    246819-BTG-H-0208 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE SPLIT - SYSTEM HEA T PUMPS 13 SEER – R-22 MODELS: E*BD-F018 THRU 060 (1.5 THRU 5 NOMINAL T ONS, 1 PHASE) E*BD-(T ,W)036 THRU 060 (2.5 THRU 5 NOMINAL T ONS, 3 PHASE) Due to continuo us product imp rovement, speci fications are subject to chan ge without notice. Vi ...

  • York E*BD-F018 THRU 060 - page 2

    246819-BTG-H-0208 2 Unitary Products Group All dimensions are in inches. They are subject to cha nge without notice. Ce rtif ied dimensio ns will be provide d upon request. Physical and Electrical Dat a - 1 Phase MODEL EABD-F018S EABD-F024S EABD-F030S EABD-F036S EABD-F042S EABD-F048S EABD-F060S Unit Supply V oltage 208-230V , 1 φ, 60Hz Normal V ol ...

  • York E*BD-F018 THRU 060 - page 3

    246819-BTG-H-0208 Unitary Products Group 3 Additional R-22 Charge / Orifice Size for V arious Matched Syste ms - 1 Phase Outdoor Unit EABD-F018S EABD-F024S EABD-F030S EAB D-F036S EABD-F042S EABD-F048S EABD-F060S Required TXV 1 TVM2A1 1 TVM2A1 1 TVM2A1 1 TVM2A1 1 TVM2C1 1 TVM2C1 1 TVM2C1 Factory Charge, lbs-oz 7 - 1 6 - 9 8 - 9 8 - 7 8 - 7 12 - 8 16 ...

  • York E*BD-F018 THRU 060 - page 4

    246819-BTG-H-0208 4 Unitary Products Group * This loose coil match does not achieve 13 SEER. PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes re frigerant for the condenser , the smallest evaporator and 15 feet of inter- connecting line tubing. 2. V erify the orifice size and the additional charge required for t he specific ...

  • York E*BD-F018 THRU 060 - page 5

    246819-BTG-H-0208 Unitary Products Group 5 All dimensions are in inche s. Th ey are su bject to change with- out notice. Certified dimensions will be pro vided upon request. Physical and Elect rical Dat a - 3 Ph ase MODEL EABD- T030S EABD- T036S EABD- T042S EABD- T048S EABD- T060S EABD- W030S EABD- W036S EABD- W042S EABD- W048S EABD- W060S Unit Sup ...

  • York E*BD-F018 THRU 060 - page 6

    246819-BTG-H-0208 6 Unitary Products Group PROCEDURES: 1. U nit factory charge listed on the unit nameplate includes refr igerant for the condenser , the smallest evaporator and 15 feet of inter-con- necting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using th e above table. 3. Additional ...

  • York E*BD-F018 THRU 060 - page 7

    246819-BTG-H-0208 Unitary Products Group 7 COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 1 & 3 PH 13 SEER HP WITH MA EABD-F018S MA08B 17 FC/MC18B 600 18 .0 12.4 13 .00 1 1.00 EABD-F024S MA08B 17 FC/MC24B 800 23.2 16.8 13.00 1 1.00 MA08B 17 FC/MC30B 800 23 ...

  • York E*BD-F018 THRU 060 - page 8

    246819-BTG-H-0208 8 Unitary Products Group — = Not Applicable. Go to www.ari. org/aridirectory for the latest additiona l matches. 1 PH 13 SEER AC WITH A V / SV - V ARIABLE SPEED EABD-F018S A V24 17 – 600 18.0 12.6 14.00 12.00 EABD-F024S A V24 17 – 800 23.8 16.7 14.00 12.00 EABD-F030S A V36 17 – 1000 29.2 20.1 14 .00 12.00 EABD-F036S A V36 ...

  • York E*BD-F018 THRU 060 - page 9

    246819-BTG-H-0208 Unitary Products Group 9 COOLING CAP ACITY - Upflow , Downflow , and Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MBH SEER 1 EER TOT AL SENS. EABD-F018S 450 750 14,17 FC/MC/PC/UC18 600 18.0 12 .4 13.00 1 1.00 14 HC18 600 17.8 12 .1 13.00 1 1.00 EABD-F024S 600 1000 14 ...

  • York E*BD-F018 THRU 060 - page 10

    246819-BTG-H-0208 10 Unitary Products Group COOLING CAP ACITY - With V ariable S peed Furnac es UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER T OTAL SENS. 1 PH 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 EABD-F018S (F ,L)L8V A12 FC/MC/PC18A 14 600 18.0 12.5 14.00 12.00 FL9V A12 FC/MC/PC18A 14 600 18.0 12 ...

  • York E*BD-F018 THRU 060 - page 11

    246819-BTG-H-0208 Unitary Products Group 11 EABD-F048S FL9(C,V)D20 FC/MC/PC60D 24 1600 46.0 35 .5 13.25 1 1.00 (F ,L)L8VC16 FC/PC60C 21 1500 45.5 35.1 13 .25 1 1.00 (F ,L)L8VC20 FC/PC60C 21 1600 46.0 35.4 13 .25 1 1.00 FL9(C,V)C16 FC/PC60C 21 1600 46.0 35 .5 13.25 1 1.00 FL9(C,V)C20 FC/PC60C 21 1600 46.0 34 .5 13.25 1 1.00 FL9(C,V)D20 HC60 24 1600 ...

  • York E*BD-F018 THRU 060 - page 12

    246819-BTG-H-0208 12 Unitary Products Group HEA TING PERFORMANCE - With Air Handler UNIT MODEL* AIR HANDLER COIL 1 MODEL ARI HEA T ING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD 1 & 3 PH 13 SEER HP WITH MA EABD-F018S MA08B FC/MC18B 18.0 3.62 1.46 10.5 2.28 1 .35 8.00 EABD-F024S M A 0 8 B F C / M C 2 4 B 2 3 . 03 . 4 41 . 9 61 3 . 12 . 3 ...

  • York E*BD-F018 THRU 060 - page 13

    246819-BTG-H-0208 Unitary Products Group 13 CP equals MBH output divided by (t otal KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating ou tput during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. 1 PH 13 SEER HP WITH A V - V ARIABLE SP ...

  • York E*BD-F018 THRU 060 - page 14

    246819-BTG-H-0208 14 Unitary Products Group CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. HEA TING PERFOR MANCE - Upflow Furnace C ...

  • York E*BD-F018 THRU 060 - page 15

    246819-BTG-H-0208 Unitary Products Group 15 HEA TING CAP ACITY - W ith V ariable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE COIL 1 MODEL ARI HEA T ING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD EABD-F018S (F ,L)L8V A12 FC/MC/PC18A 17.5 3.88 1.32 10 .0 2.42 1.21 8.60 FL9V A12 FC/MC/PC18A 17.6 3.82 1.35 10 .1 2.40 1.23 8.40 FL9(C,V)B12 ...

  • York E*BD-F018 THRU 060 - page 16

    246819-BTG-H-0208 16 Unitary Products Group CP equals MBH output divided by (to tal KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. EABD-F042S ( F , L ) L 8 V C 2 0 F C / ...

  • York E*BD-F018 THRU 060 - page 17

    246819-BTG-H-0208 Unitary Products Group 17 ACCESSORIES Refer to Price Manual for specific model numbers. St art Assist Kit (2SA067*) Blower Time Delay - A vailable to increase efficiency when installed. Installs on indoor section and maintains blower for approximately one minute a fter cooling thermostat has been satisfied. Hard St art Kit s - Pro ...

  • York E*BD-F018 THRU 060 - page 18

    246819-BTG-H-0208 18 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree bel ...

  • York E*BD-F018 THRU 060 - page 19

    246819-BTG-H-0208 Unitary Products Group 19 Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increase s by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York E*BD-F018 THRU 060 - page 20

    246819-BTG-H-0208 20 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree bel ...

  • York E*BD-F018 THRU 060 - page 21

    246819-BTG-H-0208 Unitary Products Group 21 Multipliers for determining th e performance with other indoor sections NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increase s by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree below ...

  • York E*BD-F018 THRU 060 - page 22

    246819-BTG-H-0208 22 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree bel ...

  • York E*BD-F018 THRU 060 - page 23

    246819-BTG-H-0208 Unitary Products Group 23 Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increase s by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York E*BD-F018 THRU 060 - page 24

    246819-BTG-H-0208 24 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree bel ...

  • York E*BD-F018 THRU 060 - page 25

    246819-BTG-H-0208 Unitary Products Group 25 Multipliers for determining the performance with other indoor sections . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO EABD-F018S EV APORA T OR COIL MODEL NO FC /MC/PC/UC18 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 450 600 750 MBTUH KW C.O.P . MBTUH KW C.O.P . MBTUH K ...

  • York E*BD-F018 THRU 060 - page 26

    246819-BTG-H-0208 26 Unitary Products Group Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO EABD-F024S EV APORA T OR COIL MODEL NO FC /MC/PC/UC24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 600 800 1000 MBTUH KW C.O.P . MBTUH KW C.O.P . MBTU H ...

  • York E*BD-F018 THRU 060 - page 27

    246819-BTG-H-0208 Unitary Products Group 27 Multipliers for determining the performance with other indoor sections . * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO E ABD-F030S, EABD-(T ,W)030S** EV APORA T OR COIL MODEL NO FC /MC/PC35 AIR TEMP . ENTERING OUTDOOR UNIT ...

  • York E*BD-F018 THRU 060 - page 28

    246819-BTG-H-0208 28 Unitary Products Group Multipliers for determining the perfo rman ce with other indoor sections. * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E ABD-F036S, EABD-(T ,W)036S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC48 AIR TEMP . ENTERING OUTDOOR U ...

  • York E*BD-F018 THRU 060 - page 29

    246819-BTG-H-0208 Unitary Products Group 29 Multipliers for determining the performance with other indoor sections . * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO E ABD-F042S, EABD-(T ,W)042S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC48 AIR TEMP . ENTERING OUTDOOR U ...

  • York E*BD-F018 THRU 060 - page 30

    246819-BTG-H-0208 30 Unitary Products Group Multipliers for determining the perfo rman ce with other indoor sections. * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E ABD-F048S, EABD-(T ,W)048S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC60 AIR TEMP . ENTERING OUTDOOR U ...

  • York E*BD-F018 THRU 060 - page 31

    246819-BTG-H-0208 Unitary Products Group 31 Multipliers for determining the performance with other indoor sections . * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO E ABD-F060S, EABD-(T ,W)060S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC60 AIR TEMP . ENTERING OUTDOOR U ...

  • York E*BD-F018 THRU 060 - page 32

    Subject to change without notice. Printed in U.S.A. 246819-BTG-H-0208 Copyright © by Unitary Products Group. 2008. Al l rights reserved. Supersedes: 246819-BTG-G-0607 Unitary 5005 Norman Product Y ork OK Group Drive 73069 NOTES ...

Produzent York Kategorie Heat Pump

Dokumente, die wir vom Produzenten des Geräts York E*BD-F018 THRU 060 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen York
- Bedienungsanleitungen E*BD-F018 THRU 060
- Produktkarten York
- Informationsbroschüren
- oder Energieetiketten York E*BD-F018 THRU 060
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung York E*BD-F018 THRU 060.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen York E*BD-F018 THRU 060, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen York E*BD-F018 THRU 060. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts York E*BD-F018 THRU 060 ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts York E*BD-F018 THRU 060, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von York E*BD-F018 THRU 060 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von York E*BD-F018 THRU 060 verständlich ist.

Eine gänzliche Bedienungsanleitung von York sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von York E*BD-F018 THRU 060 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von York E*BD-F018 THRU 060 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich York E*BD-F018 THRU 060, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts York E*BD-F018 THRU 060 - die uns die ersten Schritte während der Nutzung von York E*BD-F018 THRU 060 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit York E*BD-F018 THRU 060 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von York E*BD-F018 THRU 060 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich York E*BD-F018 THRU 060?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit York E*BD-F018 THRU 060 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit York E*BD-F018 THRU 060 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)