    Manual 2100-467 Page 1 of 23 SINGLE P ACKAGE AIR CONDITIONERS MODELS P A13241-A P A13301-A P A13361-A P A13361-B P A13421-A P A13421-B P A13481-A P A13481-B P A13601-A P A13601-B INST ALLA TION INSTRUCTIONS Manual : 2100-467 Supersedes: NEW File: V olume II T ab 10 Date: 03-03-06 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914 . . . Moving ...

  • Bard PA13601-A - page 2

    Manual 2100-467 Page 2 of 23 CONTENTS Getting Other Informations and Publications ........ 3 General Instructions Important ................................................................ 4 Shipping Damage .................................................... 4 General ................................................................ 4 Field Install ...

  • Bard PA13601-A - page 3

    Manual 2100-467 Page 3 of 23 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Electrical Code ...................... ANSI/NFP ...

  • Bard PA13601-A - page 4

    Manual 2100-467 Page 4 of 23 GENERAL INSTRUCTIONS IMPORTANT The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. All duct work, supply and return ducts, must be properly sized for the design air flow requirement of the equipment. ACCA is an excellent guide to proper sizing. All duct w ...

  • Bard PA13601-A - page 5

    Manual 2100-467 Page 5 of 23 TABLE 2 ELECTRICAL SPECIFICATIONS l e d o MA - 1 4 2 3 1 A PA - 1 0 3 3 1 A PA - 1 6 3 3 1 A PB - 1 6 3 3 1 A PA - 1 2 4 3 1 A PB - 1 2 4 3 1 A PA - 1 8 4 3 1 A PB - 1 8 4 3 1 A PA - 1 0 6 3 1 A PB - 1 0 6 3 1 A P – g n i t a R c i r t c e l E A t i u c r i C – z H 0 6 1 - 0 6 - 8 0 2 / 0 3 21 - 0 6 - 8 0 2 / 0 3 21 ...

  • Bard PA13601-A - page 6

    Manual 2100-467 Page 6 of 23 TABLE 3 OPTIONAL FIELD INSTALLED HEATER PACKAGES ONLY TO BE USED WITH THE MODELS INDICATED e g a k c a P r e t a e H l e d o M & s t l o V e s a h PA - 1 4 2 3 1 A PA - 1 0 3 3 1 A PA - 1 6 3 3 1 A PB - 1 6 3 3 1 A PA - 1 2 4 3 1 A PB - 1 2 4 3 1 A PA - 1 8 4 3 1 A PB - 1 8 4 3 1 A PA - 1 0 6 3 1 A PB - 1 0 6 3 1 A ...

  • Bard PA13601-A - page 7

    Manual 2100-467 Page 7 of 23 TABLE 4 OPTIONAL FIELD INSTALLED ELECTRIC HEATER TABLE r e t a e H e g a k c a P . o N l e d o M s t l o V t i n U s e s a h P y t i c a p a C & W K . r t H s t l o V 0 4 2 @ y t i c a p a C & W K . r t H s t l o V 8 0 2 @ V 8 0 2 / 0 4 2 . r t H s p m A r e t a e H l a n r e t n I t i u c r i C r e k a e r B B ...

  • Bard PA13601-A - page 8

    Manual 2100-467 Page 8 of 23 FIGURE 1 DIMENSIONS OF UNITS MIS-2142 Unit Dimension Chart Condenser air intake grille Condenser air intake grille Blower motor access door Condenser fan G 47 11/16" H Compressor access door Control panel door Heater package access panel Return opening Supply opening Drain access High voltage knockout Low voltage k ...

  • Bard PA13601-A - page 9

    Manual 2100-467 Page 9 of 23 INST ALLA TION LOCATION GENERAL The unit must be located outside, or in a well ventilated area. It must not be in the space being heated or cooled. A sound absorbing material should be considered if the unit is to be installed in such a position or location that might cause transmission of sound or vibration to the livi ...

  • Bard PA13601-A - page 10

    Manual 2100-467 Page 10 of 23 24" min. 36" min. 24" min. The distance between 1 inch clearance Air Inlet Air Inlet Supply and Return Ducts Building Heater Package Access Control Panel Access Blower Service Access Blower and Blower Motor Heater Package Control Panel Comp- ressor Nearest Structure Nearest Structure Nearest Structure Co ...

  • Bard PA13601-A - page 11

    Manual 2100-467 Page 11 of 23 FIGURE 4 ELEVATED MOUNTING PLATFORM 48" min. 32°F or lower climate 12" min. if in on surface of platform Both legs must rest 48" min. 32°F or lower climate 12" min. if in on surface of platform Both legs must rest Metal frame MIS-2144 Platform can be as shown or solid Poured concrete, brick, or bl ...

  • Bard PA13601-A - page 12

    Manual 2100-467 Page 12 of 23 FIGURE 5 CONDENSATE DRAIN TRAP 5. OTHER INSTALLATIONS – Many other installations are possible with the packaged air conditioner. No matter what the installation, always consider the following facts: A. Insure that the discharge air is not obstructed in any way so as to cause operation difficulties. B. The indoor coil ...

  • Bard PA13601-A - page 13

    Manual 2100-467 Page 13 of 23 TABLE 6 THERMOSTAT WIRE SIZE A V r e m r o f s n a r TA L Fe g u a G e r i W m u m i x a M e c n a t s i D t e e F n I 5 53 . 2 0 2 8 1 6 1 4 1 2 1 5 4 0 6 0 0 1 0 6 1 0 5 2 TRANSFORMER TAPS 230/208V, 1 phase and 3 phase equipment employ dual primary voltage transformers. All equipment leaves the factory wired on 240V ...

  • Bard PA13601-A - page 14

    Manual 2100-467 Page 14 of 23 HEAT ON UNITS WITH 15 OR MORE KW W MIS-2149 D1 DH W3 OR E2 Unit 24V Block Y C GR Y 1 B W1 W2 L E Y1 C GR W1 B Y2 R Terminal W2 W3 P L D E E L W2 B W1 R G C A1 Unit Control Panel G Y Y T8400C1313 Thermostat Subbase IF93-380 OR T8511G1070 REMOVE JUMPER FOR 2 STAGE ELECTRIC FIGURE 6 LOW VOLTAGE WIRING ...

  • Bard PA13601-A - page 15

    Manual 2100-467 Page 15 of 23 ST ART UP These units require R-410A refrigerant and polyolester oil. GENERAL: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A refrigerant. 3. Use manifold gauges rated for R-410A (800 psi/250 psi low). 4. R-410A is a binary blend of HFC ...

  • Bard PA13601-A - page 16

    Manual 2100-467 Page 16 of 23 THREE PHASE SCROLL COMPRESSOR START UP INFORMATION (PA1336, 42, 48 and 60 Models) Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction. ...

  • Bard PA13601-A - page 17

    Manual 2100-467 Page 17 of 23 HIGH PRESSURE SWITCH AND LOCKOUT SEQUENCE (Standard Feature) If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay-on- make time has expired. If the high pressur ...

  • Bard PA13601-A - page 18

    Manual 2100-467 Page 18 of 23 FAN BLADE SETTINGS Shown in Figure 8 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil. Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly. ...

  • Bard PA13601-A - page 19

    Manual 2100-467 Page 19 of 23 SUCTION AND DISCHARGE TUBE BRAZING Compliant Scroll compressors have copper plated steel suction and discharge tubes. These tubes are far more rugged and less prone to leaks than copper tubes used on other compressors. Due to different thermal properties of steel and copper, brazing procedures may have to be changed fr ...

  • Bard PA13601-A - page 20

    Manual 2100-467 Page 20 of 23 TROUBLESHOOTING GE ECM ™ MOTORS CAUTION: Disconnect power from unit before removing or replacing connectors, or servicing motor. To avoid electric shock from the motor’s capacitors, disconnect power and wait at least 5 minutes before opening motor. Symptom Cause/Procedure Motor rocks slightly • This is normal sta ...

  • Bard PA13601-A - page 21

    Manual 2100-467 Page 21 of 23 Motor Motor OK wh en R > 100k oh m ECM 2.0 Only re move Hex Head Bolt s Connector Orientation Between 4 and 8 o'clock Drip Loop Back of Control Figure 5 Winding Test Figu re 4 Note: Use the shorter bolts and ali gnment pin supplied w hen repla cing an ECM 2. 0 con tro l. Figur e 3 ECM 2.3/2.5 Power Connect or ( ...

  • Bard PA13601-A - page 22

    Manual 2100-467 Page 22 of 23 (Continued on Page 23 in Table 12) l e d o M r i A n r u t e R e r u t a r e p m e T e r u s s e r P° 5 6° 0 7° 5 7° 0 8° 5 8° 0 9° 5 9° 0 0 1° 5 0 1° 0 1 1° 5 1 1° 0 2 1° 5 2 1 4 2 3 1 A P 5 7 ° B D 2 6 ° B W e d i S w o L e d i S h g i H 2 2 1 0 5 2 5 2 1 9 6 2 8 2 1 9 8 2 0 3 1 0 1 3 3 3 1 2 3 3 6 3 1 ...

  • Bard PA13601-A - page 23

    Manual 2100-467 Page 23 of 23 TABLE 12 PRESSURE TABLE COOLING Air T emperature Entering Outdoor Coil Degree F LOW SIDE PRESSURE +2 PSIG HIGH SIDE PRESSURE +5 PSIG l e d o M r i A n r u t e R e r u t a r e p m e T e r u s s e r P° 5 6° 0 7° 5 7° 0 8° 5 8° 0 9° 5 9° 0 0 1° 5 0 1° 0 1 1° 5 1 1° 0 2 1° 5 2 1 2 4 3 1 A P 5 7 ° B D 2 6 ° B ...

Produzent Bard Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts Bard PA13601-A erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Bard
- Bedienungsanleitungen PA13601-A
- Produktkarten Bard
- Informationsbroschüren
- oder Energieetiketten Bard PA13601-A
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Bard PA13601-A.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Bard PA13601-A, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Bard PA13601-A. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Bard PA13601-A ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Bard PA13601-A, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Bard PA13601-A hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Bard PA13601-A verständlich ist.

Eine gänzliche Bedienungsanleitung von Bard sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Bard PA13601-A bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Bard PA13601-A befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Bard PA13601-A, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Bard PA13601-A - die uns die ersten Schritte während der Nutzung von Bard PA13601-A erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Bard PA13601-A hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Bard PA13601-A im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Bard PA13601-A?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Bard PA13601-A nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Bard PA13601-A hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)