Goodman GSZ/VSZ 13 SEER - page 1
GSZ/VSZ 13 SEER S plit System Heat Pump s • Refer to Service Manual RS6200006 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. • Models listed on page 3. RT6212006r10 December 2011 C ...
-
Goodman GSZ/VSZ 13 SEER - page 2
PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WA RNI NG WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause ...
-
Goodman GSZ/VSZ 13 SEER - page 3
PRODUCT IDENTIFICA TION 3 The United States Environmental Protection Agency (“EPA”) has issued various regulations re- garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. These regulations may vary by ju ...
-
Goodman GSZ/VSZ 13 SEER - page 4
PRODUCT DESIGN 4 GSZ/VSZ13 models are available in 1 1/2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. Select GSZ13 models are available in 208/230 and 460 volt 3-phase applications. These models use R-410A refrigerant. The condenser air is pulled through the condenser coil by a direct ...
-
Goodman GSZ/VSZ 13 SEER - page 5
PRODUCT DESIGN 5 Mo d el D i m en si o n s - W x D x H G / V SZ 130181A * 26 x 26 x 32 ¼ G / V S Z 130241A * 26 x 26 x 32 ¼ G / V S Z 130241B* 26 x 26 x 32 ½ G / V SZ 130301A * 26 x 26 x 32 ¼ G / V S Z 13036 1A * G SZ 130363A * 2 9 x 2 9 x 3 8 ¼ G / V S Z 130361B* 29 x 29 x 32 ½ G / V SZ 130421A * 29 x 29 x 38 ¼ G / V S Z 13048 1A * G SZ 130 ...
-
Goodman GSZ/VSZ 13 SEER - page 6
HEA T PUMP SPECIFICA TIONS 6 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...
-
Goodman GSZ/VSZ 13 SEER - page 7
HEA T PUMP SPECIFICA TIONS 7 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...
-
Goodman GSZ/VSZ 13 SEER - page 8
HEA T PUMP SPECIFICA TIONS 8 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...
-
Goodman GSZ/VSZ 13 SEER - page 9
HEA T PUMP SPECIFICA TIONS 9 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...
-
Goodman GSZ/VSZ 13 SEER - page 10
10 COOLING PERFORMANCE DA T A G/VSZ130181A* M O D E L : G /V S Z 1 3018 1A * / A R *F 182416 ** EXPA ND ED PER FOR M AN CE D ATA COOL I NG OP E RA TI ON O utdoor Am bi e n t Te m pe r ature 65 75 85 95 105 1 15 E n te r ing I n door We t B ul b Te m pe rat u r e I D B * A i r f l o w 5 96 36 77 15 96 3 6 77 15 96 36 77 1 5 9 6 3 6 7 7 15 9 6 36 77 ...
-
Goodman GSZ/VSZ 13 SEER - page 11
11 COOLING PERFORMANCE DA T A G/VSZ130181A* M O D E L: G /V S Z 130181A * / A R * F182416* * EXPAN DED PER F O RM A NCE D ATA COOL I NG OPE RA T I ON O utdoor Am bient Te m pe r at ur e 65 75 85 95 105 115 E nte r i ng I ndoor We t B ul b Te m pe rat ur e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 77 15 96 36 7 ...
-
Goodman GSZ/VSZ 13 SEER - page 12
12 COOLING PERFORMANCE DA T A G/VSZ130241A* M O D E L: G /V S Z 130241A * / A R * F 182416 * * EX PANDE D PERF ORM ANCE DAT A C O O LIN G O P E R A T IO N O utdoo r Am bi e nt Te m pe r at ur e 65 75 85 95 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r at ur e I D B * A i r f l o w 5 9 6 3 6 77 1 5 9 6 36 77 15 96 3 6 7 7 15 9 6 3 6 7 7 15 96 36 ...
-
Goodman GSZ/VSZ 13 SEER - page 13
13 COOLING PERFORMANCE DA T A G/VSZ130241A* M O D E L : G /V S Z 13 024 1A * / A R * F 1 824 16 * * EX PAN DE D PERF O RM ANCE DATA C OOL I NG OP E RA TI ON O utdoor Am bi e nt Te m pe r a ture 65 75 85 95 10 5 115 E nte ri ng I ndoor W e t B ul b Tem pe r at ur e I D B * A i r f l o w 5 9 6 3 6 77 1 5 9 6 36 77 15 96 3 6 7 7 15 9 6 3 6 7 7 1 5 96 ...
-
Goodman GSZ/VSZ 13 SEER - page 14
14 COOLING PERFORMANCE DA T A EXPAN DED PERF OR M AN CE DATA MODE L : G/ V S Z 130241B*/ AR * F 182416* * C OOLI NG OPE RA T I ON O ut door Am bie nt Te m pe r a tur e 65 75 85 95 105 115 E nt e r ing Indoor W et B ulb Te m pe r atur e ID B A i r f lo w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 M Bh 22 . 5 23.4 25.6 - ...
-
Goodman GSZ/VSZ 13 SEER - page 15
15 COOLING PERFORMANCE DA T A G/VSZ130241B* EXPAN DED PERF OR M AN CE DATA MODE L : G/ V S Z 130241B*/ AR * F 182416* * C OOLI NG OPE RA T I ON O ut door Am bie nt Te m pe r a tur e 6 5 75 8 5 9 5 105 11 5 E nt e r ing Indoor W et B ulb Te m pe r atur e ID B A i r f lo w 59 63 67 71 59 63 67 71 5 9 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 M Bh ...
-
Goodman GSZ/VSZ 13 SEER - page 16
16 COOLING PERFORMANCE DA T A G/VSZ130301A* M O D E L: G /V S Z 1 30301A * / A R * F 30301 * * E XP AND ED P ERF ORM AN CE D AT A COOL I NG OP E RA TI ON O utd o or Am b i e nt T e m pe r ature 65 75 85 95 105 115 E n te r i n g I ndo or We t B ul b Te m p e r at ur e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 3 ...
-
Goodman GSZ/VSZ 13 SEER - page 17
17 COOLING PERFORMANCE DA T A G/VSZ130301A* M O D E L : G /VSZ 1 3030 1A * / A R * F 303 01* * EXPA NDED PERFO RM AN CE DA TA COOL I NG OP ER A T I ON O utdoor Am bi e n t Te m pe r at ur e 65 75 85 95 10 5 115 E n te r i ng I ndoor We t B ul b Te m pe r ature I D B * A i r f l o w 5 96 36 77 1 5 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 36 7 7 1 ...
-
Goodman GSZ/VSZ 13 SEER - page 18
18 COOLING PERFORMANCE DA T A G/VSZ130361A* M O D E L : G /V S Z 13 03 61A * / A R *F 36 42 16* * EXP ANDED PERF ORM ANCE D AT A C OOLIN G OPE R ATIO N O utdoor Am bient Te m pe r at ur e 65 75 85 95 105 11 5 E nte r i ng I ndoor W e t B ul b Te m pe rature ID B A ir f lo w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 M B ...
-
Goodman GSZ/VSZ 13 SEER - page 19
19 COOLING PERFORMANCE DA T A G/VSZ130361A* M O D E L : G /V S Z130361A * / A R * F 364 216 * * EXPAND ED PERFO RM AN CE DA T A C OOL IN G OP E R AT ION O utd oor Am bie nt Te m pe r atur e 65 75 85 95 105 115 E nte ring I ndoor We t B ul b Te m pe r at ur e I D B * A i r f l o w 5 9 6 3 6 77 1 5 9 6 36 7 7 1 5 9 6 3 6 77 15 9 6 3 6 7 7 15 96 36 77 ...
-
Goodman GSZ/VSZ 13 SEER - page 20
20 COOLING PERFORMANCE DA T A G/VSZ130361B* EX P AND E D P ER F O RM A NC E DAT A M O D E L: G / V S Z1 3 0 36 1B * / A R * F 36 42 1 6 * * CO OL I NG OPE RATION Out d oor Ambi e nt Te mper a tur e 65 75 85 95 10 5 11 5 En t e rin g In d o or We t B u lb T e mp e rat ur e ID B A irf l o w 59 63 67 7 1 5 9 63 67 7 1 59 63 6 7 7 1 59 63 6 7 7 1 59 63 ...
-
Goodman GSZ/VSZ 13 SEER - page 21
21 COOLING PERFORMANCE DA T A G/VSZ130361B* EXP AND ED P ER FO RMANC E DAT A M O D EL: G / V SZ1 30 36 1B * / A R* F36 42 16 * * CO OL ING O PE RA T ION Out door Am bi e nt Te mpe r a ture 65 75 85 95 10 5 11 5 En t e rin g Indo or We t B u lb Te mp e rat u re ID B A irfl o w 59 63 6 7 7 1 59 63 67 7 1 59 63 6 7 7 1 59 63 6 7 7 1 59 63 6 7 7 1 59 6 ...
-
Goodman GSZ/VSZ 13 SEER - page 22
22 COOLING PERFORMANCE DA T A GZ130363A* EXPAN DED PERFORMAN CE DAT A M ODEL: GS Z 130363A* / AR*F 3 64216** COOLING OP E RATION O u td oo r Am bie n t Te m pe r ature 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe rature ID B A ir flow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 33.8 3 5.0 38. 4 - 33 ...
-
Goodman GSZ/VSZ 13 SEER - page 23
23 COOLING PERFORMANCE DA T A GZ130363A* EXPAN DED PERFORMAN CE DA T A M ODEL: GS Z 130363A* / AR*F 3 64216** COOLING OP E RATION O u td oo r Am bie n t Te m pe r ature 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe rature ID B A ir flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 34.98 3 5.75 38.19 ...
-
Goodman GSZ/VSZ 13 SEER - page 24
24 COOLING PERFORMANCE DA T A G/VSZ130421A* M O D E L : G /V S Z 130421A * / A R * F 36421** EX PANDED PERF ORM ANCE DATA COOL I NG OP ER A T I ON O utdoo r Am b i e nt Te m pe r ature 65 7 5 85 95 1 05 115 E n te r in g In d oo r We t Bulb T e m p e r at u r e ID B Air f lo w 59 63 67 71 59 63 67 71 59 63 67 71 59 6 3 67 71 59 63 67 71 59 63 67 71 ...
-
Goodman GSZ/VSZ 13 SEER - page 25
25 COOLING PERFORMANCE DA T A G/VSZ130421A* M O D E L: G /V S Z 130421 A * / A R * F 36421* * E XPANDE D PERF ORM ANCE DATA COOL I NG OP ERA T I ON O utdoo r Am bie nt T e m p e r ature 65 75 85 95 105 115 E n te r in g In d o or We t B u lb T e m p e r at u r e I D B * A i r f l o w 5 9 6 3 6 7 7 1 5 9 6 36 77 15 9 6 3 6 77 1 5 9 6 3 6 7 7 1 5 9 6 ...
-
Goodman GSZ/VSZ 13 SEER - page 26
26 COOLING PERFORMANCE DA T A G/VSZ130481A* M O D E L : G /V S Z 130481A * /A R *F 48601* * EXPAN DED PER FORM AN CE DA T A COOL I NG OP ERA T I ON O utdoor Am bi e nt Te m pe r at ur e 65 75 85 95 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r at ur e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 3 6 77 15 96 3 ...
-
Goodman GSZ/VSZ 13 SEER - page 27
27 COOLING PERFORMANCE DA T A G/VSZ130481A* M O D E L : G /VSZ 130481A * /A R *F 48601** EXPAN DED PERFOR M ANC E DATA COOL I NG OP ERA T I ON O utdoor Am bi e nt Tem pe r at ur e 65 75 85 95 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r at ur e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 3 6 77 15 96 36 77 1 ...
-
Goodman GSZ/VSZ 13 SEER - page 28
28 COOLING PERFORMANCE DA T A GSZ130483A* EXPAN DED PERFORMAN CE DA T A M ODEL: GS Z 130483A* / AR*F 4 86016** COOLING OP E RATION O u td oo r Am bie n t Te m pe r ature 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe rature ID B A ir flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 45.1 4 6.7 51. 2 - ...
-
Goodman GSZ/VSZ 13 SEER - page 29
29 COOLING PERFORMANCE DA T A GSZ130483A* EXPAN DED PERFORMAN CE DA T A M ODEL: GS Z 130483A* / AR*F 4 86016** C OOLING O P E RA TION O u td oo r Am bie n t Te m pe r ature 65 75 85 95 105 115 E nte r i ng I ndoor Wet B ul b Te m pe rature ID B A ir flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 46.66 4 7.67 50. ...
-
Goodman GSZ/VSZ 13 SEER - page 30
30 COOLING PERFORMANCE DA T A GSZ130484A* EXPAN DED PERFORMAN CE DA T A M ODEL: GS Z 130484A* / AR*F 4 86016** COOLING OP E RATION O u td oo r Am bie n t Te m pe r ature 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe rature ID B A ir flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 45.1 4 6.7 51. 2 - ...
-
Goodman GSZ/VSZ 13 SEER - page 31
31 COOLING PERFORMANCE DA T A GSZ130484A* EXPAN DED PERFORMAN CE DA T A M ODEL: GS Z 130484A* / AR*F 4 86016** COOLING OP E RATION O u td oo r Am bie n t Te m pe r ature 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe rature ID B A ir flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 46.66 4 7.67 50.93 ...
-
Goodman GSZ/VSZ 13 SEER - page 32
32 COOLING PERFORMANCE DA T A G/VSZ130601A* M O D E L : G /V S Z 130601A * / A R * F48601* * EXPAND ED PERFO RM ANC E DATA COOL I N G OPE R ATI ON O utdoor Am bi e nt Te m pe r at ur e 65 75 85 95 105 115 E nte r i ng I ndoor We t B ul b Te m pe ra ture ID B A ir f low 59 63 67 71 59 6 3 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 M Bh 5 ...
-
Goodman GSZ/VSZ 13 SEER - page 33
33 COOLING PERFORMANCE DA T A G/VSZ130601A* EX PANDED P ERF ORM ANCE DAT A C OOL I N G OP E R AT ION M ODEL: GS Z 130601A * / AR*F 48601** O utdoor Am bi e nt Tem pe r at ur e 65 75 85 95 105 11 5 E nter i ng Indoor Wet B ul b Te m pe ra ture ID B A ir f low 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 M Bh 55.9 57.9 63. ...
-
Goodman GSZ/VSZ 13 SEER - page 34
34 COOLING PERFORMANCE DA T A GSZ130603A* EXPAN DED PERFORMAN CE DA T A M ODEL: GS Z 130603A* /AR*F 4 86016** COOLING OP E RATION O u td oo r Am bie n t Te m pe r ature 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe rature ID B A ir flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 55.9 5 7.9 63. 4 - ...
-
Goodman GSZ/VSZ 13 SEER - page 35
35 COOLING PERFORMANCE DA T A GSZ130603A* EXPAN DED PERFORMAN CE DA T A M ODEL: GS Z 130603A* /AR*F 4 86016** C OOLING O P E RA TION O u td oo r Am bie n t Te m pe r ature 65 75 85 95 105 115 E nte r i ng I ndoor Wet B ul b Te m pe rature ID B A ir flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 57.81 5 9.07 63.1 ...
-
Goodman GSZ/VSZ 13 SEER - page 36
36 COOLING PERFORMANCE DA T A GSZ130604A* EXPAN DED PERFORMAN CE DA T A M ODEL: GS Z 130604A* /AR*F 4 86016** COOLING OP E RATION O u td oo r Am bie n t Te m pe r ature 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe rature ID B A ir flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 55.9 5 7.9 63. 4 - ...
-
Goodman GSZ/VSZ 13 SEER - page 37
37 COOLING PERFORMANCE DA T A GSZ130604A* EXPAN DED PERFORMAN CE DA T A M ODEL: GS Z 130604A* /AR*F 4 86016** COOLING OP E RATION O u td oo r Am bie n t Te m pe r ature 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe rature ID B A ir flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 57.81 5 9.07 63.11 ...
-
Goodman GSZ/VSZ 13 SEER - page 38
38 SPLIT SYSTEM HEA TING PERFORMANCE M OD EL : G/ V S Z 13 01 81A * / AR* F 1 8 24 1 6 ** HEAT I NG O PE RA T I O N O utdoor Am bi e nt Te m p e r at u r e 65 60 5 5 50 4 7 45 4 0 35 30 25 2 0 17 15 1 0 5 0 - 5 -1 0 MB h 21. 4 20 .2 1 9. 0 17. 8 17 .0 16 .5 1 5. 3 14. 1 13 .3 1 2. 3 1 1. 3 10. 7 10 .3 9. 2 8 .2 7. 2 6. 1 5 .0 D E LT A T 33. 0 31 .2 ...
-
Goodman GSZ/VSZ 13 SEER - page 39
39 SPLIT SYSTEM HEA TING PERFORMANCE EXP ANDED PERFORMANCE DA T A *Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature Hi g h pre s su r e i s m eas u red at t h e l iqu id s er v ic e v al v e ( t h e s ma lle r val v e ) . L ow pr e ss u r e i s me a s u re d a t th e gau ge po r t c on nec ti on . C a l cu l at i on s ...
-
Goodman GSZ/VSZ 13 SEER - page 40
40 SPLIT SYSTEM HEA TING PERFORMANCE EXP ANDED PERFORMANCE DA T A *Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature Hi g h pre s su r e i s m eas u red at t h e l iqu id s er v ic e v al v e ( t h e s ma lle r val v e ) . L ow pr e ss u r e i s me a s u re d a t th e gau ge po r t c on nec ti on . C a l cu l at i on s ...
-
Goodman GSZ/VSZ 13 SEER - page 41
41 SPLIT SYSTEM HEA TING PERFORMANCE EXP ANDED PERFORMANCE DA T A *Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature Hi g h pre s su r e i s m eas u red at t h e l iqu id s er v ic e v al v e ( t h e s ma lle r val v e ) . L ow pr e ss u r e i s me a s u re d a t th e gau ge po r t c on nec ti on . C a l cu l at i on s ...
-
Goodman GSZ/VSZ 13 SEER - page 42
42 EXP ANDED PERFORMANCE DA T A SPLIT SYSTEM HEA TING PERFORMANCE *Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature Hi g h pre s su r e i s m eas u red at t h e l iqu id s er v ic e v al v e ( t h e s ma lle r val v e ) . L ow pr e ss u r e i s me a s u re d a t th e gau ge po r t c on nec ti on . C a l cu l at i on s ...
-
Goodman GSZ/VSZ 13 SEER - page 43
43 SPLIT SYSTEM HEA TING PERFORMANCE EXP ANDED PERFORMANCE DA T A *Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature Hi g h pre s su r e i s m eas u red at t h e l iqu id s er v ic e v al v e ( t h e s ma lle r val v e ) . L ow pr e ss u r e i s me a s u re d a t th e gau ge po r t c on nec ti on . C a l cu l at i on s ...
-
Goodman GSZ/VSZ 13 SEER - page 44
44 SPLIT SYSTEM HEA TING PERFORMANCE *Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature Hi g h pre s su r e i s m eas u red at t h e l iqu id s er v ic e v al v e ( t h e s ma lle r val v e ) . L ow pr e ss u r e i s me a s u re d a t th e gau ge po r t c on nec ti on . C a l cu l at i on s a r e b as e d on n om i na ...
-
Goodman GSZ/VSZ 13 SEER - page 45
45 SPLIT SYSTEM HEA TING PERFORMANCE *Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature Hi g h pre s su r e i s m eas u red at t h e l iqu id s er v ic e v al v e ( t h e s ma lle r val v e ) . L ow pr e ss u r e i s me a s u re d a t th e gau ge po r t c on nec ti on . C a l cu l at i on s a r e b as e d on n om i na ...
-
Goodman GSZ/VSZ 13 SEER - page 46
46 See Heating Mode chart on following page. Chart applies to GSZ130481A, GSZ130483A & GSZ130484A. EXP ANDED PERFORMANCE DA T A SPLIT SYSTEM HEA TING PERFORMANCE M O D EL: G / V S Z 1304 81A * / AR * F 486 01** HE AT I NG O P ERA TI O N Outdo or Am b i ent T em p e r atur e 65 60 5 5 50 4 7 45 4 0 35 30 25 2 0 17 15 1 0 5 0 - 5 -1 0 MB h 55. 3 ...
-
Goodman GSZ/VSZ 13 SEER - page 47
47 SPLIT SYSTEM HEA TING PERFORMANCE EXP ANDED PERFORMANCE DA T A *Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature Hi g h pre s su r e i s m eas u red at t h e l iqu id s er v ic e v al v e ( t h e s ma lle r val v e ) . L ow pr e ss u r e i s me a s u re d a t th e gau ge po r t c on nec ti on . C a l cu l at i on s ...
-
Goodman GSZ/VSZ 13 SEER - page 48
48 SPLIT SYSTEM HEA TING PERFORMANCE EXP ANDED PERFORMANCE DA T A MO D E L : G /VS Z1 3 0 6 0 1 A * / A R * F4 8 6 0 1* * H EA TIN G OPE R A T IO N O utdoor Am bi ent Temp e r a tur e 65 60 5 5 50 4 7 45 4 0 35 30 25 2 0 17 15 1 0 5 0 - 5 -1 0 MB h 72. 9 69 .0 6 5. 0 60. 7 58 .0 56 .2 5 2. 2 48. 1 44 .9 4 1. 4 3 8. 1 36. 0 34 .7 3 1. 1 27. 6 24 .0 ...
-
Goodman GSZ/VSZ 13 SEER - page 49
49 SPLIT SYSTEM HEA TING PERFORMANCE EXP ANDED PERFORMANCE DA T A *Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature Hi g h pre s su r e i s m eas u red at t h e l iqu id s er v ic e v al v e ( t h e s ma lle r val v e ) . L ow pr e ss u r e i s me a s u re d a t th e gau ge po r t c on nec ti on . C a l cu l at i on s ...
-
Goodman GSZ/VSZ 13 SEER - page 50
50 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a ...
-
Goodman GSZ/VSZ 13 SEER - page 51
HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL T IPLE POW ER SOUR CES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROP ERTY DAMAGE, PERSONAL IN JUR Y OR DE A TH . WIRING DIAGRAMS 51 Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. G/VSZ130[18- ...
-
Goodman GSZ/VSZ 13 SEER - page 52
WIRING DIAGRAMS 52 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL T IPLE POW ER SOUR CES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROP ERTY DAMAGE, PERSONAL IN JUR Y OR DE A TH . U SE N. E. C . CL AS S 2 WIRE NO TES: 1) T O IND OO R UNIT L OW VOL T AGE TERMINAL BLOCK & I N DO OR THERM OST A T . ...
-
Goodman GSZ/VSZ 13 SEER - page 53
HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL T IPLE POW ER SOUR CES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROP ERTY DAMAGE, PERSONAL IN JUR Y OR DE A TH . WIRING DIAGRAMS 53 GSZ130181AD, GSZ130241[B*/C*], GSZ130301A[E/F], GSZ130361BB VSZ130181A[C/D], VSZ130241B[B/C], VSZ130301A[D/E], VSZ130361 ...
-
Goodman GSZ/VSZ 13 SEER - page 54
WIRING DIAGRAMS 54 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL T IPLE POW ER SOUR CES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROP ERTY DAMAGE, PERSONAL IN JUR Y OR DE A TH . Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. GSZ130[36-60 ...
-
Goodman GSZ/VSZ 13 SEER - page 55
HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL T IPLE POW ER SOUR CES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROP ERTY DAMAGE, PERSONAL IN JUR Y OR DE A TH . WIRING DIAGRAMS 55 Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. GSZ130[36-60 ...
Haben Sie eine Frage bezüglich Goodman GSZ/VSZ 13 SEER?
Nutzen Sie das untere Formular
Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Goodman GSZ/VSZ 13 SEER nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Goodman GSZ/VSZ 13 SEER hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.