    261660-YTG-D-0708 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE TECHNICAL GUIDE SINGLE P ACKAGE GA S/ELECTRIC UNITS AND SINGLE P ACKAGE AIR CONDITIONERS DJ 180, 210, 240 & 300 15 & 25 NOMINAL TONS 12.00 EER (15 TONS), 1 1.70 EER (17.5 TONS), 1 1.3 EER (20 TONS), 10.5 EER (25 TONS) ® DESCRIPTION YORK Sunline Magnum™ u ...

  • York DJ 300 - page 2

    261660-YTG-D-0708 2 Johnson Controls Unitary Products T ABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMEN CLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 5 FIELD-INSTALLED ...

  • York DJ 300 - page 3

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 3 PRODUCT NOMENCLA TURE D J 180 N24 A 2 A AA 1 0 1 2 4 A D = A/C, Single Pkg., R-22 Product Category A = Std. Drive Airflow B = Std. Drive/Single Input Econo. C = Std. Drive/Single Input Econo./Pow er Exhaust (Downflow Only) D = Std. Drive/Motorized Damper E = Std. Drive/Motorized Damper/Barometr ...

  • York DJ 300 - page 4

    261660-YTG-D-0708 4 Johnson Controls Unitary Products FEA TURES All models are available with a wide variety of factory- mounted options such as stainless steel he at exchange rs, phase monitor, dirty filter switch , and coil gua rd to make them suitable for almost every app lication. All units are self-contained and assembled on fu ll peri meter b ...

  • York DJ 300 - page 5

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 5 with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards. The gas supply piping can be routed into the heating compartment through ...

  • York DJ 300 - page 6

    261660-YTG-D-0708 6 Johnson Controls Unitary Products V A V , power exhaust is energized by means of a binary out- put signal from the unit's V A V control board. The exhaust fa n, motor and controls ar e installed and wired at the factory . The rain hood must be assembled and inst alled in the field. The power exhaus t option can only be used ...

  • York DJ 300 - page 7

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 7 uses an inside CO 2 sensor to perform Deman d V entila- tion. It can also use an Out side CO 2 se nsor to perform Dif- ferential Demand V entilation. It uses a Patented Comfort V entilation algorithm to provide comfort able ve ntilatio n air temperature. The patented economizer-loadi ng alg ori ...

  • York DJ 300 - page 8

    261660-YTG-D-0708 8 Johnson Controls Unitary Products FIELD-INST ALLED ACCESSORIES • SINGLE INPUT ELECTR ONIC ENTHALPY ECONO- MIZERS - Includes a slide-in / plug-in damper a ssembly with fully modulating spring-return motor actuator capa- ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system co ntains ...

  • York DJ 300 - page 9

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 9 NOTE: All gas units are two-stage heating. First stage is 50% of total. S.S.E. = S teady S t ate Ef ficienc y (80%) - output divided by input. T ABLE 1: S OUND POWER RA TING 1 UNIT SIZE CFM ESP BLOWER SOUND POWER (db 10 -12 Wa t ts ) Octave Band Centerline Frequency (Hz) SWL dB(A) dB(A) @ 10Ft. ...

  • York DJ 300 - page 10

    261660-YTG-D-0708 10 Johnson Controls Unitary Products T ABLE 4: C OOLING CAP ACITIE S FOR DJ180 Air on Evaporator Coil Temperature of Air on Condenser Coil 85°F 95°F CFM WB (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Sensible Capacity (MBH) * Return Dry Bulb (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Sensible Capacity (MBH) * Return Dry Bulb (? ...

  • York DJ 300 - page 11

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 11 T ABLE 5: C OOLING CAP ACITIE S FOR DJ210 Air on Evaporator Coil Temperature of Air on Condenser Coil 85°F 95°F CFM WB (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Sensible Capacity (MBH) * Return Dry Bulb (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Sensible Capacity (MBH) * Return Dry Bulb ( ...

  • York DJ 300 - page 12

    261660-YTG-D-0708 12 Johnson Controls Unitary Products T ABLE 6: C OOLING CAP ACITIE S FOR DJ240 Air on Evaporator Coil Temperature of Air on Condenser Coil 85°F 95°F CFM WB (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Sensible Capacity (MBH) * Return Dry Bulb (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Sensible Capacity (MBH) * Return Dry Bulb (? ...

  • York DJ 300 - page 13

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 13 T ABLE 7: C OOLING CAP ACITIE S FOR DJ300 Air on Evaporator Coil Temperature of Air on Condense r Coil 85°F 95°F CFM WB (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Sensible Capacity (MBH) * Return Dry Bulb (°F) Total Cap. 1 (MBH) Total 2 Input (kW) Sensible Capacity (MBH) * Return Dry Bulb ...

  • York DJ 300 - page 14

    261660-YTG-D-0708 14 Johnson Controls Unitary Products CFM, ST ATIC PRESSURE, AND POWER - ALTI- TUDE AND T EMPERATURE CORRECTIONS The information below should b e used to assist i n applicatio n of product when being ap plied at altitudes at or exceeding 1000 feet above sea level. The air flow rates listed in the standard blower pe rformance tables ...

  • York DJ 300 - page 15

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 15 FIGURE 2 - AL TITUDE/TEMPERA TURE CONVER SION F ACTOR ...

  • York DJ 300 - page 16

    261660-YTG-D-0708 16 Johnson Controls Unitary Products NOTES: 1. Blower performance includes fixed out door air , 2” T/A filters, a dry evaporator coil and no electric heat. 2.Refer to T a ble 13 for addition al st atic resistances. ESP = External S tatic Pressure available for the supply and re turn air du ct system. All internal unit resistance ...

  • York DJ 300 - page 17

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 17 NOTES: 1. Blower performance includes fixed out door air , 2” T/ A filters, a dry evaporat or coil and no electric heat. 2.Refer to T able 13 for addit ional stati c resistances. ESP = External S tatic Pressure available fo r the supply and r eturn air duct system . All internal unit resist ...

  • York DJ 300 - page 18

    261660-YTG-D-0708 18 Johnson Controls Unitary Products NOTES: 1. Blower performance includes fixed out door air , 2” T/A filters, a dry evaporator coil and no electric heat. 2.Refer to T a ble 13 for addition al st atic resistances. ESP = External S tatic Pressure available for the supply and re turn air du ct system. All internal unit resistance ...

  • York DJ 300 - page 19

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 19 NOTES: 1. Blower performance includes a gas-fire d heat exchanger , fi xed outdoor air , two-inch T/A filt er s and a dry evaporator co il. 2.Refer to the additional S tatic Resistances t able. ESP = External S tatic Pressure available fo r the supply and r eturn air duct system . All internal ...

  • York DJ 300 - page 20

    261660-YTG-D-0708 20 Johnson Controls Unitary Products NOTES: 1. Blower performance includes a gas-fire d heat exchanger , fi xed outdoor air , two-inch T/A fil ters and a dry evaporator co il. 2.Refer to the additional S tatic Resistances t able. ESP = External S tatic Pressure available for the supply and re turn air du ct system. All internal un ...

  • York DJ 300 - page 21

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 21 NOTES: 1. Blower performance includes a gas-fire d heat exchanger , fi xed outdoor air , two-inch T/A filt er s and a dry evaporator co il. 2.Refer to the additional S tatic Resistances t able. ESP = External S tatic Pressure available fo r the supply and r eturn air duct system . All internal ...

  • York DJ 300 - page 22

    261660-YTG-D-0708 22 Johnson Controls Unitary Products NOTES: 1. Blower performance includes a gas-fire d heat exchanger , fi xed outdoor air , two-inch T/A fil ters and a dry evaporator co il. 2.Refer to the additional S tatic Resistances t able. ESP = External S tatic Pressure available for the supply and re turn air du ct system. All internal un ...

  • York DJ 300 - page 23

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 23 T ABLE 16: BLOWER MOTOR AND DRIVE DA T A MODEL SIZE DRIVE BLOWER RANGE (RPM) MOTOR 1 ADJUS T ABLE MOTOR PULLEY FIXED BLOWER PULLEY BEL T (NOTCHED) HP FRAME EFF . (%) DESIG- NA TION OUTSIDE DIA. (IN.) PITCH DIA. (IN.) BORE (IN.) DESIG- NA TION OUTSIDE DIA. (IN.) PITCH DIA. (IN.) BORE (IN.) DESI ...

  • York DJ 300 - page 24

    261660-YTG-D-0708 24 Johnson Controls Unitary Products NOTE 1: HACR T ype per NE C. T ABLE 19: DJ ELECTRICAL D A T A WI THOUT POWERED CONVENIENCE OUTLET MODEL (TON- NAGE) VOL T AGE COMPRESSORS OD F AN MOTORS FLA EACH ID BLOWER MOTOR FLA CONV OUTLET AMPS HEA TER OPTION MIN. CIRCUIT AMP ACITY (AMPS) MAX. FUSE/ BRKR 1 SIZE (AMPS) RLA EACH LRA EACH MOD ...

  • York DJ 300 - page 25

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 25 NOTE 1: HACR T ype per NE C. T ABLE 19: DJ ELECTRICAL D A T A WITHOU T POWERED CONVENIENC E OU TLET (CONTINUED) MODEL (TON- NAGE) VOL T AGE COMPRESSORS OD F AN MOTORS FLA EACH ID BLOWER MOTOR FLA CONV OUTLET AMPS HEA TER OPTION MIN. CIRCUIT AMP ACITY (AMPS) MAX. FUSE/ BRKR 1 SIZE (AMPS) RLA EA ...

  • York DJ 300 - page 26

    261660-YTG-D-0708 26 Johnson Controls Unitary Products NOTE 1: HACR T ype per NE C. T ABLE 20: DJ ELECTR ICAL DA T A WITH POWERED CONVENIENCE OUTLET MODEL (TON- NAGE) VOL T AGE COMPRESSORS OD F AN MOTORS FLA EACH ID BLOWER MOTOR FLA CONV OUTLET AMPS HEA TER OPTION MIN. CIRCUIT AMP ACITY (AMPS) MAX. FUSE/ BRKR 1 SIZE (AMPS) RLA EACH LRA EACH MODEL K ...

  • York DJ 300 - page 27

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 27 NOTE 1: HACR T ype per NE C. T ABLE 20: DJ ELECTRICAL DA T A WITH PO WERED CONVENIENCE OUTLET (CONTINUED) MODEL (TON- NAGE) VOL T AGE COMPRESSORS OD F AN MOTORS FLA EACH ID BLOWER MOTOR FLA CONV OUTLET AMPS HEA TER OPTION MIN. CIRCUIT AMP ACITY (AMPS) MAX. FUSE/ BRKR 1 SIZE (AMPS) RLA EACH LRA ...

  • York DJ 300 - page 28

    261660-YTG-D-0708 28 Johnson Controls Unitary Products T ABLE 21: DJ VOL T AGE LIMIT A TION S 1 1. Utilization Range “A” in accorda nce with ARI S tandard 1 10. V O LTA G E L I M I TAT I O N S POWER SUPPL Y VOL T AGE MIN. MAX. VOL T AGE LIMIT A TIONS 208/230-3-60 187 253 460-3-60 414 506 575-3-60 518 630 T ABLE 22: PHYS ICAL DATA MODELS DJ180 D ...

  • York DJ 300 - page 29

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 29 T ABLE 23: SUP PLY FAN VFD WEIGHTS, IN LBS. SUPPL Y F AN MOTOR 230V 460V 575V W/O MANUAL BYP ASS 5.0 hp 25 25 30 7.5 hp 30 30 30 10.0 hp 30 30 35 15.0 hp 30 30 40 W/MANUAL BYP ASS 5.0 hp 30 30 35 7.5 hp 35 35 35 10.0 hp 35 35 40 15.0 hp 40 35 45 T ABLE 24: ELECTR IC HEA T CORREC TION FA C T O ...

  • York DJ 300 - page 30

    261660-YTG-D-0708 30 Johnson Controls Unitary Products FIGURE 4 - FRONT VIEW DIMENSIONS T ABLE 25: UTILITIES ENTRY DA T A HOLE OPENING SIZE (DIA.) USED FOR A 1-1/8” KO Control Wiring Side 3/4” NPS (Fem.) Bottom B 3-5/8” KO Power Wiring Side 3” NPS (F em.) Bottom C 2-3/8” KO Gas Pipi ng (Fron t) 1 1. One-inch gas piping NPT requ ired. D 1- ...

  • York DJ 300 - page 31

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 31 FIGURE 5 - REAR VIEW DIMENSIONS NOTE: Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts. For bottom duct application s: 1. Remove the side p anels from the supply and return air compartments to gain access to the bottom supp ...

  • York DJ 300 - page 32

    261660-YTG-D-0708 32 Johnson Controls Unitary Products NOTE: ELEC / ELEC Models : Units and ductwork are approved for zero clearance to combustible material when equipped with electric heaters. GAS / ELEC Models : A 1” clearance must be provided between any combu stible material and the supply air ductwork for a distance of 3 feet from the unit. ...

  • York DJ 300 - page 33

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 33 FIGURE 7 - UNIT CENTER OF GRA VITY FIGURE 8 - T YP ICAL UNIT APPLICATIONS ROOF JA CK INSTALLATIO N ROOF CUR B INSTALLATIO N SLAB ON GROUND INSTALLATION ...

  • York DJ 300 - page 34

    261660-YTG-D-0708 34 Johnson Controls Unitary Products FIGURE 9 - FOUR AND SIX POINT LOADS A D C E B F A D B C T ABLE 27: FOUR AND SIX POINT LOADS 180 Gas 2660 454 847 885 474 210 Gas 2928 510 954 954 510 240 Gas 2960 516 964 964 516 300 Gas 3046 531 992 992 531 180 Elec 2460 419 784 819 438 210 Elec 2728 476 888 888 476 240 Elec 2760 481 899 899 4 ...

  • York DJ 300 - page 35

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 35 1. The 2” space between the ducts allows for “jumping” an existing roof joist. 2. The 58-1/2” overall dimension of the ducts allows duct- work penetration between roof joists that are spaced on 72” centers. Note: Ducts can be installed into the curb from the roof. All electrical and ...

  • York DJ 300 - page 36

    261660-YTG-D-0708 36 Johnson Controls Unitary Products FIGURE 13 - TYPICAL SIMPLICITY ® WIRING DIAGRAM W1 W2 Y1 G OCC P P1 Y2 X R SD C C SD SD R OCC C RC G Y2 Y1 W2 W1 Jumper Smoke Detector 24 VAC Class 2 X R THERMOSTAT TERMINALS CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required o ...

  • York DJ 300 - page 37

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 37 GUIDE SPECIFICA TIONS GENERAL Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. York's Sunline Magn u m ™ un i ts ar e con v e rti b l e si ng l e pa ck- age units. All models have dual independent refri gerant cir- cuits for eff ...

  • York DJ 300 - page 38

    261660-YTG-D-0708 38 Johnson Controls Unitary Products OUTDOOR (CONDENSER) F AN ASSEMBL Y The outdoor fans shall be of the direct-d ri ven propeller type, discharge air vertically, have aluminum blades riveted to cor- rosion resistant steel spider brackets and shall be dynami- cally balanced for smooth operation. The 4 outd oor fan motors shall be ...

  • York DJ 300 - page 39

    261660-YTG-D-0708 Johnson Controls Unitary Produ cts 39 ELECTRIC HEA TING (DJ***C/E MODELS) Nickel chromium electric h eatin g elements shall be provided as required by the application with 1 or 2 stage control, as required, from 13.5 KW to 72 KW capacities. The heating section shall have a primary lim it control(s) and automa tic reset to prevent ...

  • York DJ 300 - page 40

    Subject to change without notice. Pr inted in U.S.A. 261660-YTG-D-0708 Copyright © 2008 b y Johnson Controls, Inc. All rights reserved. Supersedes: 261660-YTG-C-07 07 Johnson Contro ls Unitary Products 5005 York Drive Norman, OK 73069 • PROP ANE CONVERSION KIT - Cont ains new orifices and gas valve parts to convert from natural to L.P . gas. One ...

Produzent York Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts York DJ 300 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen York
- Bedienungsanleitungen DJ 300
- Produktkarten York
- Informationsbroschüren
- oder Energieetiketten York DJ 300
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung York DJ 300.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen York DJ 300, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen York DJ 300. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts York DJ 300 ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts York DJ 300, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von York DJ 300 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von York DJ 300 verständlich ist.

Eine gänzliche Bedienungsanleitung von York sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von York DJ 300 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von York DJ 300 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich York DJ 300, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts York DJ 300 - die uns die ersten Schritte während der Nutzung von York DJ 300 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit York DJ 300 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von York DJ 300 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich York DJ 300?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit York DJ 300 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit York DJ 300 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)