell S8670 - page 18

    Fig. 17 — Representative schematic for S8600A,B; S8610A,B. See Fig. 3 for hookup. 18 L1 (HOT) L2 1 24V TRANSFORMER LIMIT CONTROLLER ON-OFF SWITCH 24V 2 THERMOSTAT OR CONTROLLER 24V (GND) 1K1 1K2 3K2 2K2 3K1 GND (BUR- NER) MV/ PV MV PV IGNITER BURNER GROUND 1 2 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. ALTERNATE L ...

  • Honeywell S8670 - page 19

    19 69-0463 EXHIBIT A RECOMMENDED PROCEDURE FOR SAFETY INSPECTION OF AN EXISTING APPLIANCE INSTALLATION AS A PRELIMINARY STEP TO APPLYING AN AUTOMATIC INTERMITTENT PILOT SYSTEM The following procedure is intended as a guide to aid in determining that an appliance is properly installed and is in a safe condition for continuing use. This procedure is ...

  • Honeywell S8670 - page 20

    EXHIBIT B PROCEDURE FOR INSTALLING AUTOMATIC INTERMITTENT PILOT SYSTEMS Prior to beginning this procedure, a preliminary ex- amination of the appliance and the automatic intermit- tent pilot system should be made to determine that the automatic intermittent pilot system can be properly applied to the appliance. This procedure is intended as a guide ...

Produzent Honeywell Kategorie Water Pump

Dokumente, die wir vom Produzenten des Geräts Honeywell S8670 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Honeywell
- Bedienungsanleitungen S8670
- Produktkarten Honeywell
- Informationsbroschüren
- oder Energieetiketten Honeywell S8670
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Honeywell S8670.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Honeywell S8670, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Honeywell S8670. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Honeywell S8670 ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Honeywell S8670, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Honeywell S8670 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Honeywell S8670 verständlich ist.

Eine gänzliche Bedienungsanleitung von Honeywell sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Honeywell S8670 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Honeywell S8670 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Honeywell S8670, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Honeywell S8670 - die uns die ersten Schritte während der Nutzung von Honeywell S8670 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Honeywell S8670 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Honeywell S8670 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Honeywell S8670?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Honeywell S8670 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Honeywell S8670 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)