Bedienungsanleitung Carrier 58TMA

24 Seiten 0.32 mb
Download

Zur Seite of 24

Summary
  • Carrier 58TMA - page 1

    58TMA Downflow/Horizontal 2-Speed, 2-Stage, Induced-Combustion Gas Furnace Installation, Start-Up, and Operating Instructions Sizes 065-125, Series 111 NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. Index Page SAFETY CONSIDERATIONS ................................. ...

  • Carrier 58TMA - page 2

    ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will pre- vent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions w ...

  • Carrier 58TMA - page 3

    in alcoves, attics, crawlspaces, basements, closets, or utility rooms. The design of this furnace line is not A.G.A./C.G.A. certified for installation in mobile homes, recreation vehicles, or outdoors. Before installing the furnace, refer to the current edition of the NFGC and the NFPA 90B. Canadian installations must be installed in accordance NSC ...

  • Carrier 58TMA - page 4

    Improper installation, adjustment, alteration, service, mainte- nance, or use can cause carbon monoxide poisoning, explo- sion, fire, electrical shock, or other conditions which may cause personal injury, loss of life, or property damage. Consult a qualified installer, service agency, local gas sup- plier, or your distributor or branch for informat ...

  • Carrier 58TMA - page 5

    installed in that space. A confined space MUST have provisions for supplying air for combustion, ventilation, and dilution of flue gases using 1 of the following methods. (See Fig. 3 and Table 2.) NOTE: In determining free area of an opening, the blocking effect of louvers, grilles, and screens must be considered. If free area of louver or grille d ...

  • Carrier 58TMA - page 6

    KGASB0201ALL is used. Manufacturer’s accessory floor base is not required when this furnace is installed on manufacturer’s Coil Assembly Part No. CD5 or CK5, or Coil Box Part No. KCAKC is used. 1. Determine application being installed from Table 3. 2. Construct hole in floor per dimensions specified in Table 3 and Fig. 5. 3. Construct plenum to ...

  • Carrier 58TMA - page 7

    2. When completed, downflow subbase, plenum, and furnace (or coil casing when used) should be installed as shown in Fig. 6. Step 4—Horizontal Attic Installation Do not install furnace on its back; safety control operation will be adversely affected. Never connect return-air ducts to the sides or back of the furnace. A failure to follow this warni ...

  • Carrier 58TMA - page 8

    → Fig. 9—Horizontal Crawlspace Installation on Hanger Rods A96633 NOTES: ANGLE IRON OR EQUIVALENT ROD LOCATION USING DIMPLE LOCATORS (SEE DIMENSIONAL DWG FOR LOCATIONS) 3 ⁄ 8 -IN. ROD 1. A 1 In. clearance minimum between top of furnace and combustible material.  2. The entire length of furnace must be supported when ...

  • Carrier 58TMA - page 9

    If flexible connector is required or allowed by authority having jurisdiction, black iron pipe shall be installed at gas valve and extend a minimum of 2 in. outside furnace casing. Use the proper length of pipes to avoid stress on gas control manifold. A failure to follow this warning could result in a gas leak causing fire, explosion, personal inj ...

  • Carrier 58TMA - page 10

    Step 8—Electrical Connections 115-V WIRING Refer to unit rating plate or Table 6 for equipment electrical requirements. The control system requires an earth ground for proper operation. Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. Make all electrical connections in accordance with the current edition o ...

  • Carrier 58TMA - page 11

    This furnace can be installed with either single-stage heating or 2-stage heating thermostat. For single-stage thermostats, connect thermostat W to W/W1 at furnace control terminal block. (See Fig. 15.) For single-stage thermostats the control determines, based on length of previous heating on and off cycles, when to operate in low- and high-gas he ...

  • Carrier 58TMA - page 12

    his furnace is equipped with 2 manual reset limit switches in gas control area. The switches will open and shut off power to gas valve if a flame rollout or an overheating condition occurs in gas control area. DO NOT bypass switches. Correct inadequate combustion air supply, component failure, re- stricted flue gas passageway before resetting switc ...

  • Carrier 58TMA - page 13

    → Fig. 18—Unit Wiring Diagram A97508 LEGEND ALS1 AUXILIARY LI MIT SWITCH, OVERTEMP. MANUAL RES ET, SPST (N. C.) ALS2 AUXILIARY LI MIT SWITCH, OVERTEMP. AUTO RESET, SPST (N.C. ) BHI / LOR BL OWER MOTOR SPEED CHANG E RELAY, SPDT BHT / CLR BLOWER MOTOR SPEED CHANGE RELAY , SPDT BLWM BLOWER MOTOR, 4 or 5 -S PEED, PERMANEN T-SPLIT-CAPAC ITOR BLWR BL ...

  • Carrier 58TMA - page 14

    The furnace starts up in either low- or high-gas heat. If furnace starts up in low-gas heat, control CPU determines low-gas heat on time (from 0 to 16 minutes) which is permitted before switching to high-gas heat. If power is interrupted, stored history is erased, and control CPU selects low-gas heat for up to 16 minutes and then switches to high-g ...

  • Carrier 58TMA - page 15

    (1.) The thermostat closes R to G-and-Y circuits. The R-Y circuit starts outdoor unit, and R to G-and-Y circuits start furnace blower motor BLWM on high- cool speed. (2.) The EAC terminals EAC-1 and EAC-2 are energized with 115v when blower motor BLWM is operating. (3.) When thermostat is satisfied, R to G-and-Y circuits are opened. The outdoor uni ...

  • Carrier 58TMA - page 16

    BLWM operation at heat pump heating speed until end of prepurge period, then shuts off until end of HSI ignitor on period (22 sec). b. When installed with a heat pump, furnace control CPU automatically holds blower off time to 22 sec during HSI ignitor on period. After 17 sec of HSI ignitor on period, a trial-for-ignition sequence occurs as describ ...

  • Carrier 58TMA - page 17

    e. Move setup switch SW-2 to OFF position after completing low-heat adjustment. f. Jumper R and W2 thermostat connections on control center. (See Fig. 14.) This keeps furnace locked in high-heat operation. g. Turn high-heat adjusting screw (5/64 hex Allen wrench) counterclockwise (out) to decrease input rate or clockwise (in) to increase rate. NOTE ...

  • Carrier 58TMA - page 18

    Table 10—Model 58TMA Orifice Size and Manifold Pressure for Correct Input (Tabulated Data Based on 21,000 Btuh High Heat/13,500 Btuh Low Heat per Burner, Derated 4% for Each 1000 Ft Above Sea Level)* ALTITUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0.64 0.66 Orifice No. Manifold Pressur ...

  • Carrier 58TMA - page 19

    Table 10—Model 58TMA Orifice Size and Manifold Pressure for Correct Input—Continued (TABULATED DATA BASED ON 21,000 BTUH HIGH HEAT/13,500 BTUH LOW HEAT PER BURNER, DERATED 4% FOR EACH 1000 FT ABOVE SEA LEVEL)* ALTITUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0.64 0.66 Orifice No. Mani ...

  • Carrier 58TMA - page 20

    Table 10—Model 58TMA Orifice Size and Manifold Pressure for Correct Input—Continued (TABULATED DATA BASED ON 21,000 BTUH HIGH HEAT/13,500 BTUH LOW HEAT PER BURNER, DERATED 4% FOR EACH 1000 FT ABOVE SEA LEVEL)* ALTITUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0.64 0.66 Orifice No. Mani ...

  • Carrier 58TMA - page 21

    a. Place duct thermometers in return and supply ducts as near furnace as possible. Be sure thermometers do not see heat exchangers so that radiant heat will not affect thermometer readings. This is particularly important with straight-run ducts. b. When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to d ...

  • Carrier 58TMA - page 22

    components in R-W/W1 circuit. Accurate amp draw read- ings can be obtained at wires normally connected to thermostat subbase terminals R and W/W1. Fig. 21 illus- trates an easy method of obtaining actual amp draw. The amp reading should be taken after blower motor has started and furnace is operating in low heat. To operate furnace in low heat, fir ...

  • Carrier 58TMA - page 23

    CHECKLIST 1. Put away tools and instruments, and clean up debris. 2. Check SW-1 through SW-4 after completing installation to ensure desired settings for thermostat type (SW-1 and SW-2) and blower off delay (SW-3 and SW-4). Refer to Tables 6 and 7. 3. Verify manual reset switches have continuity. 4. Ensure blower and gas control access doors are pr ...

  • Carrier 58TMA - page 24

    A94328 SER VICE TRAINING P ackaged Service T raining prog rams are an e xcellent wa y to increase your knowledge of the equipment discussed in this man ual, including: • Unit F amiliarization • Maintenance • Installation Ov er vie w • Operating Sequence A large selection of product, theor y , and skills prog rams is av ailable , using popul ...

Produzent Carrier Kategorie Furnace

Dokumente, die wir vom Produzenten des Geräts Carrier 58TMA erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Carrier
- Bedienungsanleitungen 58TMA
- Produktkarten Carrier
- Informationsbroschüren
- oder Energieetiketten Carrier 58TMA
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Carrier 58TMA.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Carrier 58TMA, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Carrier 58TMA. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Carrier 58TMA ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Carrier 58TMA, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Carrier 58TMA hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Carrier 58TMA verständlich ist.

Eine gänzliche Bedienungsanleitung von Carrier sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Carrier 58TMA bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Carrier 58TMA befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Carrier 58TMA, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Carrier 58TMA - die uns die ersten Schritte während der Nutzung von Carrier 58TMA erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Carrier 58TMA hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Carrier 58TMA im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.