Bedienungsanleitung Carrier PREMIERLINK 33CSPREMLK

44 Seiten 2.24 mb
Download

Zur Seite of 44

Summary
  • Carrier PREMIERLINK 33CSPREMLK - page 1

    Manufactu rer reser ves the rig ht to dis continue , or chan ge at a ny time, spec ificat ions or des igns without notice an d withou t inc urring obligations. PC 111 Catalog No . 533-8 0072 Pr inted in U.S .A. Form 3 8-54SI Pg 1 11-0 2 Replaces : 38-52 SI Book 1 4 Ta b 3 a 2 a Installation, Star t-Up and Configur ation Instr uctions P ar t Number ...

  • Carrier PREMIERLINK 33CSPREMLK - page 2

    2 Carrier ’ s diagnostic standard tier display tools such as Navigator or Scrolling Marquee can be used with t he Premier- Link controller . A cce ss is available via an RJ-11 connection or a 3-wire connection to the communication bus. User interfac es available for use with the CCN system are PC ’ s equipped with Carrier user interface softwar ...

  • Carrier PREMIERLINK 33CSPREMLK - page 3

    3 PremierLink Contr oller Inputs and Outputs — The PremierLink controller inputs and outputs are shown in T able 1. Contr ol Wiring — The PremierLi nk controller can be connected to either a Carrier-approved therm ostat or CCN compatible tempe rature sensor . 1. T urn of f pow er to the cont rol bo x. 2. Strip the ends of the red, white, and bl ...

  • Carrier PREMIERLINK 33CSPREMLK - page 4

    4 RED RED BRN GRN FA N CMP1 CMP2 HS2 HS1 PWR HS3/EXH/RVS RED RED J8 J1 PWR CUT T O ISOLA TE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELA YS WHT BLU YEL RED ORN PNK PremierLink Connections 40RM Connections 38AK, AKS, ARZ, ARS T erminal Board (TB) W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 CCR 40RM, 40RMQ, 40RMS HEA T ACCESSORY W2 W1 C W2 R Y ...

  • Carrier PREMIERLINK 33CSPREMLK - page 5

    5 RED RED BRN GRN FA N CMP1 CMP2 HS2 HS1 PWR HS3/EXH/RVS RED RED J8 J1 PWR CUT T O ISOLA TE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELA YS WHT BLU YEL RED ORN PNK PremierLink Connections 40RM Connections 38ARD T erminal Board (TB) W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 40RM, 40RMQ, 40RMS HEA T ACCESSORY W2 W1 C W2 R Y1 Y2 W1 G C X LLSV ...

  • Carrier PREMIERLINK 33CSPREMLK - page 6

    6 RED RED BRN GRN FA N CMP1 CMP2 HS2 HS1 PWR HS3/EXH/RVS RED RED J8 J1 PWR CUT T O ISOLA TE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELA YS WHT BLU YEL RED ORN PNK PremierLink Connections 40RM Connections 38AH T erminal Board (TB2) W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 40RM, 40RMQ, 40RMS HEA T ACCESSORY W2 W1 C 4 5 3 2 1 RED RED BRN GR ...

  • Carrier PREMIERLINK 33CSPREMLK - page 7

    7 RED RED BRN GRN FA N CMP1 CMP2 HS2 HS1 PWR HS3/EXH/RVS RED RED J8 J1 PWR CUT T O ISOLA TE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELA YS WHT BLU YEL RED ORN PNK PremierLink Connections 40RMQ Connections CR W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 40RM, 40RMQ, 40RMS HEA T ACCESSORY W2 W1 C 38AQ007 Control Connections CR R O W BL Y RED R ...

  • Carrier PREMIERLINK 33CSPREMLK - page 8

    8 Table 1 — PremierLink Controller Inputs and Outputs LEGEND INPU TS PO WER TERMINAL (S) SP ACE TEMPERA TU RE (SPT ) AI (10K Ther mistor) J6-7, J6-6 SET POINT ADJUSTMENT (ST O) AI (10K Ther mistor) J6-5, J6-6 SUPPL Y AIR TEMPERA TURE (S A T) AI (10K Ther mistor) J6-3, J6-4 OUTDOOR AIR TEMPERA TURE (O A T) AI (10K Ther mistor) J6-1, J6-2 IA Q SENS ...

  • Carrier PREMIERLINK 33CSPREMLK - page 9

    9 Table 2 — Color Code Recommendatio ns Inst all Sens or s ( See Fig. 3-10 ) — The Premi erLink™ controller can be used with ei ther the T 58 Communicating sen- sor or any combination of CO 2 and space tem perature sensors . Refer to the instructions supplied with each sensor for electrical requirements. NOTE: All sensors are f ield-installed ...

  • Carrier PREMIERLINK 33CSPREMLK - page 10

    10 Table 3 — Thermistor Resista nce vs Temp erature Values for Spa ce Tempera ture Sen sor, Supply Air Temperature Sens or, and Outdoor Air Temperature Sen sor SUPPL Y AIR TEMPE RA T URE (SA T ) SENSOR INST AL- LA T IO N — T he 33ZCSENSA T supply air temperat ure sensor is required for controller operation. The sensor consists of a thermistor e ...

  • Carrier PREMIERLINK 33CSPREMLK - page 11

    11 Perform the following steps if state or local code requires the use of conduit, or if your installation requires a cable length of more than 8 ft: 1. Secure the probe to the duct with two field-supplie d self- drilling screws. 2. If you are extending cable length beyond 8 ft, use plenum rated, 20 A WG, twisted pair w ire. 3. Connect the sensor l ...

  • Carrier PREMIERLINK 33CSPREMLK - page 12

    12 J6 6 7 RED BLK RED RED BLK BLK BLK RED BLK RED SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4 J6 6 7 RED BLK RED BLK SENSOR 2 SENSOR 1 RED RED BLK SENSOR 3 SENSOR 4 BLK BLK RED RED RED BLK BLK SENSOR 8 SENSOR 9 SENSOR 5 RED BLK SENSOR 6 SENSOR 7 BLK RED SP A CE TEMPERA TURE A VERA GING — 4 SENSOR APPLICA TION SP AC E TEMPERA TURE A VERAGING — 9 SENSOR ...

  • Carrier PREMIERLINK 33CSPREMLK - page 13

    13 LE GEND Fig. 7 — Pre mierLink ™ Controller and Sensor Wiring — 33ZCT55S PT, 33ZCT56S PT, 33Z CT58SPT Space Temperature Se nsors; 33ZCSENSAT Supply Air Tempera ture Sensor; 33ZCSENCO2 (Outdoor), and 3 3ZCT55CO2, 33ZCT56CO2 (Indoor) Air Quality Sensors OA T — Outdoor Air T emperature Sensor SA T — Supply Air T emperature Sensor SPT — S ...

  • Carrier PREMIERLINK 33CSPREMLK - page 14

    14 Fig. 8 — PremierLink ™ Co ntrolle r Wiring — Combination Temperature and CO 2 Sensor — 33ZCT55C O2, 33 ZCT56CO2 NO TE: No wire is connected to c onnector J-5 pin 4. Y ou must relocat e a wire from an unused ter minal. T ypically one of the red wires from c onnector J-4 may be used for this purpos e. This pin on J-5 provided 24 VDC po wer ...

  • Carrier PREMIERLINK 33CSPREMLK - page 15

    15 NO TE: Remov e all un used red wires from J4 connector to pre v ent 24 v ac shor ting other components or ground. Inputs on J4 are 24 v ac. Red leads are voltage source. Fig. 9 — Pre mierLin k ™ Controller Sensor Wiring — With Programmable or Non-P rogrammable Thermostat ...

  • Carrier PREMIERLINK 33CSPREMLK - page 16

    16 NO TE: Remov e red wire f rom J4-9 to pre v ent 24 v ac shor ting out other components or ground. Inputs on J4 are 24 v ac. Red leads a re voltage source. Fig. 10 — Premie rLink ™ Field-Installed Controller Sensor Wiring — Discrete Input ...

  • Carrier PREMIERLINK 33CSPREMLK - page 17

    17 Fig. 11 — Typical Mounting Location for Supply Air Tempera ture (SAT) Sensor On Split Sys tem Units 8 7 6 5 4 32 1 2 1 HG 24 V AC OR 24 VDC NC ALARM RELA Y CONT ACTS COM NO } 0-10VDC SIG COM (J5-3) 4-20mA (J5-2) + + - + - Fig. 12 — Outdoor Air Quality (CO 2 ) Sensor (33ZCSENCO2) — Typical Wiring Dia gram Fig. 13 — Outdoor Air Quality Sen ...

  • Carrier PREMIERLINK 33CSPREMLK - page 18

    18 Connect to CCN Com m unication Bus — The PremierLink™ controller connects to the bus in a d aisy chain arrangemen t. Negative pins on each component m ust be connected to respective negative p ins and likewise positive p ins on each component must be connected to respective positive pins. Th e contro ller s ignal pins mu st be w ired t o the ...

  • Carrier PREMIERLINK 33CSPREMLK - page 19

    19 Mounting — Mount the enthalpy switch/receiver in a location where the outdoor air can be sampled (such as the outdoor air intake). The entha lpy switch/receiver is not a NEMA 4 encl o- sure and should be mounted in a location that is not exposed to outdoor elements such a s rain or snow . Use two f ield-supplied no. 8 x 3 / 4 -in. TEK screws. ...

  • Carrier PREMIERLINK 33CSPREMLK - page 20

    20 Connect the 4-20 mA In terminal on the enthalpy switch/ receive r to the 4 -20 m A Ou t ter minal o n the ret urn air enth alpy sensor . Connect t he 24-36 VDC Out terminal on the enthalpy switch/rece ive r to the 24-36 VD C In t erminal on the return ai r enthalpy sensor . See Fi g. 21. Enthalpy Switch/Reciever Jump er Settings — There are tw ...

  • Carrier PREMIERLINK 33CSPREMLK - page 21

    21 W iri ng Enthalp y Sensors — T o wire the enthalpy sensor, per- form the following (see Fig. 24 a nd 25): NOTE: T o mount outdoor air sensor remotely , remove it from back of enthalpy control and follow steps 3 and 6. 1. Use a 2-conductor, 18 or 20 A WG, twis t ed pair cable to connect the return air enthalpy sensor to t he differential enthal ...

  • Carrier PREMIERLINK 33CSPREMLK - page 22

    22 Q7 6 9 B — Be cause the Honeyw ell adapter is de signed for a negative 4 to 20 mA input instead of a positive signal, the Q769B adapter requires a separate transformer a nd a current loop isolator to perform properly . C onnecting th e adapter directly to the PremierLin k controller could caus e the 4 to 20 mA outpu t on the contr oller to be ...

  • Carrier PREMIERLINK 33CSPREMLK - page 23

    23 NOTE: If Pr em ier Lin k ™ Cont roller is grounded and actuator is grounded on common side , then common wire from PremierLink controller J9-2 is not needed. Fig. 25 — PremierLink Controller Wi ring — Differential Enthalpy Con trol (33AMKITEN T000) ...

  • Carrier PREMIERLINK 33CSPREMLK - page 24

    24 Economizer wit h Johnson 4 to 20 mA Actua - tor — The PremierLink Controller can be connected to an economizer that us es a Johnso n 4 to 20 mA actuato r . DR I V E DI R E C T I ON — The actua tor drive direction is dependent upon the position of Switch 3 a nd the spring return direction. See T able 5. The actuator i s factory set for Direct ...

  • Carrier PREMIERLINK 33CSPREMLK - page 25

    25 Output 20 VDC at 25 mA Feedback 0 (2)-10 or 6-9 VDC Input 0 (2)-10 or 6-9 VDC, 0 (4)-20 mA 24 V AC/VDC COM (3) (5) (4) (2) (1) J9-1 TO 24V TRANSFORMER Gray White/Red Red Y ellow White WIRE HARNESS FROM ACTUA TOR ACTUA TOR 50TJ400812 M9206-GGC-2 ECONOMIZER 12-PIN HARNESS RED 24 V AC 1 2 3 4 5 BRN TRANSFORMER GROUND 6 7 8 9 10 11 12 PNK PL6 4-20mA ...

  • Carrier PREMIERLINK 33CSPREMLK - page 26

    26 ST ART -U P Use the Carri er network communica tion software to start up and configure the Prem ierLink™ controller . Changes can be made using the ComfortWORKS ® soft- ware, ComfortVIEW™ software, or N etwork Service T ool. The Network Se rvice T ool is a port able interface device that allows the user to change system set-up and set point ...

  • Carrier PREMIERLINK 33CSPREMLK - page 27

    27 keys which are the up arrow ( ), down arrow ( ), and keys. IN S T A L L A T I O N — The Navigator display module is intend- ed to be a mobile device, so the re are no holes in the device for permanent mounting. T he module has a magnetic mount that is strong enough to hold the device in place on any clea n, dry metal surf ace. T o enter LEN (l ...

  • Carrier PREMIERLINK 33CSPREMLK - page 28

    28 T o access the sub-mode to change the Unocc upied OA T Lockout Setpoint, press the down arrow to scroll down until the Navigator™ module display reads: SETP OA TL >NTLO UHDB T o view an expansion of the sub-mode, press the and keys simultaneously and the Navigator will display: >NTLO UNOCC. OA T LOCKOUT TEMP The Navigator will rema in in ...

  • Carrier PREMIERLINK 33CSPREMLK - page 29

    29 Tab le 7 — Points Displ ay NO TE: Bold values i ndicate points that can be f orced through communications. SU P P L Y F AN ST A TU S — T his point displa ys the S upply Fan status if controller is configured to receive input from the Supply Fan. Otherwise this point will display the output state of the Supply Fan Relay . This mode ca n only ...

  • Carrier PREMIERLINK 33CSPREMLK - page 30

    30 HE A T S T A G E 2 — T he Heat Stage 2 point provide s the state of the Heating 2 output. Heating Stage 2: Display Units: Discrete ASCII Default V a lue: Off Display Range: Off/ On Network Ac cess: Read Only HEA T ST AGE 3, EXHAUST F AN , OR REVERSING V A L V E — This point di splays the commanded state of auxi l- iary output. This output ca ...

  • Carrier PREMIERLINK 33CSPREMLK - page 31

    31 Table 8 — Thermostat Control Input Display AL A R M RE - A L A R M T I M E — This decision i s used to con- figure the number of minutes that will elapse bet ween re-alarms. A re-al arm occurs when the conditi on that caused the initial alarm continues to persist for the number of mi nutes specified. Re-alarming continues to occur a t the sp ...

  • Carrier PREMIERLINK 33CSPREMLK - page 32

    32 DU R A T I O N — The Duration field indica tes how long the holiday will last (in days). Duration: Range: 0 to 365 Default V a lue: 0 As an example, i f a Holiday is configured for M onth 2, Day 5, Duration 2, then the Holiday will start February 5 and end February 7. Table 11 — Holiday Configuration Occupancy Configurat ion Screen — Th e ...

  • Carrier PREMIERLINK 33CSPREMLK - page 33

    33 UNOCCUPIED HIGH — The Un oc cu pie d H igh se t po in t d e- scribes the high temperat ure limit of the space during Unoccu- pied mode. Unoccupied High: Units: Degrees F (D egrees C) Range: 45.0 to 99.9 Default V alue: 90.0 HIGH OA T LIMIT FOR IAQ PRE-OCCUP ANC Y PU R G E — The High OA T unit for IAQ Pre-Occupancy Purge function determines t ...

  • Carrier PREMIERLINK 33CSPREMLK - page 34

    34 Table 14 — Service Configuration Selection ST AG ED C OOLING — The s t a g in g fun c t i on i s us e d f o r D X cooling (1 or 2 stages). The sta ging function uses the cooling submaster reference from the PID and c ompares the value to the supply air temperature to calculate the required number of output stages to energize. T ime Guard del ...

  • Carrier PREMIERLINK 33CSPREMLK - page 35

    35 The integral gain affects the PID calcula tion; an increa se will ma ke the IAQ submaste r referenc e change greater as t he error in indoor air quality increases. The integral gain should be selected to eliminate proportional droop without over shoot. Enter the desired integral gain for the Indoor Air Qualit y con- trol algorithm. The Derivativ ...

  • Carrier PREMIERLINK 33CSPREMLK - page 36

    36 The DXCTLO should be turned OFF (to ignore the DXLOCK setpoint) in applications where there is either no OA T sensor (local or broadcast) or t he OA T sensor has failed. For V ersion 1 .3 — If there is a valid OA T sensor reading and DXCTLO is set t o “OFF”, compressor cool ing wi ll NOT be allowed. Please note that t his functionality was ...

  • Carrier PREMIERLINK 33CSPREMLK - page 37

    37 PremierLink ™ Configurati on Screen — The PremierLink Configuration screen al low s the user to configure all functions. See T a ble 15. OP E R A T I N G M O D E — The Ope rat ing Mode function determines the operating mode of the PremierLink controller . There are two operat ing modes from wh ich to choose: TST A T and CCN Sensor . The TS ...

  • Carrier PREMIERLINK 33CSPREMLK - page 38

    38 GLOBAL SC HEDULE BROADC AST — The Gl obal Sc hed- ule Broadcast setting confi g ures the controller t o broadcast or receive a global schedule. If se t to Y es, the controller will a ct as a global schedule master and its schedule will be broadcast to the CCN. If set t o No, the c ontroller will not broadcast a global schedule and it wi ll rec ...

  • Carrier PREMIERLINK 33CSPREMLK - page 39

    39 Low Refere nce spe cif ies Low Poin t of the Out door IAQ Sensor Range in ppm. Low Reference: Uni ts: PPM (parts per million) Range: 0 to 5000 Default V a lue: 0 High Reference specifies High Point of the Outdoor IAQ Sensor Range in ppm. High Reference: Units: PPM (parts per million) Range: 0 to 5000 Default V alue: 2000 OUTDOOR AIR QUALITY LOCK ...

  • Carrier PREMIERLINK 33CSPREMLK - page 40

    40 NEXT UNOCCUPIED DA Y — Th e N e xt Un o ccu pi e d Da y point displays the day of w eek when the next unoccupied peri- od will begin. This point is used with the Next Unoccupied T ime so the user will know when the next unoccupied period will occur . If the controller is fol lowing a global schedule t his point will remain at defaul t. Next Un ...

  • Carrier PREMIERLINK 33CSPREMLK - page 41

    41 IAQ PRE-OCCUP ANCY PURGE — Ind i ca tes tha t the pr e- occupancy purge mode is currently act ive. IAQ Pre-occupancy Purge: Display Range: No/Y es Default V a lue: No Netwo rk Ac cess: Read Only UNOCCUPIED FREE COOLING — In d i ca t e s th a t unoccu- pied free cooling is i n effect. Unoccupied Free Cooling: Display Range: No/Y es Default V ...

  • Carrier PREMIERLINK 33CSPREMLK - page 42

    42 The A verage O ccupied Hea t Set Point displays t he Occupied Heat set point from the Linkage The rmostat. A verage Occupi ed Heat Set Point : Di splay Un its: Degrees F (Degrees C) Display Range: 0.0 to 99.9 Default V alue: 0.0 Network Access: None The A v erage Occupied Cool Set Point displays the Occu- pied Cool set point from the Linkage The ...

  • Carrier PREMIERLINK 33CSPREMLK - page 43

    ...

  • Carrier PREMIERLINK 33CSPREMLK - page 44

    Manufactu rer reser ves the rig ht to dis continue , or chan ge at a ny time, spec ificati ons or des igns without notice an d wit hout inc urring obligations. PC 111 Catalog No . 53 3-80072 Pr inted in U.S .A. Form 3 8-54S I P g 44 1 1-02 Rep laces: 38 -52S I Book 1 4 Ta b 3 a 2 a Copyright 20 02 Car rier Cor po ration ...

Produzent Carrier Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts Carrier PREMIERLINK 33CSPREMLK erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Carrier
- Bedienungsanleitungen PREMIERLINK 33CSPREMLK
- Produktkarten Carrier
- Informationsbroschüren
- oder Energieetiketten Carrier PREMIERLINK 33CSPREMLK
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Carrier PREMIERLINK 33CSPREMLK.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Carrier PREMIERLINK 33CSPREMLK, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Carrier PREMIERLINK 33CSPREMLK. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Carrier PREMIERLINK 33CSPREMLK ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Carrier PREMIERLINK 33CSPREMLK, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Carrier PREMIERLINK 33CSPREMLK hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Carrier PREMIERLINK 33CSPREMLK verständlich ist.

Eine gänzliche Bedienungsanleitung von Carrier sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Carrier PREMIERLINK 33CSPREMLK bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Carrier PREMIERLINK 33CSPREMLK befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Carrier PREMIERLINK 33CSPREMLK, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Carrier PREMIERLINK 33CSPREMLK - die uns die ersten Schritte während der Nutzung von Carrier PREMIERLINK 33CSPREMLK erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Carrier PREMIERLINK 33CSPREMLK hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Carrier PREMIERLINK 33CSPREMLK im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Carrier PREMIERLINK 33CSPREMLK?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Carrier PREMIERLINK 33CSPREMLK nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Carrier PREMIERLINK 33CSPREMLK hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)