    990-1054 A , 08 /01 User’s Manual English APC Smart-UPS ® 2200VA /3000VA 3U Rack M ount Uninterr uptible Pow er Supply 230VA C/120VA C ...

  • APC 3000VA - page 2

    ...

  • APC 3000VA - page 3

    1 1: S AF E T Y I NFORMA TION Am erican Power Conversion Corporation (APC) is the leading n ational and international manu fac- turer of sta te-of-the -art uninterr upti ble p ower sup plie s, re dunda nt switches, p ower management so ft- w are, and related equi pment. A PC products prot ect hardw are, softw are, and data f rom th e threat of powe ...

  • APC 3000VA - page 4

    2 anesthesia ven tilators, infusion pumps, an d any other device designated as “critical” by the U.S.F.D.A. Hospital grade w iring dev ices and leakage cu rrent may be ordered as options on man y APC UPS system s, APC does not claim that units w ith this m odification are certified or listed as Hospital Grade by A PC or any oth er organization. ...

  • APC 3000VA - page 5

    3 B ATTERY S AFETY This equipm ent contains potentially hazardou s voltages that m ay cause pers onal injury if handled incorrectly. This equipm ent m ust be installed and serviced only by qualified electrical service personnel. n This equipm ent contains poten tially hazardous voltages. Do not attem pt to disassemble th e unit. The only ex ception ...

  • APC 3000VA - page 6

    4 2: I NST A LLA TION The UPS has a “rack” des ign so it can be m ounted in a 19-inch (46.5 cm ) equipm ent rack. Hardw are is provi ded. U NPACKING 1. Inspect the UPS upon receipt. APC design ed robust packag ing for y our product. How ever, acci- dents an d damage m ay occu r during sh ipment. Notif y the carrier an d dealer if there is dam a ...

  • APC 3000VA - page 7

    5 5. Connect th e battery and attach th e front bezel. 6. Connect th e equipmen t and power to th e UPS. 7. Turn on th e UPS. I NSTALLIN G THE M OUNTING R AILS I N THE R ACK Install the m ounting rails in th e rack. Directions are included w ith the rail kit. The UPS comes w ith standard 19- inch (46.5 cm ) rack moun ting rails, brackets , and clea ...

  • APC 3000VA - page 8

    6 3. Locate the battery m odule handle at the top of the battery f ace plate  . 4. Be careful during th is step—the battery module is heavy . Pull the battery m odule handle toward y ou to slide the battery m odule out of the UPS. DO NOT pull on the battery cables or the wh ite cord. M OUNTING THE UPS IN THE R ACK Due to its w eight, two peopl ...

  • APC 3000VA - page 9

    7 C ONNECTING THE B AT TERY AND A TTACHING THE F RONT B EZEL 1. Facing the f ront of the UPS, locate the battery cables  and the UPS battery connector jack  to the right of th e battery m odule. 2. To connect the battery connector plug  to the battery jack, push the plu g into the jack so the metal pieces inside each part are touch ing. Pr ...

  • APC 3000VA - page 10

    8 4. Turn on all conn ected equipmen t (loads). To use the UPS as a m aster ON/OFF sw itch, be sure all connected loads are switched on. The loads will n ot be p owered un til the UPS is turned on. 5. Add any optional accessories. See th e documen tation accompany ing th e accessory f or details. T URNING ON THE UPS Make sure th e battery is conn e ...

  • APC 3000VA - page 11

    9 3: O PER A TION I NDICATORS A ND C ONTROLS ON THE S MART -U PS The APC Un interru ptible Pow er Supply (UPS) is des igned to prev ent blackou ts, brow nouts , sags an d surges from reaching y our computer an d other valuable electronic equipmen t. T he UPS filters out small u tility line flu ctuations and isolates your equipmen t from large distu ...

  • APC 3000VA - page 12

    10 S ELF -T EST Automatic Self-Test The UPS performs a s elf-test au tomatically when turned on, and ev ery tw o week s thereafter (by def ault). Refer to the User Configurati on Items for details on changing the default interval. Autom atic self-test eases m aintenance requiremen ts by elimin ating the need for periodic manual self -tests. During ...

  • APC 3000VA - page 13

    11 Voltage Trim This LED illumin ates to indicate the UPS is co mpensatin g for a high util- ity v oltage. Voltage Boost This LED illumin ates to indicate the UPS is co mpensatin g for a low utility volta ge. B ATTERY P OWER If the utility power fails, th e UPS can provide p ower to the conn ected equipment from its internal battery f or a finite p ...

  • APC 3000VA - page 14

    12 S MAR T -UPS R EAR P ANEL The rear panel has the input and output conn ectors, computer interface port, and default setting bu t- tons for the low battery w arning level an d voltage sensitivity in dicator. 120V Models 230V Models B ASIC C ONNE CTORS Computer Interface Port Power m anagem ent softw are and interf ace kits can be us ed with the U ...

  • APC 3000VA - page 15

    13 To red uce UPS sensitivity , press the voltag e sensitivity button. Use a pointed object (su ch as a pen) to do so. Press th e button once to set sensitivity to reduced . Press it again to set sensitivity to low . Press the button a third time to reset normal sensitivity. You also ca n change the sensitivity level thr ough software. norm a l red ...

  • APC 3000VA - page 16

    14 O N -B A TTERY O PERATION The Smart-UP S switches to battery oper ation auto matically if the utility power fails. W hile running on-battery , an internal alarm sounds (periodic beeps). Pre ss the button (f ront panel) to silen ce the UPS alarm (for th e current alarm only). You can change th e audible indicator if y ou are using the PowerChu te ...

  • APC 3000VA - page 17

    15 4: U SER C ONFIGU RA TION I TEMS N OTE : S ET TING T HESE ITEMS REQU IRES SOFTWA RE OR O PTIONA L HA RDWA RE . F UNCTION F ACTORY D EFAULT U SER S ELECTABL E C HOICES D ESCRIPTION Autom atic Self- Tes t Every 14 days (336 hours ) Every 7 days (168 hours ), On Startup Only , No S elf-T est This function sets the interv al at which the UPS will ex ...

  • APC 3000VA - page 18

    16 N OTE : S ET TING T HESE ITEMS REQU IRES SOFTWA RE OR O PTIONA L HA RDWA RE . F UNCTION F ACTORY D EFAULT U SER S ELECTABL E C HOICES D ESCRIPTION High Transfer Point 120V Models 132 VAC 230V Models 253 VAC 120V Models 138, 135, 129 VAC 230V Models 264, 271, 280 VAC To avoid unnecess ary battery usage, set the high tr ansfer po int higher if the ...

  • APC 3000VA - page 19

    17 5: S T ORAGE A ND M A INTENA NCE S TORAG E S TORAGE C ONDITIONS Store the UPS covered and flat (rack mou nt orientation) in a cool, dry location, with its batteries fully charged. Disconnect any cables connected to the computer interface port to avoid unnecessary bat- tery dr aina ge. E XTENDED S TORAGE At - 15 to +30 ° C (+5 to +86 ° F), char ...

  • APC 3000VA - page 20

    18 6: T RA NSPORTING Y OUR S MA RT -UPS R EMOVING THE UPS FROM THE R AC K Always DIS CONNECT T HE BATTE RY before ship ping the UPS to avoi d dam age durin g transport. (U.S. Federal Regulation requires that batteries are disconnected during shipment.) The battery may rem ain in the UPS; it does not hav e to be re- m oved. This requirem ent applies ...

  • APC 3000VA - page 21

    19 7: T ROUBLESHOOTING Use the chart below to solve m inor UPS installation prob lems. A lso refer to the APC web site. Con- tact APC for ass istance w ith complex UPS problem s. P ROBLEM A ND P OSSIBLE C AUS E S OLUTION UPS WILL NOT TURN ON ON button not pushe d. Press the ON button once t o power the UPS and the load. UPS not conne cted to AC pow ...

  • APC 3000VA - page 22

    20 P ROBLEM A ND P OSSIBLE C AUS E S OLUTION A LL INDICATORS ARE L IT AND THE UPS EMITS A CONSTANT BEEPING Int ernal UPS fault. Do not at tempt to use t he UPS. T urn the UPS off and have it serviced immediately. A LL INDICATORS ARE OF F AND THE UPS IS PLUGGED INTO A WALL OUTLET The UPS is shut down a nd the bat- tery is di scharged fr om an ex ten ...

  • APC 3000VA - page 23

    21 S ERVICE If the un it requires service, do not return it to the dealer. Instead, follow these steps: 1. Review th e problems di scussed i n the Troubl eshooting section of this m anual to eliminate com - mon problems . 2. Verify that no circuit breakers are tripped. A tripped circuit breaker is th e most com mon problem . 3 . I f t h e p r o b l ...

  • APC 3000VA - page 24

    22 8: C ONT A CT , R EGULA TOR Y , A ND W A RRA NTY I NFORMA T ION C ONTACTING AP C Refer to the inform ation provided at the APC Internet site: ht t p :/ / www. a p c. c o m/ s u pport/contact R EGULATORY A GENCY A PPROVALS 230V M ODEL S This is a Class A product. In a dom estic env ironmen t this product m ay caus e radio interferen ce, in wh ich ...

  • APC 3000VA - page 25

    23 D ECLARA TION OF C ONFORMITY L IMITED W ARRA NTY Am erica n Po we r Convers ion (APC) w arrants its products to be f ree f rom def ects in m ateri als and w orkma nship for a period of tw o yea rs from the date of purchase . Its obligation unde r this wa rranty is limited to re pairing or replac ing, at its ow n sole option, any such def ective ...

Produzent APC Kategorie Power Supply

Dokumente, die wir vom Produzenten des Geräts APC 3000VA erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen APC
- Bedienungsanleitungen 3000VA
- Produktkarten APC
- Informationsbroschüren
- oder Energieetiketten APC 3000VA
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung APC 3000VA.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen APC 3000VA, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen APC 3000VA. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts APC 3000VA ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts APC 3000VA, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von APC 3000VA hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von APC 3000VA verständlich ist.

Eine gänzliche Bedienungsanleitung von APC sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von APC 3000VA bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von APC 3000VA befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich APC 3000VA, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts APC 3000VA - die uns die ersten Schritte während der Nutzung von APC 3000VA erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit APC 3000VA hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von APC 3000VA im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich APC 3000VA?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit APC 3000VA nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit APC 3000VA hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)